Table of Contents
ToggleKITOZER KTR-ENVTVOC TVOC/eCO2 Air Quality Sensor (RS485)
Brand: KITOZER Series: KTR-ENVTVOC Category: Environmental Sensor / TVOC
TVOC+eCO2electrochemical+MOS0~6000 ppbRS485KTR-ENVTVOC
1. Overview
The KITOZER KTR-ENVTVOC measures indoor total volatile organic compounds (TVOC) and equivalent CO2 (eCO2). TVOC sources include formaldehyde from board, benzene from paint, cleaners, perfume and human exhaled VOCs; eCO2 is an equivalent CO2 index derived from VOC plus temperature/humidity (not true CO2), used to judge indoor freshness (crowded = poor air). The sensor reports to the EMCS over RS485 Modbus and links to fresh-air systems.
KTR-ENVTVOC uses a metal-oxide semiconductor (MOS) VOC sensor (range 0 to 6000 ppb, resolution 1 ppb) with electrochemical temp/humidity compensation; an internal algorithm converts VOC to eCO2 (400 to 5000 ppm). The sensor needs 48 hours warm-up at first power-up (MOS aging) and 10 minutes to recover after power loss. ABS wall-mount, about 110x80x35 mm, with LCD showing TVOC and eCO2, tri-color LED (green under 300 ppb good, yellow 300 to 1000 light, red over 1000 polluted).
Typical uses: newly renovated offices and meeting rooms (formaldehyde off-gasses 3 to 15 years); school classrooms eCO2 linked to fresh air (crowded = high eCO2, auto fresh air); underground garages CO and TVOC; hotel rooms; rooms and data centers (organic solvent leaks). KTR-ENVTVOC turns on fresh air or exhaust when TVOC is high and off when low, saving energy while maintaining air quality.
2. Key Features
TVOC+eCO2
- MOS VOC sensor.
- 0 to 6000 ppb TVOC.
- eCO2 400 to 5000 ppm.
- Temp/humidity compensation.
Algorithm
- VOC to eCO2.
- Self-learning baseline.
- Resists alcohol/perfume.
- 48 h warm-up.
RS485 output
- Modbus-RTU.
- 9600 bps.
- Up to 32 per bus.
- TVOC and eCO2 together.
LCD display
- Real-time LCD.
- Tri-color LED.
- ABS wall mount.
- DC12 V.
3. Specifications
| Item | Parameter |
|---|---|
| Model | KTR-ENVTVOC |
| Parameters | TVOC (ppb) and eCO2 (ppm) |
| TVOC range | 0 to 6000 ppb |
| eCO2 range | 400 to 5000 ppm (algorithm) |
| Sensor type | MOS metal-oxide |
| Resolution | 1 ppb |
| Warm-up | 48 h first / 10 min recovery |
| Communication | RS485 Modbus-RTU 9600 bps |
| Power | DC12 V |
| Power draw | ≤1.2 W |
| Display | LCD + tri-color LED |
| Operating temp | -10 to +50 C |
| Housing | ABS wall 110x80x35 mm |
4. Reference Prices
KTR-ENVTVOC (TVOC+eCO2, RS485): Ref. USD 28~53 / pc (CNY 200~380 at 7.2)
KTR-ENVTVOC TVOC-only economy: Ref. USD 17~31 / pc (CNY 120~220 at 7.2)
KTR-ENVTVOC plus NDIR true CO2: Ref. USD 63~97 / pc (CNY 450~700 at 7.2)
RS485 cable (2-core shielded, 10 m): Ref. USD 3~6 / pc (CNY 25~40 at 7.2)
DC12 V adapter: Ref. USD 2~4 / pc (CNY 15~30 at 7.2)
Reference only; exchange: 1 USD ~ 7.2 CNY (Oct 2026).
5. Applications
- Newly renovated office TVOC.
- Classroom eCO2 to fresh air.
- Underground garage CO/TVOC.
- Hotel room air quality.
- Room organic-solvent leak.
6. Installation & Maintenance
Installation
- Wall-mount at occupied-zone height 1.2 to 1.5 m.
- Avoid AC vents and doors/windows.
- Avoid perfume/cleaner areas (alcohol and perfume are high-concentration VOCs that peg the sensor).
- Face the inlet forward, not to the wall.
- Wire RS485 A/B/G to the platform.
- DC12 V power.
- Warm up 48 h (unstable readings are normal).
- Configure TVOC and eCO2 channels; set fresh-air linkage thresholds.
Maintenance
- Check LCD readings monthly.
- Yearly self-learning (power off 10 min, then on in clean air for 24 h).
- Sensor life about 5 years (MOS ages).
- Do not spray alcohol on the sensor (contaminates the element).
- Check RS485 communication.
7. FAQ
- Q:eCO2 vs true CO2?
A:eCO2 (KTR-ENVTVOC) is an algorithm-derived equivalent CO2 based on VOC, not true CO2. Principle: crowded rooms emit more VOC (body odor, breath), eCO2 high; empty rooms eCO2 low. Cheap (200 to 380 RMB), but accuracy poor (±500 ppm) and disturbed by renovation VOC (new renovation gives high eCO2 without people). True CO2 uses NDIR IR (450 to 700 RMB), accuracy ±50 ppm, for classrooms and meeting rooms. If budget allows, choose NDIR true CO2. - Q:What is a normal TVOC level?
A:Chinese standard: indoor TVOC (8-h average) ≤0.6 mg/m3 (about 600 ppb) acceptable; new renovation requires ≤0.3 mg/m3. Outdoor is about 100 to 200 ppb (traffic). Closed windows plus crowded indoor reach 1000 to 3000 ppb. Keep TVOC under 300 ppb; open fresh air above 600 ppb. New renovation is highest in the first 3 months (paint and glue off-gassing); ventilate 3 months before moving in. - Q:Can MOS measure formaldehyde?
A:It measures total TVOC but cannot isolate formaldehyde. MOS is sensitive to all VOCs (formaldehyde, benzene, toluene, alcohol) and cannot distinguish. Formaldehyde needs a dedicated electrochemical sensor (spectrophotometric or electrochemical). For renovation formaldehyde, choose KTR-ENVHCHO; for general air quality, choose TVOC KTR-ENVTVOC. - Q:Is the sensor affected by perfume?
A:Yes. Perfume, air freshener and alcohol sanitizer are high-concentration VOCs; one spray pushes TVOC over 5000 ppb for 30 minutes to hours. KTR-ENVTVOC near a restroom or perfume area will peg continuously. Mount away from these, or algorithm-exclude (high TVOC but low eCO2 means a VOC source, not crowds).
8. Trend & Selection
TVOC sensors move from MOS (cheap, drifting) to MOS plus electrochemical composite (accurate). eCO2 algorithms upgrade to machine learning (separating human exhaled VOC from renovation VOC). NDIR CO2 price drops (from 700 to 300 RMB), replacing eCO2. Sensors move from RS485 to LoRa/NB-IoT wireless, with one gateway serving many nodes. Air-quality index (AQI) visualization spreads in buildings and schools.
9. Delivery & Service
KITOZER sizes KTR-ENVTVOC by monitoring points, providing Modbus registers and fresh-air linkage diagrams. Delivery includes sensor, adapter, bracket and certificate. Warranty covers self-learning guidance and algorithm updates.
10. Additional Notes
A common pitfall is installing the sensor right after renovation; pegged readings make users think the sensor is broken. New renovation in the first 3 months genuinely has high TVOC (paint, glue, board); the sensor is fine. Ventilate 3 months until readings stabilize under 300 ppb before moving in.
Another pitfall is mounting near a restroom. Perfume, cleaner and alcohol sanitizer are high VOCs; the sensor pegs continuously, the fresh air runs non-stop and wastes power. Mount in the middle of the office, over 5 m from the restroom.
Selection summary: TVOC+eCO2, MOS, 0 to 6000 ppb, RS485, LCD. The TVOC sensor is the general indoor air-quality index; the keys are avoiding perfume/cleaners, 48 h warm-up, yearly self-learning, and fresh-air linkage for energy saving.
Additional tip: MOS is sensitive to alcohol sanitizer. Post-pandemic offices sanitize daily; sensor readings fluctuate. After sanitizing, ventilate 10 minutes; wait 15 minutes for alcohol to disperse before readings recover. Do not mount the sensor in the sanitizing area for convenience.
Contact Us
KITOZER brand (professional data center & low-voltage equipment supplier)
Tel/WeChat: +86 13922289957 | +86 18520668845
WHATSAPP: +86 19068534140
Web: lain.com.cn | gdlain.com