ToggleKITOZER KTR-AGM-12100 VRLA AGM Battery (12V 100Ah)
Brand: KITOZER Series: KTR-AGM-12100 Category: Battery / VRLA AGM
12V100AhAGM sealed10-year lifeUPS backupKTR-AGM-12100
1. Overview
The KITOZER KTR-AGM-12100 is a valve-regulated sealed lead-acid (VRLA) battery, 12V100Ah, using AGM (absorbent glass mat) separator technology. The electrolyte is absorbed in the glass mat, so it does not flow or leak and the cell can be mounted in any orientation; normal use is maintenance-free. It is used in UPS systems, DC panels, telecom sites and solar storage as backup power. When mains fails, the battery stack feeds the inverter, which converts DC to 220 V AC for servers, switches and cameras until the generator starts or mains returns.
Key specs: 12 V, 100 Ah (20-hr rate); Pb-Ca positive grid (corrosion-resistant); AGM glass-fiber separator; immobilized sulfuric acid electrolyte; M8 copper terminals; float voltage 13.5~13.8 V at 25 C; equalize 14.4~15.0 V; self-discharge <=3% per month at 25 C; design float life 10 years at 25 C; ABS flame-retardant case; 330x172x215 mm; about 30 kg.
Typical layout: a 10 kVA UPS with a 240 V DC bus needs 20 x 12 V cells in series (20×12 = 240 V), each 100 Ah, total 2400 VAh, giving about 15~20 minutes at full load. The 20 cells sit in a battery cabinet on shelves with insulating partitions. Positive to UPS DC+, negative to DC-, and the last cell’s negative bonds to ground.
2. Key Features
AGM maintenance-free
- Electrolyte held in glass mat.
- No leakage, no terminal corrosion.
- No water addition in normal use.
- Sealed with safety relief valve.
10-year design life
- Pb-Ca grid resists corrosion.
- 10-year float life at 25 C.
- Self-discharge <=3% / month.
- Suits long-term float standby.
High discharge current
- 100 Ah supports 1C (100 A).
- Handles UPS inrush.
- Internal resistance <=3 mOhm.
- Better cold-weather discharge than flooded.
Flame-retardant ABS
- UL94-V0 ABS case.
- Impact-resistant, leak-proof.
- M8 copper terminals, low contact resistance.
- Standard footprint, fits mainstream cabinets.
3. Specifications
| Item | Value |
|---|---|
| Model | KTR-AGM-12100 |
| Nominal voltage | 12 V |
| Rated capacity (20-hr) | 100 Ah |
| Design life (float, 25 C) | 10 years |
| Positive grid | Pb-Ca alloy |
| Separator | AGM glass-fiber |
| Electrolyte | Immobilized sulfuric acid (maintenance-free) |
| Terminals | M8 copper |
| Float voltage | 13.5~13.8 V (25 C) |
| Equalize voltage | 14.4~15.0 V (25 C) |
| Self-discharge | <=3% / month (25 C) |
| Operating temp | -15 to +50 C discharge / 0 to +40 C charge |
| Case | ABS flame-retardant |
| Dimensions (LxWxH) | 330x172x215 mm |
| Weight | about 30 kg |
4. Reference Price
KTR-AGM-12100 12V100Ah AGM: RMB 680~880 / unit (about USD 95~122)
KTR-AGM-1265 12V65Ah: RMB 420~560 / unit (about USD 58~78)
KTR-AGM-12200 12V200Ah: RMB 1180~1580 / unit (about USD 164~219)
Battery cabinet (holds 20 x 12V100Ah): RMB 800~1200 / unit (about USD 111~167)
Inter-cell link with lugs: RMB 25~40 / pc (about USD 3~6)
Battery monitor (12 cells): RMB 680~980 / unit (about USD 95~136)
Reference prices only; final price subject to quotation. (1 USD ≈ 7.2 CNY)
5. Applications
- UPS battery stacks.
- Substation DC panels and operating supplies.
- Telecom base stations and access rooms.
- Off-grid solar and residential storage.
- Elevator emergency lighting and fire power.
- Tunnel / harbor DC operating supplies.
- Data-center UPS battery banks.
6. Installation & Maintenance
Installation
- Level the cabinet, put an insulating mat underneath.
- Carry cells into the cabinet (30 kg each, two people).
- Align cells the same way, positives on one side.
- Add insulating partitions between shelves.
- Series-connect adjacent cells with copper links (+ to -).
- Torque M8 screws to 8~10 N·m; do not over-tighten.
- Measure the stack open-circuit voltage; should equal cell voltage x count +/-5%.
- Connect stack + / – to the UPS DC bus, then bond to ground.
- Verify polarity with a meter before energizing.
Maintenance
- Measure per-cell float voltage monthly.
- Quarterly measure stack voltage and charge current.
- Annually do a capacity test (30~50% discharge check).
- Half-yearly re-torque links.
- Keep cells dry; wipe with a damp cloth (not a feather duster).
- Hold ambient at 20~25 C (every 10 C halves life).
- If a cell reads below 13.2 V, equalize or replace it.
- Replace the whole stack at end of life (8~10 years); do not mix old and new.
7. FAQ
- Q:Runtime is short; can I add more cells?
A:No. The UPS DC bus voltage is fixed (e.g. 240 V); extra cells over-voltage the UPS. To extend runtime, upsamp the Ah rating (100 Ah to 200 Ah), not the count. Count sets voltage, Ah sets runtime. - Q:Can I mix old and new cells?
A:No. Old cells have high internal resistance and low capacity; they become the weak link and drag down the whole stack. During charging, old cells fill first while new ones are still low; during discharge, old cells empty first and get over-discharged. Replace the whole stack. - Q:A cell is bulging; can I keep using it?
A:No. Bulging means deformed plates and trapped gas; continued use risks leakage or rupture. De-energize and replace immediately; dispose of the old cell as hazardous waste (lead and acid). Bulging is caused by over-charge, high ambient temperature, or aging. - Q:How long can cells be stored before recharge?
A:AGM self-discharges <=3% / month. After 3 months about 90% remains, after 6 months about 80%. Install within 3 months of delivery; if stored over 6 months, equalize first (14.4 V for 24 h). Long-term storage needs a top-up every 6 months.
8. Industry Trends & Selection
The battery industry is shifting from lead-acid to LFP lithium, which is smaller, longer-lived (10+ years) and maintenance-free, but pricier. AGM lead-acid remains mainstream in UPS and DC panels thanks to mature technology, low cost and recycling. New AGM is evolving into flooded-style 2 V large cells up to 2000 Ah. Smart battery monitors (per-cell voltage modules) are standard in racks. Select cell count by the UPS bus (count = bus / 12 V) and Ah by runtime (Ah = load W x time h / bus V / inverter efficiency).
9. Delivery & Service
KITOZER sizes KTR-AGM cells and cabinets by UPS capacity and runtime, and provides interconnection drawings and monitor layouts. Delivery includes cells, links, manual and certificate. Install guidance and capacity-test support are covered; the cells carry a 3-year warranty.
10. Notes
A common pitfall is high ambient temperature. Battery life halves for every 10 C rise; a 35 C summer room can halve a 10-year design to 5 years. Keep the battery cabinet zone at 25 C, away from heat sources.
Another pitfall is insufficient link torque. M8 screws need 8~10 N·m; a hand screwdriver is not enough — use a torque wrench. High contact resistance causes heating and can burn terminals.
Selection summary: 12V100Ah; AGM; 10-year life; float 13.5~13.8 V; 25 C. The battery is the UPS granary; keys are temperature control, regular voltage checks, and whole-stack replacement.
Tip: do not throw old cells in the trash; they are hazardous waste (lead and acid). KITOZER recycles old cells and credits part of the new purchase. Transport upright with terminals insulated to prevent short-circuit fire.
SEO
Contact Us
KITOZER brand (professional data-center & low-voltage equipment supplier)
Tel/WeChat: +86 13922289957 | +86 18520668845
WHATSAPP: +86 19068534140
Web: lain.com.cn | gdlain.com