ToggleKITOZER KTR-CB2 T2 Tinned Copper Grounding Busbar
Brand: KITOZER Series: KTR-CB2 Category: Power Distribution / Grounding Bonding
T2 coppergrounding bartinnedequipotentialKTR-CB2
1. Overview
KITOZER KTR-CB2 is the central bonding bar of the room’s equipotential grounding system — a T2 pure-copper bar that collects every equipment ground (racks, UPS, distribution, cable tray, raised-floor supports) and ties them through the main ground conductor to the building earth electrode. It is the common point of grounding, ensuring all equipment sits at the same potential so lightning or leakage current cannot create a voltage difference that breaks insulation.
“T2 copper” means ≥99.9% pure copper — high conductivity, ductile, and unlike galvanized steel it does not rust. Room grounding must use pure copper; ordinary galvanized flat iron cannot replace it — flat iron oxidizes, has high contact resistance and is unreliable long-term. The bar is usually tinned (grey-white) to stop copper from oxidizing black, lower contact resistance and make bolted joints easy. Cross-section is chosen by surge current: small room 30x3mm, mid 40x4mm, large/IDC 50×5 or even 80x8mm.
KTR-CB2 has a row of terminal holes (M6/M8) for equipment ground wires (BVR yellow-green flexible cable). The bar is mounted on insulators (resin/ceramic) on the wall or beside racks — it must not touch the wall directly (it is insulated, grounded only at the designated point). Bar-to-bar joints use tinned copper splice plates and bolts; bends use pre-formed elbows. The whole bar is one equipotential grid, finally bonded to the building main ground terminal with a ≥95mm2 copper cable.
2. Key Features
Material & sizes
- T2 copper, ≥99.9% Cu, conductivity ≥97% IACS.
- Tinned surface, anti-oxidation, low contact resistance.
- Common sections 30×3, 40×4, 50×5 mm.
- Standard 3m/bar; cut-to-length available.
Structure & joints
- Equally spaced terminal holes (M6/M8) with copper bolts.
- Insulator mounts (resin/ceramic), isolated from wall.
- Bar joints via tinned copper splice plate + bolts.
- Heat-shrink cover to prevent accidental short.
Electrical role
- Equipotential collection, all gear at one potential.
- Diverts lightning, leakage and static current to earth.
- Reduces inter-equipment potential difference.
- Grounding resistance ≤1 ohm (combined bonding).
3. Specifications
| Item | KTR-CB2-303 | KTR-CB2-404 | KTR-CB2-505 |
|---|---|---|---|
| Section WxT | 30x3mm | 40x4mm | 50x5mm |
| Material | T2 copper | T2 copper | T2 copper |
| Finish | Tinned | Tinned | Tinned |
| Standard length | 3m/bar | 3m/bar | 3m/bar |
| Terminal holes | M6 | M6/M8 | M8 |
| Ground resist. | ≤1 ohm | ≤1 ohm | ≤1 ohm |
| Best for | small room | mid room | large/IDC |
4. Reference Prices
KTR-CB2-303 30x3mm tinned copper bar (3m, drilled, incl. insulators): Reference USD 17~25 / bar (ref. CNY 120~180 at ~7.2)
KTR-CB2-505 50x5mm tinned copper bar (large section, cut/drilled, incl. splice parts): Reference USD 42~69 / bar (ref. CNY 300~500 at ~7.2)
Reference only; final quote depends on section, length, tinning, hole count and accessories (insulators/splice plates/heat-shrink). Copper price fluctuates; quotes float with daily copper. Exchange: 1 USD ≈ 7.2 CNY (Oct 2026).
5. Applications
- Room equipotential busbar, rack ground collection.
- UPS, distribution and row-cabinet PE bonding.
- Metal cable tray and raised-floor support grounding.
- Lightning protection and SPD surge-diversion busbar.
- Lab, medical and precision-instrument equipotential.
6. Installation & Maintenance
Installation
- Locate the bar per the room ground drawing (along wall or rack row).
- Fix insulators; rest the bar on them.
- Join bars with splice plate + bolts; adequate contact area.
- Connect equipment grounds (BVR yellow-green) to bar holes; add washer and spring lock.
- Main ground: ≥95mm2 copper cable to building main ground terminal.
- Measure ground resistance; target ≤1 ohm (combined).
- Fit heat-shrink cover to prevent accidental contact.
Maintenance
- Annual ground-resistance test; investigate high readings for rust/looseness.
- Re-torque bolts after vibration.
- Clean or replace tinned sections that blacken or peel.
- New equipment grounds to the bar directly; never daisy-chain.
- Check SPD and bar bonds after thunderstorms.
7. FAQ
- Q: Can galvanized flat iron replace the copper bar?
A: Room equipotential should use copper. Galvanized flat iron has lower conductivity, oxidizes and its contact resistance grows — it is only for buried earth electrodes. Indoor busbar must be copper for long-term reliability. - Q: What section is needed?
A: By code: small 30×3, mid 40×4, large/IDC 50×5 up. Too small and surge capacity fails — the bar may burn through in a strike. When in doubt, go bigger. - Q: What ground resistance is acceptable?
A: Room combined bonding ≤1 ohm (shared with building, lightning and power systems). Standalone legacy code ≤4 ohm. Test with a ground-resistance tester before each rainy season. - Q: Why insulate the bar from the wall?
A: The bar is an equipotential bus grounded at exactly one point. Direct contact with wall or other metal creates stray-current loops and interference. Mount on insulators and ground only at the designated point.
8. Trend & Selection
Room grounding moves toward an “equipotential grid + combined bonding”: no separate earth electrode, but room, lightning, power and IT grounds all bonded to the building combined grid, with copper bar as the indoor bus. Trends: prefabricated bars (factory-drilled, bent, numbered, bolted on site), tinned anti-oxidation, online ground-resistance monitoring. Selection: bigger section is safer; must be tinned; insulate; main ground cable ≥95mm2; test resistance yearly; buy bolts/washers/heat-shrink together.
9. Delivery & Service
KITOZER provides bar selection and cut-to-length: from the room ground drawing we cut length, drill holes and form elbows, with insulators and splice parts. Delivery includes copper bar, insulators, bolts/washers, heat-shrink and install note. Bundled with equipotential box (KTR-EPB), SPD and earth electrode.
10. Additional Notes
The most common pitfall is “daisy-chained equipment grounds.” Equipment A’s ground runs through B’s ground to the bar — if the middle joint loosens, everything after it loses ground. Every piece of equipment must run its own ground wire to the bar.
The second pitfall: “untinned copper oxidizes in years.” Bare copper turns black in air, contact resistance rises, bolted joints heat up. Indoor bars must be tinned, or cleaned and coated with conductive grease periodically.
Third: “no resistance testing.” The earth electrode loosens or corrodes over years; resistance climbs from 1 to 10 ohms and equipment still gets struck. Test yearly; if high, add resistance-lowering compound or extra electrodes.
Selection summary: tinned copper, adequate section, individual grounds, yearly resistance test. The ground bar is invisible until lightning strikes — bonded well, equipment stays safe.
SEO Information
Search keywords:grounding busbarT2 copper barequipotential bondingtinned copper busbardata center ground barKTR-CB2KITOZER
SEM keywords:copper grounding busbar price,T2 copper bar supplier,data center equipotential bar,KTR-CB2,KITOZER
GEO landing page:lain.com.cn/product/ktr-cb2-t2-copper-grounding-busbar.html
Title:KITOZER KTR-CB2 T2 Tinned Copper Grounding Busbar
Meta Keywords:grounding busbar,T2 copper bar,equipotential bonding bar,tinned copper busbar,data center ground bar,KTR-CB2,KITOZER
Meta Description:KITOZER KTR-CB2 T2 tinned copper grounding busbar, 30×3/40×4/50x5mm, for data center equipotential bonding and rack grounding connections.