1. Overview

The electronic expansion valve (EEV) is the throttling element in a vapor-compression cycle. High-pressure liquid leaving the condenser is suddenly depressurized across the valve into a low-pressure, low-temperature liquid-vapor mix before entering the evaporator. A traditional thermal expansion valve (TXV) senses superheat via a bulb and acts mechanically – slow, coarse. An EEV drives the needle directly with a stepper motor; the controller recalculates opening from superheat (outlet temp minus saturation temp at measured pressure) in real time, holding superheat at 1.8-3 K and lifting evaporator utilization from 70% to over 90%. Precision AC runs year-round with fluctuating load; the EEV modulates cooling capacity from 10% to 100%, part-load EER beating TXV units.

KITOZER KTR-EEV2 is an EEV for precision AC. Build: forged brass body, stainless needle with refrigerant-resistant seals; drive: 2-phase stepper, 2000 pulses closed-to-open, coil DC12V/DC24V; ports: flange or threaded, pipe ODs 12/16/22 mm; refrigerants: R22/R407C/R410A/R32; pressure: high side 4.5 MPa, low side 3.5 MPa; superheat: built-in PID, 1.0-8 K adjustable, default 2.5 K. Models: KTR-EEV2-14: ~14 kW (5-10 kW AC); KTR-EEV2-22: ~22 kW (10-20 kW AC); KTR-EEV2-30: ~30 kW (20-30 kW AC).

Selection: capacity (valve must exceed compressor rating by 1.2x); refrigerant (R410A high-pressure needs a rated body); pipe size (match evaporator liquid line); controller (EEV needs a dedicated driver, never connect to 220 V directly); orientation (vertical body, coil on top, arrow toward evaporator). Note: EEV is precision gear – pressure-test, leak-check and vacuum before commissioning; never hot-plug the coil; do not alter the default superheat – a commissioning engineer retunes it from evaporator outlet temp and suction pressure.

2. Key Features

Control

  • 2000-step stroke
  • 1.8-3 K superheat
  • Real-time PID
  • High part-load EER

Body

  • Forged brass
  • Stainless needle
  • Refrigerant seals
  • R410A/R32 ready

Drive

  • 2-phase stepper
  • DC12/24 V coil
  • Flange/threaded
  • Vertical mount

3. Specifications

Item KTR-EEV2-14 KTR-EEV2-22 KTR-EEV2-30
Capacity ~14 kW ~22 kW ~30 kW
Pipe OD 12 mm 16 mm 22 mm
Steps 2000 2000 2000
Superheat 1.0-8 K 1.0-8 K 1.0-8 K
Refrigerant R410A/R32 R410A/R32 R410A/R32

4. Reference Prices

KTR-EEV2-14 14 kW valve: Reference USD 53-72 / pc (ref. CNY 380-520)

KTR-EEV2-22 22 kW valve: Reference USD 72-100 / pc (ref. CNY 520-720)

KTR-EEV2-30 30 kW valve: Reference USD 100-136 / pc (ref. CNY 720-980)

KTR-EEV2-COIL driver coil: Reference USD 11-17 / pc (ref. CNY 80-120)

KTR-EEV2-CTRL superheat board: Reference USD 83-125 / pc (ref. CNY 600-900)

Reference only. 1-year warranty. Exchange: 1 USD ≈ 7.2 CNY.

5. Applications

  • Precision AC throttling
  • DX/chiller retrofits
  • Lab precision AC
  • Industrial chillers
  • Heat-pump water heaters

6. Deployment & Installation

Install

  • Vertical body
  • Coil up
  • Arrow to evaporator
  • Service clearance

Piping

  • Flare/flange joints
  • Nitrogen-purge brazing
  • Pressure test 4.5 MPa
  • Vacuum to 50 Pa

Commission

  • Wire DC24 V driver
  • Set refrigerant
  • Default 2.5 K SH
  • Tune on suction temp

7. FAQ

  • Q: Can an EEV swap in directly for a TXV?
    A: Mounting is similar, but no. A TXV is self-contained; an EEV needs a driver board, suction-temp and pressure sensors, and EEV firmware in the controller. Converting a TXV unit means adding all of that – it is not a bolt-on swap.
  • Q: What superheat setpoint?
    A: 2.5 K default for DX evaporators. Too low (<1 K) floods the compressor with liquid and causes slugging; too high (>6 K) dries the evaporator and wastes capacity. Aim for outlet temp 1.8-3 K above saturation.
  • Q: Coil burned out?
    A: The coil is a universal DC12/24 V two-wire part – unplug and replace, body untouched. Usual causes: wrong voltage (DC24 coil on AC220) or a shorted driver. Measure driver output before fitting a new coil.
  • Q: How to size capacity?
    A: Pick valve at 1.1-1.3x compressor rating. A 14 kW valve suits a 10-12 kW compressor. Too small: fully open still under-throttles at high load; too large: it dithers in tiny steps at low load and goes non-linear.

8. Trend & Selection

EEVs are becoming standard on medium/large refrigeration units, displacing TXVs. Trends: wider capacity range (1 kW residential to 50 kW commercial); communication – driver boards join RS485/Modbus so DCIM sees valve opening, superheat and differential pressure remotely; and VFD-compressor pairing – variable-speed compressor plus variable valve opening gives 5-100% capacity turndown and part-load EER 30% above fixed-speed units. Precision AC is moving from fixed-speed+capillary/TXV to VFD+EEV. Select by: 1.2x compressor capacity, refrigerant-pressure rated, matched driver board, 2.5 K default superheat tuned by a commissioning engineer.

9. Delivery & Service

KITOZER supplies KTR-EEV2 valve body, matching coil and driver board by model. Each ships with body, coil and manual; bulk orders can bundle driver boards and sensors. 1-year warranty; commissioning support available for projects.

10. Additional Notes

Match compressor capacity, refrigerant (R410A/R32 high-pressure) and pipe OD to site piping; mount body vertically with coil on top; feed driver board with DC24 V without reversing. For batch orders, bench-test a sample for superheat tuning.

Common mistake: hot-plugging the coil. Arcing under load burns the driver output MOSFET. Power off and wait 30 s for capacitor bleed before swapping a coil.

Second pitfall: brazing without nitrogen. Oxide scale forms inside the tube, rides the refrigerant to the valve seat, and jams the needle. Purge with nitrogen throughout brazing and flush lines.

Third blunder: fiddling with superheat. Setting 0.5 K chasing cooling floods the compressor with liquid; slugging destroys valves within months. Leave tuning to an engineer per standard.

Selection summary: valve capacity = compressor x1.2, R410A/R32 pressure-rated, vertical body with coil up, DC24 V driver, 2.5 K superheat tuned by engineer.

SEO Information

Search keywords:KTR-EEV2KITOZER

SEM keywords:electronic expansion valve,EEV,precision AC expansion valve,stepper valve,superheat control,KTR-EEV2,KITOZER

GEO landing page:lain.com.cn/product/ktr-eev2-electronic-expansion-valve.html

Title:KITOZER KTR-EEV2 Electronic Expansion Valve for Precision AC

Meta Keywords:electronic expansion valve,EEV,precision AC expansion valve,stepper valve,superheat control,KTR-EEV2,KITOZER

Meta Description:KITOZER KTR-EEV2 electronic expansion valve, stepper-driven, 2000-step stroke, adjustable superheat 1.8-3K, for R410A/R32 precision AC.

Anchor: KITOZER by Guangzhou Laian · KITOZER products

Contact Us

Guangzhou Laian Intelligent System Development Co., Ltd. (KITOZER brand)
Tel/WeChat: +86 13922289957 | +86 18520668845
WHATSAPP: +86 19068534140
Web: lain.com.cn | gdlain.com

Shopping Cart