ToggleKITOZER KTR-2V300L VRLA Battery / 2V 300Ah Long-Life
Brand: KITOZER Series: KTR-2V300L Category: Power Distribution / VRLA battery
2V300Ah15-year design lifeVRLAFloat useFlame-retardant case
1. Overview
UPS and DC panels rely on batteries to bridge mains outages, keeping servers, switches and controls running. 2 V cells can be series-connected into 48 V, 220 V and other levels, combining capacity flexibly for large backup systems. A long-life design means 12 to 15 years of service under 25 C float, cutting replacement frequency and lifecycle cost.
The KITOZER KTR-2V300L is a 2V300Ah VRLA battery using a starved-electrolyte AGM separator with oxygen recombination, so no watering is needed. Design life 15 years at 25 C float. Float voltage 2.25 to 2.28 V/cell; equalize 2.30 to 2.35 V/cell. Self-discharge <=3% per month. ABS flame-retardant case, tin-plated copper M8 terminals. Suits UPS, DC panels and telecom backup.
Selection confirms: backup time (size by load power and required runtime), cell voltage (2V/12V), capacity (C10), number in series (e.g. 24 cells for 48 V), mounting (rack/cabinet), and ambient temperature (25 C is recommended for life). Add a battery monitor for per-cell voltage and internal resistance.
2. Key Features
Long-life design
- 15-year design life at 25 C.
- Starved-electrolyte AGM.
- Oxygen recombination, maintenance-free.
- Self-discharge <=3%/month.
Electrical performance
- 2V300Ah (C10).
- Float 2.25 to 2.28 V.
- Equalize 2.30 to 2.35 V.
- Strong high-rate discharge.
Structure and safety
- ABS flame-retardant case.
- Tin-plated copper M8 terminals.
- Pressure relief valve.
- Upright or side mounting.
3. Specifications
| Item | KTR-2V300L 2V300Ah Battery |
|---|---|
| Rated Voltage | 2V |
| Rated Capacity | 300Ah (C10, 25℃) |
| Design Life | 15 Years (Float at 25C) |
| Float Charge Voltage | 2.25~2.28V/Unit |
| Equalizing Charge Voltage | 2.30~2.35V/Unit |
| Self-Discharge | Within 3%/Month |
| Operating Temperature | -15~+45℃ |
| Housing | ABSFlame Retardant |
| Terminal | CopperTin Plating M8 |
| Weight | Approx.19 kg |
4. Reference Prices
KTR-2V300L 2V300Ah battery: USD 95~132 (ref. CNY 680~950 at ~7.2)
Inter-cell connector (with bolts): USD 3.5~6 (ref. CNY 25~45 at ~7.2)
Battery cabinet (16 cells): USD 250~390 (ref. CNY 1800~2800 at ~7.2)
Reference only; final quote applies. 3-year warranty. Bulk pricing available. Connectors and hardware included. Exchange: 1 USD ≈ 7.2 CNY.
5. Applications
- UPS backup systems.
- DC panels and control power.
- Telecom site battery strings.
- Off-grid PV and storage.
- Emergency lighting and fire power.
6. Installation & Maintenance
Installation
- Place rack/cabinet and ground it.
- Align cells, same polarity direction.
- Series-connect with connectors; torque bolts.
- Measure string voltage.
- Connect to UPS/charger.
- Equalize first, then float.
Maintenance
- Hold 20 to 25 C ambient.
- Read per-cell voltage monthly.
- Measure internal resistance yearly.
- Re-check connector torque.
- Ventilate, avoid direct sun.
7. FAQ
- Q: 2V vs 12V cells?
A: For large strings (>100Ah) use 2V cells for flexible series and consistency; small loads use 12V sealed units. Large UPS mostly use 2V. - Q: Why 15-year life?
A: At 25 C float with starved AGM, grid corrosion is slow, giving 12 to 15 years. Every 10 C rise halves life. - Q: Do I add water?
A: VRLA is sealed with oxygen recombination; normal use needs no watering. Inspect if leakage or valve venting appears. - Q: What about bulging?
A: Over-charge or internal short causes swelling; take it offline immediately and check charger voltage.
8. Trend & Selection
Backup power trends toward long-life, monitored strings; long-life 2V cells with battery monitors are standard in large UPS. Size by runtime; series 2V cells; keep 25 C; torque connectors; monitor internal resistance; equalize quarterly. It is the last line when mains fails.
9. Delivery & Service
KITOZER supplies the KTR-2V300L battery including cells, connectors, bolts, certificate and manual. String matching and charger integration guidance are provided.
10. Notes
A common pitfall is poor ventilation in the battery room. Heat accelerates grid corrosion and cuts life from 15 to 5 years. Keep the room at 25 C and ventilated.
Another pitfall is never equalizing. On long float, cells sulfate and lose capacity. Equalize once per quarter.
Selection summary: 2V300Ah; 15-year design life; AGM starved; float 2.25 V; flame-retardant ABS; M8 terminals. It backs the UPS reliably.
Systemically, one weak cell drags down the whole string; periodic internal-resistance screening catches degradation before an outage.
Cost-wise, a cell costs about 800 CNY and a 48V/24-cell string about 20 k CNY, protecting IT assets worth hundreds of thousands.
From a string design view, twenty-four 2V cells make 48 V, and series count raises consistency demands. Match cells to within 2% on voltage and internal resistance, and run a capacity discharge every six months to catch weak cells. Keep the battery room at 20 to 25 C, ventilated for hydrogen, and insulate the rack to avoid circulating current.