Brand: KITOZERãSeries: KTR-BT150ãCategory: Energy Storage / Battery
12V150AhGeldeep cycleUPS backupKTR-BT150
Table of Contents
Toggle1. Overview
The KITOZER KTR-BT150 is a 12V 150 Ah gel (GEL) valve-regulated lead-acid battery, designed for UPS, telecom base stations, solar storage and emergency lighting. Compared with standard lead-acid, gel batteries have gelled electrolyte (silica thickened), no free acid, no leakage, good thermal stability, and long deep-cycle life (up to 600 cycles @50% DoD) â ideal for long float charge and frequent discharge storage.
KTR-BT150 is rated 12V, 150 Ah (C20), weighing ~45 kg. Terminals are M8 copper bolt posts for series/parallel. Internally it uses AGM separators with gelled electrolyte; oxygen recombination efficiency â¥98%, no acid mist under normal use. Self-discharge is low (â¤3%/month @25â), allowing 6-month storage without recharge. Design life: 12 years float (25â), 600~1500 deep cycles.
Typical uses: room UPS battery strings (multi-series to 48V/240V/384V), telecom backup, off-grid PV storage, EPS emergency power, railway signaling. Strings are series-connected to match the UPS DC bus (e.g., 12VÃ20=240V).
2. Key Features
Gel electrolyte
- SiOâ thickened gel.
- No free acid / no leak.
- Good thermal stability.
- 600~1500 deep cycles.
VRLA sealed
- AGM separator.
- Oâ recombination â¥98%.
- No acid mist.
- Safety relief valve.
Long life
- 12-year float @25â.
- Self-discharge â¤3%/month.
- 6-month storage.
- Low-antimony grid.
Terminal & build
- M8 copper bolt terminals.
- Flame-retardant ABS case.
- Can lie on side.
- Explosion-proof vent plug.
3. Specifications
| Item | Parameter |
|---|---|
| Model | KTR-BT150 |
| Nominal voltage | 12V |
| Rated capacity (C20) | 150 Ah |
| Weight | ~45 kg |
| Dimensions | ~485Ã170Ã240 mm (incl. terminals) |
| Terminal | M8 copper bolt |
| Grid alloy | low-Sb Pb-Ca |
| Self-discharge | â¤3%/month (25â) |
| Float voltage | 13.5~13.8V (25â) |
| Equalize voltage | 14.4~14.9V (25â) |
| Design life | 12 yr float / 600~1500 cycles |
| Operating temp | -20~50â discharge / 0~40â charge |
4. Reference Prices
KTR-BT150 12V150 Ah gel battery:Ref. USD 125~208 / unit (CNY 900~1500 @7.2)
KTR-BT150 12V150 Ah (rack + cables kit):Ref. USD 167~250 / unit (CNY 1200~1800 @7.2)
KTR-BT150 old battery recycling credit:Ref. USD 14~28 / unit (per lead price)
Reference only; exchange: 1 USD ~ 7.2 CNY (Oct 2026).
5. Applications
- Room UPS battery string.
- Telecom base station backup.
- Off-grid PV storage.
- EPS emergency lighting.
- Railway / metro signaling backup.
6. Installation & Maintenance
Installation
- Install batteries in dedicated cabinet/rack.
- Determine series count by UPS DC voltage.
- Connect between cells with copper bars/cables.
- Torque terminals per manual (typically 8~10 N·m).
- Finally connect UPS DC bus +/-.
- Measure string voltage (e.g., 240V).
- Connect string to float charger.
- Charge 24~48 h before loading.
Maintenance
- Measure per-cell float voltage quarterly.
- Annual capacity discharge test.
- Inspect terminals for corrosion (apply Vaseline).
- Keep battery room 20~25â.
- Record per-cell internal resistance.
- Replace failed cells promptly (same model/batch).
7. FAQ
- Q:Gel vs AGM â choose?
A:AGM (starved electrolyte) suits high-frequency shallow cycles (UPS), lower cost; gel suits deep cycles and wide temps (PV/solar), longer life but pricier. Room UPS usually AGM suffices, but high-temp rooms (>30â) recommend gel. - Q:How long do batteries last?
A:Design float life 12 years at 25â, but actual life depends on temp and depth of discharge. Every 10â rise halves life; frequent deep discharge (>50% DoD) also shortens it. Room UPS batteries are typically replaced every 5~8 years. - Q:Can I mix old and new batteries?
A:No. Old and new cells differ in internal resistance and capacity; in series, the old cell over-charges and over-discharges, accelerating failure. Replace the whole string with same model/batch â mixed strings shorten overall life. - Q:Battery bulging â what to do?
A:Bulging means internal gas over-pressure, likely over-charge or high temp. Stop use immediately, disconnect, ventilate. Bulged batteries cannot be reused â replace them. Check float voltage (>13.8V indicates over-charge).
8. Trend & Selection
Batteries are shifting toward lithium (LFP) replacement â higher energy density, longer cycle life (>6000), smaller size, but higher cost. VRLA gel remains widely used for cost-effectiveness and safety (no thermal runaway). Hybrid strings (lead+Li) and smart BMS are trends.
9. Delivery & Service
KITOZER sizes KTR-BT150 strings by UPS power and backup time, providing string-count calculation and rack dimension advice. Delivery includes batteries (per qty), connecting copper bars, insulation sleeves, certificate and install manual. Warranty covers first discharge test guidance.
10. Additional Notes
A common pitfall is uncontrolled battery-room temperature. Temperature is the #1 factor in battery life â above 25â, every 10â rise halves life. The battery room must have AC, kept at 20~25â.
Another pitfall is omitting Vaseline on terminals. Copper terminals oxidize in humid air, increasing contact resistance and causing over-charge. Apply Vaseline or conductive grease after installation.
Also size the string for the actual backup time, not the UPS rated kVA. A 20 kVA UPS with 10-min backup needs a different string than one with 30-min backup. Calculate required Ah from load watts à backup hours / battery voltage, plus a 20% margin.
Selection summary: 12V150 Ah gel; 12-yr float; M8 terminals; 600+ deep cycles; low self-discharge. The battery is the UPS’s energy warehouse â right capacity, controlled temp, periodic voltage checks, holds through outages.
Contact Us