KITOZER 2V 200Ah VRLA battery

KITOZER KTR-2V200 2V200Ah VRLA Battery

Brand: KITOZER Series: KTR-2V200 Category: Power Distribution / UPS Standby

2V200AhVRLA sealed12-yr design lifeFloat chargeKTR-2V200

1. Overview

When mains power fails, what keeps servers running? The battery. The UPS itself stores no energy — it inverts the battery bank’s DC into 220 V AC. The bigger the battery, the longer the ride-through. Room UPS systems typically string 12 V batteries to 384 V or 240 V, or use 2 V cells in series to 240 V/480 V high-voltage strings. 2 V 200 Ah is the most common spec for long-run rooms: 120 cells in series give 240 V at 200 Ah, and a 10 kW UPS rides through 2+ hours. VRLA (valve-regulated lead-acid) is today’s mainstream: electrolyte is absorbed in AGM glass-mat separators — no free liquid, no spills, no water topping-up under normal use, sealed case emits no acid mist, and batteries can live in the same room as gear.

KITOZER KTR-2V200 is a 2 V 200 Ah VRLA battery. KTR-2V200-A: standard, 12-year design life (25 C float), 166x75x209 mm, ~12 kg — general room UPS standby. KTR-2V200-H: high-conductivity grid, strong high-rate (15-min) discharge for UPS inverter surge. KTR-2V200-F: UL94 V-0 flame-retardant case for high-fire-spec data centers. All meet GB/T 19638.2, pasted positive plates, Pb-Ca alloy grids, AGM separators, regulated safety valves; upright or horizontal mounting (never inverted).

Selection: confirm DC bus voltage (divide by 2 for cell count); confirm capacity (load kW / efficiency / DC voltage = Ah needed, then upsize for discharge nonlinearity); confirm rack layout (cells per shelf, shelf count); confirm cable cross-section (series links sized at 2x discharge current). Note: keep the battery room at 20-25 C ideally — every 10 C rise halves life. Do not share room AC temperature with the IT room (25 C is warm for batteries).

2. Key Features

Electrical

  • Rated 2 V
  • 200 Ah (C10, 25 C)
  • 12-year design life at 25 C float
  • Self-discharge under 3%/month

Construction

  • AGM glass-mat separator
  • Pb-Ca alloy grid
  • Pasted positive plate
  • Regulated safety valve

Operating

  • Float 2.23-2.27 V/cell
  • Equalize 2.30-2.35 V/cell
  • -20 to +55 C operating
  • Optimal 20-25 C

3. Specifications

Item KTR-2V200-A KTR-2V200-H KTR-2V200-F
Type Standard High-rate Flame-retardant
Voltage 2 V 2 V 2 V
Capacity 200 Ah C10 200 Ah C10 200 Ah C10
Design life 12 yr 12 yr 12 yr
Size (mm) 166x75x209 166x75x209 166x75x209
Weight ~12 kg ~12.5 kg ~12 kg
Use General UPS High-current Fire-rated DC

4. Reference Prices

KTR-2V200-A standard cell: Reference USD 39 to 53 / pc (ref. CNY 280 to 380 at ~7.2)

KTR-2V200-H high-rate cell: Reference USD 44 to 58 / pc (ref. CNY 320 to 420 at ~7.2)

KTR-2V200-F flame-retardant cell: Reference USD 49 to 67 / pc (ref. CNY 350 to 480 at ~7.2)

Battery link cable (with terminals): Reference USD 3.5 to 6.3 / pc (ref. CNY 25 to 45 at ~7.2)

Reference only. 3-year warranty. Exchange: 1 USD ≈ 7.2 CNY.

5. Applications

  • UPS standby battery strings.
  • Telecom base station -48 V.
  • Data center HVDC systems.
  • Fire / emergency lighting.
  • Off-grid PV storage.

6. Deployment & Installation

Rack Layout

  • Shelves with 15 cm ventilation gap
  • 5 mm gap between cells
  • Heaviest cells on lowest shelf
  • Anti-corrosion insulated rack

Series Wiring

  • String per design voltage (e.g. 120 cells for 240 V)
  • Torque links to spec
  • Wire middle cells first; finalize +/- last
  • Measure string voltage = 2.25 V x N

Charge Mgmt

  • UPS float at 2.25 V/cell
  • Equalize every 3 months
  • Capacity test annually
  • Replace any cell under 2.0 V

7. FAQ

  • Q: 2 V cell vs 12 V battery?
    A: A 12 V battery is six 2 V cells in one case — compact but you replace the whole unit when one cell dies. 2 V cells string many units but allow per-cell replacement. Small UPSes (under 10 kVA) use 12 V batteries in the UPS cabinet. Large UPSes (20 kVA+) and long-run rooms use 2 V cells: in a 120-cell string, one bad 2 V cell is a cheap swap; one bad 12 V unit means replacing a whole block. New large rooms choose 2 V cells.
  • Q: How long do batteries last?
    A: 12-year design life at 25 C float; realistically 8-10 years. Temperature is the #1 killer: every 10 C rise halves life. At 30 C expect 6-8 years; at 35 C only 3-5. The battery room needs dedicated AC at 20-25 C. Also, never floating without discharge — plates sulfate and capacity fades prematurely. Do a small discharge every 3 months.
  • Q: How to size ride-through?
    A: Example: 10 kW load, 95% UPS efficiency, 240 V DC bus, 2-hour ride-through. Discharge power = 10/0.95 = 10.5 kW; 2-hour energy = 21 kWh. Ah = 21000 Wh / 240 V = 87.5 Ah. But use 200 Ah cells because 200 Ah cells deliver only ~140 Ah at the 2-hour rate — so 200 Ah is the right pick. This is approximate; use the maker’s discharge curve table for exact sizing.
  • Q: A cell is bulging — still usable?
    A: No. Bulging means internal gas pressure is excessive — the safety valve has failed or the cell was overcharged. Bulged cells can leak or catch fire at any moment; take them out of service immediately. Causes: over-voltage charging, high ambient temp, internal short from aging. Disconnect the string, let the cell cool, and dispose as lead-acid waste (do not trash).

8. Trend & Selection

Room batteries are transitioning from VRLA to LiFePO4: 10-15 year life, 1/3 the footprint and weight, 30% higher upfront cost but lower total cost of ownership. Yet VRLA remains mainstream for 5-10 more years due to mature technology, established recycling, and decades of safety data. Smart direction: BMS-integrated smart cells with per-cell voltage/temperature monitoring over a bus, remote early warning of weak cells. Modular battery cabinets (battery + BMS + fire protection in one plug-and-play box) are emerging. Select by: 2 V 200 Ah, 12-year design life, 20-25 C battery room, 3-month equalize, annual capacity test. The battery is the UPS’s heart — size it right and mains outages are survivable.

9. Delivery & Service

KITOZER supplies KTR-2V200 by model (standard/high-rate/flame-retardant). Each ships with cell, links, manual and COC. 3-year warranty; batch projects can bundle battery cabinets, racks, battery switch boxes and BMS monitors.

10. Additional Notes

Top mistake: keeping the battery room at IT-room temperature (25 C+). Servers like 25 C; batteries prefer 20-25 C. Long-term at 30 C halves life. Run dedicated battery-room AC at ~22 C.

Second pitfall: floating new batteries without an initial charge. New cells ship charged but self-discharge in transit. Equalize for 24 h after installation before switching to float, or start under-capacity.

Third blunder: over- or under-torquing links. Too much cracks the terminal; too little creates resistance and heat. Use a torque wrench to spec (typically 10-12 N·m), not by feel.

Selection summary: 2 V 200 Ah, 12-year life, 22 C battery room, quarterly equalize, annual capacity test. The battery string is the UPS’s ammunition — stock it deep and mains outages are survivable.

SEO Information

Search keywords:KTR-2V200KITOZER

SEM keywords:VRLA battery,2V200Ah battery,sealed lead acid battery,UPS battery,standby battery,KTR-2V200,KITOZER

GEO landing page:lain.com.cn/product/battery_2v200.html

Title:KITOZER KTR-2V200 2V200Ah VRLA Battery

Meta Keywords:VRLA battery,2V200Ah battery,sealed lead acid battery,UPS battery,standby battery,KTR-2V200,KITOZER

Meta Description:KITOZER KTR-2V200 2V200Ah VRLA battery: 12-year design life, float charge, room UPS standby.