Table of Contents
ToggleKITOZER KTR-DPS3 DC 24V Signal Surge Protective Device
Brand: KITOZER Series: KTR-DPS3 Category: Power Distribution / Lightning Protection
DC 24VSignal SPDDIN-railKTR-DPS3
1. Overview
KITOZER KTR-DPS3 is a DIN-rail DC 24V signal surge protective device (SPD), wired in parallel on sensor, transmitter and dry-contact signal lines to divert lightning-induced and switching surges, protecting downstream acquisition modules and PLCs. Weak-current lines that enter from outdoors or run long distances carry induced surges that can destroy RS485 modules and analog input boards. A signal SPD is the over-voltage gate on weak-current lines.
KTR-DPS3 works at DC 24V, with nominal discharge current In 5kA and maximum Imax 10kA (8/20μs), response time no more than 1ns. It has a remote-signaling contact that closes on SPD failure. DIN 35mm rail mount, series-wired with clear IN and OUT terminals. Suitable for RS485, dry contact, 4 to 20mA analog and DC 24V supply lines.
Widely used on datacenter DCIM sensor lines: temp/humidity sensors, leak cables, smoke detectors, access readers, beam detectors and camera POE. Typical deploy: outdoor or long-distance lines pass through KTR-DPS3 before the acquisition module; the SPD ground uses at least 6mm² yellow-green wire to the grounding bar.
2. Key Features
DC 24V protection
- Rated voltage DC 24V.
- Nominal discharge 5kA.
- Max discharge 10kA.
- Response ≤1ns.
Remote signaling
- Failure dry contact.
- Remote SPD health monitor.
- Window indicator: OK/fail.
- Simple wiring.
DIN-rail mount
- DIN 35mm rail.
- Clear IN/OUT terminals.
- Compact footprint.
- Series-wired.
Multi-signal use
- RS485 surge protection.
- Dry contact and 4-20mA.
- DC 24V supply lines.
- Sensors and transmitters.
3. Specifications
| Item | KTR-DPS3 | KTR-DPS6 |
|---|---|---|
| Rated voltage | DC 24V | DC 48V |
| In | 5kA (8/20μs) | 10kA (8/20μs) |
| Imax | 10kA (8/20μs) | 20kA (8/20μs) |
| Response | ≤1ns | ≤1ns |
| Signaling | Yes | Yes |
| Mount | DIN rail | DIN rail |
| Signals | RS485/dry/24V | RS485/ETH/48V |
| Ground wire | ≥6mm² | ≥10mm² |
4. Reference Prices
KTR-DPS3 DC 24V signal SPD (DIN, signaling): Reference USD 14 to 42 / pc (ref. CNY 100 to 300 at ~7.2)
KTR-DPS6 DC 48V signal SPD (high current): Reference USD 28 to 69 / pc (ref. CNY 200 to 500 at ~7.2)
Reference only; price varies by voltage class, discharge rating and quantity. Grounding bar, ground wire and power SPD billed separately. Exchange: 1 USD ~ 7.2 CNY (Oct 2026).
5. Applications
- Outdoor-fed sensor lines.
- RS485 bus before rack entry.
- Access control and reader lines.
- Smoke and beam perimeter signals.
- DC 24V sensor supply lines.
6. Installation & Maintenance
Installation
- Clip SPD onto DIN rail.
- Series-wire: IN to line, OUT to equipment.
- Ground terminal with 6mm² yellow-green wire to the bar.
- Wire signaling contact to DCIM DI.
- Never reverse IN and OUT.
- One SPD per signal line.
Maintenance
- Check window is green quarterly.
- Review signaling alarms after storms.
- Measure ground resistance ≤1Ω yearly.
- Replace on red window or alarm.
- Tighten ground connections.
7. FAQ
- Q: Signal SPD vs power SPD?
A: Power SPD sits on the distribution feed and protects strong current; signal SPD sits on weak-current lines. Rooms need both: Class B/C power SPD in the cabinet, and signal/antenna SPD on data lines. - Q: Why must the SPD be grounded?
A: When diverting a surge, the current must flow to earth. A thin ground wire or high resistance leaves a large voltage drop, and downstream gear still burns. Ground resistance must be no more than 1Ω. - Q: Does an SPD age?
A: Yes. Each surge degrades the MOV; the window turns red when it fails. After storm season or on a red window, replace it, or it offers no protection. - Q: Do all signal lines need one?
A: Short in-room runs can skip it; outdoor-fed, long-distance and lines crossing building boundaries must have it. Most DCIM sensors are outdoor or floor-crossing, so install them.
8. Trend & Selection
Signal SPDs are moving from discrete devices to integrated, monitored units with LED status and RS485 reporting degradation, linked to DCIM for early warning. Install SPD on outdoor-fed lines; match voltage class; In no less than 5kA; wire signaling to DCIM; ground wire no less than 6mm²; ground resistance no more than 1Ω; inspect and replace after storms.
9. Delivery & Service
KITOZER supplies lightning-protection packages: based on signal-line count, voltage and outdoor exposure, we recommend SPD specs. Bundled with power SPD, grounding bar and equipotential bonding. Delivery includes SPD and manual; bulk orders include on-site grounding guidance. Warranty covers replacement.
10. Additional Notes
The most common error is a floating ground connection. A ground wire fastened to a single screw at 1.5mm² has a huge voltage drop during a surge, and downstream modules still burn. Use at least 6mm² stranded copper directly to the grounding bar, with no intermediate terminals.
Another pitfall: reversed IN and OUT. The outdoor side must be IN and the equipment side OUT. Reversed, the protection element sits on the equipment side, so the surge hits the device before the SPD. Terminals are marked; align them.
Selection summary: DC 24V signal SPD; In no less than 5kA; DIN-rail; with signaling; ground wire no less than 6mm²; ground resistance no more than 1Ω; inspect after storms. The SPD is the over-voltage gate on weak-current lines; a reliable gate keeps sensors and modules alive through a strike.
SEO Information
Search keywords:signal SPD24V surge protectorsurge protective deviceRS485 SPDDIN-rail SPDdatacenter lightning protectionKTR-DPS3KITOZER
SEM keywords:[‘signal SPD price’, ’24V signal surge supplier’, ‘RS485 surge protector’, ‘datacenter SPD’, ‘DIN rail surge protector’, ‘KTR-DPS3’, ‘KITOZER’]
GEO landing page:lain.com.cn/product/ktr-dps3-24v-dc-signal-spd.html
Title:KITOZER KTR-DPS3 DC 24V Signal Surge Protective Device
Meta Keywords:signal SPD,24V surge protector,surge protective device,RS485 SPD,DIN-rail SPD,datacenter lightning protection,KTR-DPS3,KITOZER
Meta Description:KITOZER KTR-DPS3 DC 24V signal SPD, DIN-rail, In 5kA, Imax 10kA, response no more than 1ns, with signaling, for RS485 and sensor lines.
Anchor: KITOZER · Power distribution
Contact Us
Guangzhou Laian Intelligent System Development Co., Ltd. (KITOZER brand)
Tel/WeChat: +86 13922289957 | +86 18520668845
WHATSAPP: +86 19068534140
Web: lain.com.cn | gdlain.com