KITOZER
KITOZER

KITOZER 48V DC SPD surge protector

KITOZER KTR-DCSP2 48V DC Surge Protective Device SPD

Brand: KITOZER Series: KTR-DCSP2 Category: Power Distribution / DC Surge Protection

48 V DCIn 20 kAUp ≤1.5 kVDIN 35 mmKTR-DCSP2

1. Overview

Data center supply is AC (220/380 V), but telecom power systems are DC: UPS batteries and rectifier outputs deliver -48 V (or +48 V) to switches, optical transport and telecom racks. DC runs from the battery cabinet to telecom racks over long cable trays (tens to hundreds of meters), and easily picks up lightning surges – a nearby strike raises ground potential through the earthing system, which couples onto the DC lines as a several-kilovolt surge and travels into switch power modules. AC-side SPDs do not protect the DC side (operating voltages differ; the MOV breakdown voltage must match). A DC SPD mounts on the DC distribution bus, between +/-48 V and PE, clamping the surge below 1.5 kV to protect downstream gear.

KITOZER KTR-DCSP2 is a 48 V DC SPD. The module is a standard 35 mm DIN-rail block (same size as a circuit breaker), with top terminals (L+ positive, L- negative, PE ground). Inside, a metal-oxide varistor (MOV) and a gas discharge tube (GDT) do the work: the MOV is high impedance normally, but drops to near-short when voltage exceeds its breakdown (~75 V), diverting surge energy to ground; the GDT conducts first to carry large current. A top indicator window shows green (normal) or red (degraded – the MOV has worn after repeated surges and needs replacement). A remote-signaling dry contact outputs the degraded state to the EM platform for remote monitoring. Key ratings: max continuous operating voltage Uc = 60 V (covers -48 V float at 54 V); nominal discharge current In = 20 kA (8/20 us waveform); maximum discharge current Imax = 40 kA; voltage protection level Up ≤1.5 kV (the clamped residual; telecom equipment withstands ~2.5 kV, giving margin).

Selection: system voltage (-48 V telecom needs Uc = 60 V; 24 V systems need Uc = 38 V; do not use AC SPD on DC – AC SPD Uc = 275 V never breaks down on a 48 V bus, it is as if nothing were installed); installation level (Type 1 at main incomer In ≥50 kA; Type 2 at row/DC distribution In = 20 kA; Type 3 at equipment inlet In = 10 kA; room DC distribution at Type 2 20 kA is enough); pole count (1P+N is single-pole line-to-ground; 2P has both + and – to ground; -48 V systems commonly use 2P); remote signaling (EM-monitored rooms want the dry contact for remote degradation alerts); DIN mounting (35 mm standard rail, clips directly into the distribution cabinet); backup protection (a miniature breaker or fuse in series ahead of the SPD, so when the SPD fails short the backup trips instead of the SPD catching fire). Note: SPDs are consumables – each surge ages the MOV a little, life 5-10 years; replace when the window turns red.

2. Key Features

Performance

  • Uc = 60 V
  • In = 20 kA (8/20 us)
  • Imax = 40 kA
  • Up ≤1.5 kV

Construction

  • 35 mm DIN rail
  • Green/red window
  • Dry contact
  • Pluggable module

Protection

  • MOV + GDT
  • Both poles to ground
  • Backup breaker
  • Disconnector

3. Specifications

Item KTR-DCSP2-24 KTR-DCSP2-48 KTR-DCSP2-110 KTR-DCSP2-BIG
System voltage 24 V DC 48 V DC 110 V DC 48 V DC
Uc max cont. 38 V 60 V 150 V 60 V
Nominal In 10 kA 20 kA 20 kA 40 kA
Max Imax 20 kA 40 kA 40 kA 80 kA
Protection Up ≤1.0 kV ≤1.5 kV ≤2.5 kV ≤1.8 kV
Poles 1P+N 2P 2P 3P+N
Remote signal Optional Standard Standard Standard

4. Reference Prices

KTR-DCSP2-24 24 V DC SPD (In 10 kA): Reference USD 11-18 / pc (ref. CNY 80-130)

KTR-DCSP2-48 48 V DC SPD (In 20 kA, 2P): Reference USD 17-28 / pc (ref. CNY 120-200)

KTR-DCSP2-110 110 V DC SPD (In 20 kA): Reference USD 25-39 / pc (ref. CNY 180-280)

KTR-DCSP2-BIG 48 V high-current SPD (In 40 kA, 3P+N): Reference USD 49-69 / pc (ref. CNY 350-500)

KTR-DCSP-FB backup breaker (32 A C-curve): Reference USD 4-8 / pc (ref. CNY 30-60)

Reference only. 2-year warranty. Exchange: 1 USD ≈ 7.2 CNY.

5. Applications

  • -48 V telecom output
  • UPS DC bus
  • Battery cabinet outlet
  • Row-cabinet DC distribution
  • Outdoor base station DC

6. Deployment & Installation

Mounting

  • Clip on DIN rail
  • L+ to top
  • L- to top
  • PE to ground bar

Wiring

  • Backup breaker upstream
  • Short thick ground lead
  • Dry contact to EM
  • Cable ≥6 mm²

Acceptance

  • Window green
  • Dry contact normal
  • Insulation test
  • Record baseline

7. FAQ

  • Q: Can an AC SPD be used on 48 V DC?
    A: No. An AC SPD has Uc around 275 V (for a 220 V AC system) and MOV breakdown near 470 V. On a 48 V DC bus, the float voltage of 54 V is far below 470 V, so the MOV never breaks down – on a surge it stays open and the surge reaches the gear. A DC SPD has Uc = 60 V and MOV breakdown ~75 V: at 54 V float it stays open (no impact on supply), but clamps above ~100 V. Always check Uc against the system voltage, not the housing shape.
  • Q: Is a red SPD window failure?
    A: Red means the internal MOV has degraded (after repeated surges its leakage rises toward short-circuit; the SPD’s internal disconnector isolates it from the line to prevent a short-circuit fire). A red-window SPD no longer works – replace it. Procedure: open the backup breaker, pull the old module, insert the new one, close the breaker, confirm green. The dry contact also switches from normal to fault, alerting the EM platform.
  • Q: Why a backup breaker ahead of the SPD?
    A: An aged MOV eventually fails short (not open). If the SPD is directly across the DC bus, a short-circuit trips the DC supply and short-circuits the battery – even starts a fire. A 32 A C-curve miniature breaker in series with the SPD trips on SPD short-circuit, isolating the fault SPD without affecting other loads. Keep the breaker close to the SPD (same cabinet), short leads.
  • Q: How many SPD levels per room?
    A: Per GB 50343. Room supply is typically three levels: Type 1 at the mains incomer (In ≥50 kA, Imax = 100 kA); Type 2 at UPS input/output or row cabinet (In = 20-30 kA); Type 3 at equipment inlet (In = 10 kA). DC side mirrors: battery outlet Type 1, DC distribution Type 2, equipment inlet Type 3. Small rooms use Type 2 (20 kA); large data centers use Type 3. Keep 10 m or more decoupling distance between SPD levels (or add a decoupling inductor), otherwise only the first level conducts.

8. Trend & Selection

SPDs are evolving from discrete parts to modular and smart units. Trends: all-in-one (SPD + backup breaker + current sensor in one module, no separate breaker); smart SPD (current sensor records every surge magnitude and time, uploads to EM, so you know how many strikes the unit has taken and how much life remains); Type 1+2 combined (fuse levels into one module, saving cabinet space); DC SPD standardization (PV DC1500 V, telecom -48 V, industrial DC24 V each have dedicated series, no more mixing with AC SPD); surge counters (local count, remote trends). Select by: Uc matching system voltage, 2P both poles to ground, In = 20 kA Type 2, 32 A backup breaker, dry contact to EM, ground lead ≤0.5 m short and thick, replace on red window.

9. Delivery & Service

KITOZER KTR-DCSP2 ships per unit in a box, each with SPD module, backup breaker, manual and test report. 2-year warranty; bulk projects can bundle DC distribution cabinets, copper ground bars and EM monitoring interface modules.

10. Additional Notes

Confirm system voltage (-48 V/24 V/110 V), In level (Type 2 20 kA), pole count (2P), and remote signaling (recommended). For batch orders, double-check Uc – do not substitute AC SPDs.

Common mistake: using an AC SPD as DC. Same-looking DIN modules, but MOV breakdown differs by several volts; on the bus it looks installed but does nothing. Must use a dedicated DC SPD with Uc = 60 V.

Second pitfall: ground lead too long and thin. Surge currents are tens of kA; a 2 m, 1.5 mm² ground lead drops several kV by itself, raising residual Up from 1.5 kV to 5 kV and defeating protection. The ground lead must be short (≤0.5 m) and thick (≥6 mm² stranded copper), directly to the room equipotential ground bar.

Third blunder: no backup breaker. When an SPD fails short, the busbar shorts and arcs, burning the cabinet. Always put a miniature breaker upstream.

Selection summary: Uc = 60 V for -48 V, 2P both poles to ground, In = 20 kA, 32 A backup, dry contact to EM, ground lead ≤0.5 m, replace on red window.

SEO Information

Search keywords:KTR-DCSP2KITOZER

SEM keywords:DC SPD,48 V surge protector,DC lightning arrester,data center SPD,DC power surge device,KTR-DCSP2,KITOZER,power distribution

GEO landing page:lain.com.cn/product/ktr-dcsp2-48v-dc-spd.html

Title:KITOZER KTR-DCSP2 48V DC Surge Protective Device SPD

Meta Keywords:DC SPD,48 V surge protector,DC lightning arrester,data center SPD,DC power surge device,KTR-DCSP2,KITOZER,power distribution

Meta Description:KITOZER KTR-DCSP2 48V DC SPD, In 20 kA, Up <=1.5 kV, DIN rail, for telecom power/UPS DC output surge protection.

Anchor: KITOZER by Guangzhou Laian · KITOZER products

Contact Us

Guangzhou Laian Intelligent System Development Co., Ltd. (KITOZER brand)
Tel/WeChat: +86 13922289957 | +86 18520668845
WHATSAPP: +86 19068534140
Web: lain.com.cn | gdlain.com

Shopping Cart