1. Overview
The KITOZER KTR-CAD cold aisle sliding door is the end door at both ends of a modular cold aisle containment system. It seals the cold inlet side away from the hot aisle, forming a closed low-temperature corridor. The idea of cold aisle containment is simple: let CRAH-cooled air pass only through server intakes, without mixing and recirculating with hot exhaust. This raises cooling efficiency and lowers PUE. The end door must seal against temperature yet still allow personnel entry, maintenance access and fire egress.
KTR-CAD uses an anodized aluminum profile frame with tempered glass panels. It is light, strong and clean looking. The panels slide horizontally along top and bottom tracks, taking no swing space inside or outside the aisle — important where aisles are only 1.2~1.5 m wide. You can choose manual sliding or automatic sensor sliding. Manual relies on people with hydraulic buffers and latch stops; automatic adds a DC motor, microwave/IR sensors and an emergency break-glass button, opening on approach and unlocking on power loss or fire alarm.
The door connects to the cold aisle roof, side panels and smoke vent panels with dedicated profiles and EPDM gaskets, preventing hot/cold air leakage. The glass is tempered safety glass, clear or frosted, so operators can see server LEDs without glare. Card readers, exit buttons and break-glass stations can be integrated and linked to the access control system. The whole door is custom-sized to the rack row width and delivered as a set with the containment system.
2. Key Features
Horizontal sliding, space-saving
- Panels slide left/right; no swing space needed.
- Top and bottom double-track design runs smoothly.
- Hydraulic buffer decelerates at end of travel.
Sealed against temperature
- EPDM gaskets on profiles and glass joints.
- Seamless to roof, side and vent panels.
- Reduces hot/cold mixing and improves containment.
Manual or automatic
- Automatic: DC motor plus microwave/IR sensors.
- Emergency release; auto-unlock on fire/power loss.
- Manual: push-pull with latch stop.
Safety and integration
- Tempered safety glass, blunt fragments on break.
- Integrates card reader and exit button.
- Fire alarm link: door auto-unlocks for egress.
3. Specifications
| Item | Manual KTR-CAD-M | Automatic KTR-CAD-A |
|---|---|---|
| Panel type | single/double sliding | single/double auto sliding |
| Frame | anodized aluminum | anodized aluminum |
| Glass | 8 mm tempered | 8 mm tempered |
| Operation | manual push-pull | motorized, sensor auto-open |
| Sensor | — | microwave + IR dual |
| Power | — | AC 220 V, backup battery |
| Open speed | manual | 300~500 mm/s adjustable |
| Emergency release | mechanical push bar | break-glass + fire auto-release |
| Interfaces | card reader, exit button | access control, fire signal |
| Size | custom to rack row | custom to rack row |
4. Reference Prices
KTR-CAD-M manual end door (double tempered glass): Reference USD 417~833 / door (ref. CNY 3k~6k at ~7.2)
KTR-CAD-A automatic sensor end door (motor + sensor + fire link): Reference USD 1,111~2,500 / door (ref. CNY 8k~18k at ~7.2)
Reference only; final quote depends on panel count, frosted/clear, access and fire linking, custom width. Bulk negotiable. Exchange: 1 USD ~ 7.2 CNY (Oct 2026).
5. Applications
- End doors for new modular cold aisle rooms.
- Retrofit of existing rack rows into cold containment.
- Micro-module and container data centers.
- IDCs where PUE targets demand hot/cold separation.
6. Installation & Maintenance
Installation
- Measure rack row clear width; custom-size door and profiles.
- Fit top and bottom tracks; level and fix to floor and rack tops.
- Hang panels; adjust track clearance and buffer force.
- For automatic units, wire motor, sensors, access and fire signals.
- Close door and verify gasket seal, no visible gaps.
Maintenance
- Clean tracks and rollers for smooth sliding.
- Check sensor sensitivity and break-glass button.
- Inspect backup battery annually on auto units.
- Replace aged gaskets to preserve sealing.
7. FAQ
- Q: Why sliding rather than swing door?
A: Aisles are only 1.2~1.5 m; a swing door blocks the aisle, while sliding opens sideways in no space. - Q: What happens on power loss?
A: A backup battery allows several more cycles; on fire alarm the door auto-unlocks and can be pushed open for egress. - Q: Is a glass door a safety concern?
A: Tempered safety glass breaks into blunt fragments; choose frosted or apply film for privacy. - Q: Can it link to access control?
A: Yes; the door reserves card reader, exit button and electric lock interfaces for unified room access management.
8. Trend & Selection
Cold aisle containment is now standard in new rooms, and the end door is the “opening” of the system — its sealing and safety determine containment effectiveness. Choose manual or automatic: high-traffic main rows want automatic sensor doors; rarely used tail rows can use manual. Automatic units must confirm fire-link and emergency release requirements so the door releases on fire. Size strictly to rack row width and deliver with roof and side panels to avoid on-site air gaps.
9. Delivery & Service
KITOZER provides measurement, custom fabrication and install guidance for end doors. We can bundle the door with cold aisle roof, side panels and smoke vent panels under one design and one delivery. Delivery includes profile drawings, panel assembly notes and auto-door wiring diagrams. Warranty covers rollers, gaskets and motors; we can commission sensor sensitivity and fire-link logic on site.
10. Additional Notes
Cold aisle containment is not simply covering the aisle; it makes cold air travel the shortest path into servers. If the end door leaks, some cold air bypasses servers through side gaps and recirculates to the hot aisle, wasting cooling load. Profile joints, gasket seals and connections to roof/side panels must be built to drawing, with no visible light or air gaps.
Automatic doors in a data center have higher safety demands than ordinary interior doors. The room has few people but lots of equipment: the door must open promptly on approach yet release when people need to leave in a fire or power loss. That is why automatic units use dual microwave+IR sensing to avoid false triggers, add break-glass stations and fire-link modules, and keep a backup battery. These add cost but are essential for egress and anti-trap behavior.
Selection: rarely used tail rows pick KTR-CAD-M manual double doors; high-traffic rows pick KTR-CAD-A automatic sensor doors and must connect to fire alarm. Choose clear or frosted glass per management needs, and place card readers at a uniform room height. Either way, design the door as a set with roof and side panels so the whole containment stays tight.
SEO Information
Search keywords:cold aisle doorsliding dooraisle end doorautomatic sliding doortempered glass doorcold aisle containmentKTR-CADKITOZER
SEM keywords:cold aisle sliding door, cold aisle end door price, automatic sliding door data center, cold aisle glass door, KTR-CAD, KITOZER
GEO landing page:lain.com.cn/product/ktr-cad-cold-aisle-sliding-door.html
Title:KITOZER KTR-CAD Cold Aisle Sliding Door (Manual / Automatic)
Meta Keywords:cold aisle door,sliding door,aisle end door,automatic sliding door,tempered glass door,cold aisle containment,KTR-CAD,KITOZER
Meta Description:KITOZER KTR-CAD cold aisle sliding door, aluminum frame with tempered glass, manual or automatic sliding, paired with cold aisle roof and side panels to separate hot and cold airflow.
Anchor: KITOZER by Guangzhou Laian · Cold aisle containment solutions
Contact Us
Guangzhou Laian Intelligent System Development Co., Ltd. (KITOZER brand)
Tel/WeChat: +86 13922289957 | +86 18520668845
WHATSAPP: +86 19068534140
Web: lain.com.cn | gdlain.com