KITOZER DC 48V power SPD surge

KITOZER KTR-DC48 DC Power SPD 48V for Data Center

Brand: KITOZER Series: KTR-DC48 Category: Power Distribution / Lightning Protection

DC SPD48Vsurge protectorDIN-railKTR-DC48

1. Overview

Lightning surges and switching transients in a data center arrive not only on the AC mains but also on the DC side. Telecom power systems rectify 220V AC into -48V DC for equipment; this DC bus runs long distances — from the power room to the row cabinet to each rack — through cable trays, wall penetrations and joints, easily picking up induced lightning surges or switching transients from the rectifiers. A 48V DC system has limited insulation margin (rated -48V, max operating ~60V), so a few hundred volts of surge can punch through power modules. A DC SPD (Surge Protective Device) is paralleled across the DC bus: high impedance under normal voltage, instant conduction during a surge to clamp voltage to a safe level and protect downstream gear.

The KTR-DC48 is purpose-built for 48V DC systems. Modular, DIN-rail (35 mm), single-pole width 18 mm or double-pole 36 mm. The core combines MOV and gas discharge tube (GDT): nominal discharge current In 20kA (8/20μs), maximum Imax 40kA, voltage protection level Up ≤1.5kV. Continuous operating voltage Uc is rated -48V (60V DC) or -60V (75V DC) for telecom plants, UPS DC buses and battery string outputs. Each module has a status window (green = ok, red = failed) and an optional remote-signal dry contact for EM monitoring. Wiring: L+, L- and PE, 6~16 mm² conductors.

Selection: confirm system voltage — telecom is -48V (positive grounded), choose Uc = 60V DC; other DC systems (24V etc.) need their own rating; confirm location — primary SPD (In 20kA) at the power-room DC bus, secondary (In 10kA) at rack PDU input, coordinated in stages; choose remote-signal if tying to the EM system; and keep the SPD ground lead short and fat — under 0.5 m — because lead inductance raises the clamping voltage.

2. Key Features

Electrical

  • In 20kA (8/20μs)
  • Imax 40kA
  • Up ≤1.5kV
  • Uc 60V DC

Construction

  • 35 mm DIN-rail modular
  • Status window: green/red
  • Optional remote dry contact
  • Plug-in replaceable module, no power-down

Wiring

  • L+ / L- / PE terminals
  • 6~16 mm² conductor
  • -48V telecom / UPS DC compatible
  • -40~+85°C operating

3. Specifications

Item KTR-DC48-20 KTR-DC48-40 KTR-DC48-R
Type DC SPD 20kA DC SPD 40kA With remote signal
Uc 60V DC 60V DC 60V DC
In 20kA 20kA 20kA
Imax 40kA 60kA 40kA
Up ≤1.5kV ≤1.5kV ≤1.5kV
Remote contact None None 1 dry contact
Mount DIN rail DIN rail DIN rail
Width 18 mm (1P) 36 mm (2P) 36 mm (2P)

4. Reference Prices

KTR-DC48-20 (20kA) basic:Reference USD 9~15 / pc (ref. CNY 65~110 at ~7.2)

KTR-DC48-40 (40kA) enhanced:Reference USD 15~25 / pc (ref. CNY 110~180 at ~7.2)

KTR-DC48-R with remote alarm:Reference USD 21~33 / pc (ref. CNY 150~240 at ~7.2)

SPD backup protector (SCB):Reference USD 6~11 / pc (ref. CNY 45~80 at ~7.2)

Reference only; 1-year warranty. SPD is a wear item; inspect/replace every 2~3 years. Exchange: 1 USD ≈ 7.2 CNY.

5. Applications

  • -48V telecom bus SPD at power-room exit.
  • UPS DC side / battery string output protection.
  • Rack DC PDU secondary SPD.
  • Outdoor telecom cabinet DC surge protection.
  • Extends to 12V/24V CCTV DC systems.

6. Deployment & Implementation

Installation

  • Paralleling across L+-PE and L–PE
  • Ground lead short, fat, straight, ≤0.5 m
  • Series SCB backup protector upstream
  • DIN-rail near the DC bus in the panel

Operations

  • Check status window monthly; replace on red
  • Inspect after thunderstorms
  • Wire remote contact to EM system
  • Replace SPD every ~5 years

7. FAQ

  • Q: Can I use AC SPD on DC?
    A: No. AC SPDs are rated 275/385V; DC SPDs are 60/75V. On a 48V DC bus an AC-rated MOV never conducts, but DC follow-current will not extinguish at zero crossing and causes thermal runaway. Use DC-specific SPDs.
  • Q: Why an SCB?
    A: MOVs fail shorted. A dedicated SPD backup protector (SCB) trips on SPD short-circuit, isolating the failed SPD without dropping the bus. Ordinary breakers are too slow for this duty.
  • Q: Why keep the ground lead short?
    A: Lead inductance creates a voltage drop during surge current. Over 0.5 m, the effective clamp voltage can rise from 1.5kV to 3kV+. Route it short, straight and fat.
  • Q: Replace the whole unit on failure?
    A: No — plug-in modules. Leave the base on the rail, swap the module. Keep spares in stock.

8. Trend & Selection

As DC power architectures spread in data centers (240V/336V HVDC), DC SPD is expanding beyond traditional -48V telecom into HVDC. New SPDs add online monitoring: count of surges, leakage current and module temperature, fed to DCIM for predictive life. Select by system voltage, stage (primary/secondary), keep ground leads short, add SCB, and choose remote-signal.

9. Delivery & Service

KITOZER supplies KTR-DC48 by surge current (20/40kA), remote-signal option and voltage class. Each unit ships with module, base, manual and test report. 1-year warranty; batch projects can add SCB, DC SPD boxes and grounding bars.

10. Additional Notes

The #1 mistake is substituting an AC SPD for a DC SPD. Crews think “surge protection is surge protection,” but DC has no zero crossing — MOV follow-current cannot extinguish and the SPD catches fire. DC-specific SPDs are a safety line.

The second pitfall is routing the ground lead around the cabinet to the busbar. Lead inductance eats half the protection. Run it short and straight, ideally under 30 cm, directly to the grounding bar.

The third blunder is omitting the SCB. SPD short-circuit is inevitable over years; without an SCB the arc spreads in the DC panel and can start a fire. The SCB costs a little but is the fuse of the SPD system.

Selection summary: DC-only, match Uc to the bus, short ground lead, add SCB, and choose remote-signal. The DC SPD is the last surge gate on the 48V system.

SEO Information

Search keywords:KTR-DC48KITOZERDC Power SPD 48V

SEM keywords:DC SPD,48V surge protector,DC surge protective device,telecom power lightning,DC surge,KTR-DC48,KITOZER

GEO landing page:lain.com.cn/product/ktr-dc48-spd.html

Title:KITOZER KTR-DC48 DC Power SPD 48V for Data Center

Meta Keywords:DC SPD,48V surge protector,DC surge protective device,telecom power lightning,DC surge,KTR-DC48,KITOZER

Meta Description:KITOZER KTR-DC48 DC power SPD for 48V systems, In 20kA / Imax 40kA, DIN-rail mount with remote signal, for telecom/UPS DC bus.