ToggleKITOZER KTR-CO2-NDIR CO2 Sensor (NDIR, RS485, 0-5000ppm)
Brand: KITOZER Series: KTR-CO2-NDIR Category: Environmental Monitoring / CO2 Sensor
NDIR0-5000ppm+/-50ppmRS485KTR-CO2-NDIR
1. Overview
A classroom full of students or a windowless meeting room drives CO2 up from the outdoor 400 ppm to 1500 or even 2500 ppm. Above 1000 ppm people feel drowsy; above 2000 ppm, headaches. Demand-controlled ventilation uses CO2 to set airflow: open wide when crowded, idle when empty — fresh air and energy savings at once. The KITOZER KTR-CO2-NDIR uses non-dispersive infrared (NDIR), more accurate and longer-lived than early semiconductor sensors. It outputs RS485 Modbus to a building controller or fresh-air unit, modulating the damper.
Key specs: dual-channel NDIR (reference + measure); range 0~5000 ppm; accuracy +/-(50 ppm + 3% reading); repeatability +/-20 ppm; T90 <=60 s; warm-up 3 min; RS485 Modbus-RTU at 9600 bps; DC12~24 V, <=1 W; optional 0-10 V / 4-20 mA analog out; LCD shows CO2 and temperature; wall-mount; ABS case; 0~50 C operating; NDIR lamp life 15 years.
Typical use: a 60-seat classroom has one KTR-CO2-NDIR at 1.5 m on the wall, RS485 to the DDC. The DDC opens the fresh-air damper to 50% above 1000 ppm, 100% above 1500 ppm, and backs off to 20% below 800 ppm. CO2 rises to 1200 ppm in class and the damper opens; after school CO2 falls to 500 ppm and airflow drops to minimum, saving energy.
2. Key Features
Dual-channel NDIR
- NDIR principle.
- Dual channel compensates lamp aging.
- Accuracy +/-(50 ppm + 3%).
- 15-year drift-free life.
RS485 + analog
- Modbus-RTU digital.
- Optional 0-10V / 4-20mA.
- Direct to fresh-air controller.
- Daisy-chain bus.
LCD display
- On-site CO2 readout.
- Temperature on same screen.
- Backlight optional.
- Address set by keys.
Long life
- NDIR lamp 15 years.
- No consumables.
- No annual calibration drift (<=20 ppm/yr).
- Auto baseline calibration (optional).
3. Specifications
| Item | Value |
|---|---|
| Model | KTR-CO2-NDIR |
| Principle | NDIR dual-channel |
| Range | 0~5000 ppm |
| Accuracy | +/-(50 ppm + 3% reading) |
| Repeatability | +/-20 ppm |
| Response T90 | <=60 s |
| Warm-up | 3 min |
| Comm | RS485 Modbus-RTU (9600 bps) |
| Analog out | 0-10V / 4-20mA (optional) |
| Power | DC12~24V |
| Power consumption | <=1 W |
| Display | LCD (CO2 + T) |
| Mounting | Wall 1.5 m |
| Case | ABS |
| Operating temp | 0~50 C |
| Lamp life | 15 years |
4. Reference Price
KTR-CO2-NDIR RS485 with LCD: RMB 380~520 / unit (about USD 53~72)
KTR-CO2-NDIR-AO analog out (0-10V/4-20mA): RMB 450~620 / unit (about USD 63~86)
KTR-CO2-NDIR-10K 0-10000 ppm industrial: RMB 580~780 / unit (about USD 81~108)
KTR-CO2-T T+RH+CO2 3-in-1: RMB 520~720 / unit (about USD 72~100)
8-channel RS485 logger: RMB 280~420 / unit (about USD 39~58)
Damper actuator (24V): RMB 150~220 / pc (about USD 21~31)
Reference prices only; final price subject to quotation. (1 USD ≈ 7.2 CNY)
5. Applications
- Classroom fresh-air control.
- Office meeting-room air quality.
- Underground car park CO monitoring.
- Greenhouse CO2 enrichment.
- Dense lab ventilation.
- Hospital ward air quality.
- Data-center rack inlet air.
6. Installation & Maintenance
Installation
- Wall-mount at 1.5 m, away from AC outlets, doors and windows.
- Fix the 86-box base.
- DC12~24V to V+/V-.
- RVSP shielded pair to RS485 A/B.
- Add 120 ohm terminator at the last unit.
- Clip the sensor onto the base.
- Warm up 3 min; LCD shows readings.
- Scan Modbus addresses from the DDC.
Maintenance
- Blow the inlet with compressed air quarterly (dust).
- Annual two-point calibration with 500/2000 ppm gas.
- NDIR lamp lives 15 years; replace the whole unit at end.
- Do not open the optical cavity (calibration is lost).
- If reading sticks at 400 ppm, check the lamp.
- Do not reverse RS485 A/B.
- Do not mount in restrooms (ammonia interferes).
- Set 100 ppm hysteresis on fresh-air thresholds.
7. FAQ
- Q:NDIR vs semiconductor CO2 sensor?
A:Semiconductor (Metal-oxide) reads via resistance change; short life (2~3 years), drift, and cross-sensitivity to alcohol and hydrogen. NDIR reads via infrared absorption; accurate, 15-year life, no cross-interference. Buildings and classrooms choose NDIR; cheap consumer gear uses semiconductor. - Q:New sensor reads 400 ppm, is it right?
A:Outdoor fresh air is about 420 ppm. A new sensor unpacked indoors reading 400~500 ppm is normal. If a crowded room still reads 400, the sensor is bad or the baseline drifted — recalibrate. - Q:How often to calibrate?
A:NDIR drifts under 20 ppm/year; a two-point calibration at a metrology lab annually is recommended. Units with auto-baseline (parked outdoors at 400 ppm for hours) can go 3 years. - Q:How many sensors per fresh-air controller?
A:One RS485 bus handles 32 units; practically stay under 20. Large halls (gymnasiums) use one per 500 m2; small rooms use one each.
8. Industry Trends & Selection
CO2 sensors are moving from single CO2 to multi-parameter (CO2 + T/RH + PM2.5 + VOC). Communications are upgrading from RS485 to BACnet / Modbus TCP / LoRa wireless, plugging straight into building automation. NDIR miniaturization has dropped prices from 1000 to the 300 RMB range, enabling consumer fresh-air units. CO2-linked ventilation is becoming standard in schools and offices. Choose NDIR for buildings, semiconductor for cheap consumer gear; choose RS485 or analog by controller; choose with-display or blind by need. Classrooms and offices prefer the with-display NDIR so people can see the number.
9. Delivery & Service
KITOZER sizes KTR-CO2-NDIR sensors by room area and fresh-air interface, and provides Modbus address maps and control logic advice. Delivery includes sensor, base, manual and certificate. Out-of-tolerance readings are recalibrated or replaced free under warranty.
10. Notes
A common pitfall is mounting the sensor by a door or window. Open windows pull in fresh air and the sensor reads low, which does not represent the occupied room. Mount mid-room at breathing height (1.2~1.5 m), away from supply outlets and openings.
Another pitfall is a too-sensitive linkage. A damper that snaps open at 1000 ppm and shut at 900 ppm cycles dozens of times a day and wears out the actuator. Set two thresholds: 1000 ppm opens 50%, 1500 ppm opens fully, 800 ppm backs off to minimum, with a 100 ppm dead band between.
Selection summary: NDIR; 0-5000 ppm; RS485; LCD; wall-mount. The CO2 sensor is the room’s air-quality meter; keys are breathing-height placement, hysteresis on the linkage, and periodic calibration.
Tip: the first 3 minutes after power-up the reading drifts as the NDIR lamp stabilizes — it is not broken. Record readings after 3 minutes when stable.