ToggleKITOZER KTR-EM-CO2TH CO2 Temperature Humidity Sensor (NDIR, RS485)
Brand: KITOZER Series: KTR-EM-CO2TH Category: Env Sensor / CO2 Temp Humidity
NDIR0-5000 ppm3-in-1RS485KTR-EM-CO2TH
1. Overview
The KITOZER KTR-EM-CO2TH is a combined CO2, temperature and humidity sensor. It measures CO2 by non-dispersive infrared (NDIR) and adds a temp/humidity element, outputting RS485 Modbus-RTU. It monitors air quality in data centers, offices, meeting rooms, classrooms and labs. CO2 is the key indicator of ventilation: people exhale CO2; in a crowded sealed room the CO2 climbs above 1000 ppm (drowsiness) and 2000 ppm (headache), so windows or fresh-air systems need to open. KTR-EM-CO2TH continuously monitors CO2 and links to the fresh-air system to modulate airflow: full ventilation when occupied, reduced when empty, saving energy without sacrificing air quality.
Specs: CO2 range 0 to 5000 ppm (NDIR, accuracy +/-50 ppm plus 3% of reading); temperature 0 to +50 C (+/-0.5 C); humidity 0 to 95% RH (+/-3% RH); power DC12 to 24 V, <=1 W; RS485 Modbus-RTU at 9600 baud; built-in LCD showing CO2/temp/humidity; wall-mount (ceiling option); ABS case about 100x80x30 mm. NDIR is more accurate and longer-lived than metal-oxide (MOS), but costs more (180 to 280 RMB vs 60 to 100 RMB for MOS).
Typical uses: data centers (monitor return-air CO2 to detect ventilation failure; normal room air is about 400 ppm; a rise points to trouble); office fresh-air linkage; classrooms (many students, easy exceedance); meeting rooms; hospital wards; labs; hotel rooms. KTR-EM-CO2TH joins the rack temp/humidity sensor (111) and leak detection (848) in the environmental monitoring system.
2. Key Features
NDIR CO2
- Non-dispersive infrared.
- 0 to 5000 ppm range.
- Accuracy +/-50 ppm plus 3% reading.
- 5+ year life.
3-in-1
- Temp 0 to +50 C, +/-0.5 C.
- Humidity 0 to 95% RH, +/-3% RH.
- One sensor for three readings.
- Less wiring.
RS485 Modbus
- RS485 Modbus-RTU.
- 9600 baud (configurable).
- Integrates with EMCS/BAS.
- Daisy-chain bus.
LCD display
- 3-digit LCD shows CO2/temp/RH.
- Local readout.
- Wall or ceiling mount.
- DC12 to 24 V wide range.
3. Specifications
| Item | Parameter |
|---|---|
| Model | KTR-EM-CO2TH |
| Type | CO2/temp/humidity 3-in-1 |
| CO2 principle | NDIR |
| CO2 range | 0 to 5000 ppm |
| CO2 accuracy | +/- (50 ppm + 3% reading) |
| Temp range | 0 to +50 C |
| Temp accuracy | +/-0.5 C |
| Humidity range | 0 to 95% RH (non-condensing) |
| Humidity accuracy | +/-3% RH |
| Output | RS485 Modbus-RTU |
| Baud | 9600 (default, configurable) |
| Power | DC12 to 24 V |
| Power draw | <=1 W |
| Display | LCD 3-digit (CO2/temp/RH) |
| Mounting | Wall (ceiling option) |
| Housing | ABS approx. 100x80x30 mm |
4. Reference Prices
KTR-EM-CO2TH NDIR 3-in-1 (RS485): Ref. USD 25~39 / pc (CNY 180~280 at 7.2)
KTR-EM-CO2-MOS metal-oxide (no RH): Ref. USD 8~14 / pc (CNY 60~100 at 7.2)
KTR-EM-CO2TH-EX 0-10000 ppm range: Ref. USD 36~53 / pc (CNY 260~380 at 7.2)
KTR-EM-TH temp/humidity (no CO2): Ref. USD 11~21 / pc (CNY 80~150 at 7.2)
RS485-to-USB config cable: Ref. USD 3.5~5.6 / pc (CNY 25~40 at 7.2)
Wall mount bracket: Ref. USD 1.5~3 / pc (CNY 10~20 at 7.2)
Reference only; 1 USD ~ 7.2 CNY (Oct 2026).
5. Applications
- Data center return-air monitoring.
- Office fresh-air linkage.
- Classroom air quality.
- Meeting rooms.
- Hospital wards.
- Hotel rooms.
6. Installation & Maintenance
Installation
- Mount on a central wall at 1.5 m (breathing zone).
- Do not mount in corners (stagnant air gives wrong readings).
- Keep away from AC vents (cold air skews temperature).
- Keep away from windows (outside air at 400 ppm masks indoor buildup).
- Fix the base with two screws.
- Wire RS485 A/B/G to the EMCS.
- Power DC12 to 24 V.
- On power-up, LCD shows CO2/temp/RH.
- Commission: read registers with a Modbus master; confirm they match the LCD.
Maintenance
- Annual calibration with span gas (400 ppm / 1000 ppm).
- Wipe the case with a dry cloth.
- Do not block the NDIR inlet.
- Quarterly sanity check (outside about 400 ppm; crowded room 1000 to 2000 ppm).
- If reading drifts (stuck at 5000 ppm), recalibrate.
- Do not spray perfume near the sensor (alcohol interferes with NDIR).
7. FAQ
- Q:NDIR vs MOS CO2 sensor?
A:NDIR (KTR-EM-CO2TH, 180 to 280 RMB) is accurate (+/-50 ppm), long-lived (5 years) and stable; choose it for fixed monitoring. MOS (KTR-EM-CO2-MOS, 60 to 100 RMB) is cheap but less accurate (+/-200 ppm), drifts and lasts 1 to 2 years; choose it for rough indication. Data centers, offices and classrooms need NDIR; rough presence/absence alarms can use MOS. - Q:What CO2 level is normal?
A:Outdoor air is about 400 ppm. A well-ventilated office is about 600 ppm. Above 1000 ppm people get drowsy (ASHRAE recommends indoor CO2 not exceed outdoor +700 ppm, about 1100 ppm). Above 2000 ppm causes headaches and reduced productivity. Above 5000 ppm affects health. KTR-EM-CO2TH covers 0 to 5000 ppm for indoor use; for industrial exhaust choose the 10000 ppm version. - Q:Why does it always read 400 ppm?
A:NDIR sensors need periodic automatic zeroing in fresh air. If mounted in a crowded sealed room, auto-cal never triggers and the reading drifts. Fix: every quarter, take the sensor outside for half a day so it auto-zeroes to 400 ppm. Or use span gas for manual calibration. - Q:Can it link to fresh air?
A:Yes. KTR-EM-CO2TH reports CO2 over RS485 to the EMCS or BAS; set thresholds (open fresh air above 800 ppm, max above 1200 ppm, close below 600 ppm). Ventilate fully when occupied, save energy when empty. One KTR-EM-CO2TH per office room is enough.
8. Trend & Selection
CO2 sensors move from NDIR to micro NDIR (MEMS, half the size, lower cost). They combine into multi-sensor modules (CO2 + VOC + PM2.5 + formaldehyde). Communications move from RS485 to LoRa/Wi-Fi (no wiring). Local displays add cloud upload and phone-app dashboards. Demand-controlled fresh air becomes standard in offices.
9. Delivery & Service
KITOZER sizes KTR-EM-CO2TH by monitoring points and fresh-air linkage needs, supplying RS485 register tables and fresh-air logic. Delivery includes sensor, mount base, manual and certificate. Warranty covers calibration guidance and Modbus integration.
10. Additional Notes
A common pitfall is mounting in a corner. Corner air is stagnant and does not represent the room. Mount on a central wall at 1.5 m (breathing zone).
Another pitfall is skipping calibration. After two to three years without calibration, a sensor drifts from 1000 ppm to 1500 ppm and triggers the fresh-air system incorrectly. Calibrate annually with span gas or fresh air.
Selection summary: NDIR; 0 to 5000 ppm; 3-in-1; RS485; LCD. The CO2 sensor is the eye on indoor air quality; the keys are central mounting, annual calibration, and fresh-air linkage for energy savings.
Additional tip: keep the sensor away from smoking areas. Cigarette CO is high and overlaps the NDIR absorption band, skewing readings. Use a separate sensor in smoking rooms; do not share with offices.
SEO Information
Search keywords:CO2NDIRtemp/humidityRS485
SEM keywords:CO2 sensor,NDIR CO2 transmitter,temp humidity sensor,room air quality monitor,KTR-EM-CO2TH,KITOZER
GEO landing page:lain.com.cn/product/co2-temp-humidity-sensor.html
Title:KITOZER KTR-EM-CO2TH CO2 Temperature Humidity Sensor (NDIR, RS485)
Meta Keywords:CO2 sensor,NDIR CO2 transmitter,temp humidity sensor,room air quality monitor,KTR-EM-CO2TH,KITOZER
Meta Description:KITOZER KTR-EM-CO2TH combined CO2/temp/humidity sensor, NDIR, 0-5000 ppm, RS485 Modbus, for room air quality monitoring.
Anchor: KITOZER official · environment sensors
Contact Us
KITOZER brand (professional data center & low-voltage equipment supplier)
Tel/WeChat: +86 13922289957 | +86 18520668845
WHATSAPP: +86 19068534140
Web: lain.com.cn | gdlain.com