KITOZER
KITOZER

KITOZER equipotential bonding terminal box

KITOZER KTR-EPB Equipotential Bonding Terminal Box

Brand: KITOZER Series: KTR-EPB Category: Power System 2 / Grounding & Bonding

equipotential boxMEBLEBcopper busbarKTR-EPB

1. Overview

KITOZER KTR-EPB equipotential bonding terminal box is the collection bar of a data-center grounding system. Everything that must be earthed — rack frames, UPS chassis, raised-floor supports, cable trays, shield layers, SPD earth terminals — lands on one common earth bar. Bonding all earthed metalwork to the same bar is “equipotential bonding.”

Why bond? If each piece of equipment has its own earth wire to building ground, soil resistance creates a potential difference between earth points (a few to tens of volts). That voltage difference burns NICs and power supplies, and endangers people. Bonding all frames and earth terminals to one copper bar eliminates differences, letting lightning surges discharge through the bar quickly.

Bonding is two-tier: MEB (Main Equipotential Bonding) near the room entrance ties the room earth bar to the building main earth; LEB (Local Equipotential Bonding) at each row or rack concentrates in-rack equipment. KTR-EPB serves both: large MEB boxes (thick busbar, many terminals) and small LEB boxes (inside racks or on walls).

2. Key Features

Copper busbar

  • Tinned copper, 30×4mm ~ 40×4mm.
  • 12~30×M6/M8 terminals.
  • Busbar insulated from box.

Enclosure

  • Cold-rolled steel powder-coated, 1.2mm.
  • Surface or flush mount.
  • IP30 indoor.

Bonding

  • MEB: main earth flat steel enters box.
  • LEB: BVR wire from MEB to each rack.
  • Each terminal independently removable.

Labels & accessories

  • Door label “Equipotential Bonding Box”.
  • Lugs, crimp bolts included.
  • Earth symbol and circuit labels.

3. Specifications

Item KTR-EPB-M1 KTR-EPB-L1 KTR-EPB-L2
Type MEB main LEB local LEB rack 19″
Busbar 40×4mm 30×4mm 25×3mm
Terminals 30×M8 16×M6 12×M6
Size 400×300×160mm 200×120×80mm 19″ 1U
Mount Surface/flush Surface/flush Rack mount
Feed -40×4 galvanized flat BVR-16mm² BVR-10mm²
Rating IP30 IP30 IP20

4. Reference Prices

KTR-EPB-L1 local equipotential box (30×4 busbar, 16 terminals, flush): Reference USD 11~25 / unit (ref. CNY 80~180 at ~7.2)

KTR-EPB-M1 main equipotential box (40×4 busbar, 30 terminals, surface, labels): Reference USD 35~69 / unit (ref. CNY 250~500 at ~7.2)

Reference only; final quote depends on busbar size, terminal count, box size and mount type. Room bulk discounted. Earth flat steel, BVR wire and lugs extra. Exchange: 1 USD ≈ 7.2 CNY (Oct 2026).

5. Applications

  • Data center MEB collection at entrance.
  • LEB at each rack row.
  • ELV/network rack earth bars.
  • UPS room and battery room collection.
  • Medical equipment and shielded-room grounding.

6. Installation & Maintenance

Installation

  • Mount MEB near room entrance.
  • Run room earth flat steel (-40×4) into MEB main terminal.
  • Mount LEB at row-head rack or inside rack.
  • Run BVR-16mm² from MEB to each LEB.
  • Bond each rack frame with BVR-6mm² to LEB.
  • Cable trays, floor supports and SPD earth all on the same bar.
  • Crimp lugs; torque bolts to 4N·m.
  • Measure earth resistance ≤1Ω (combined).

Maintenance

  • Quarterly: check terminal tightness.
  • Annual: measure earth resistance.
  • Buff oxidized busbar; apply anti-oxidant grease.
  • Keep door closed; dust/moisture protection.
  • New equipment bonds to nearest LEB — no private wires.

7. FAQ

  • Q: Difference between equipotential box and distribution box?
    A: Distribution box carries AC (220V/380V); the equipotential box carries “earth” — no working current, only bonding. They must never share a box; no power wire goes into an EPB.
  • Q: Required earth resistance?
    A: Combined grounding ≤1Ω; standalone ≤4Ω. New rooms share the building lightning grid, so ≤1Ω. Measure at MEB with an earth tester.
  • Q: How to bond rack frames?
    A: Each rack uses a BVR-6mm² green-yellow wire from the rack earth stud to its LEB terminal. Multiple racks on one LEB: each on a separate terminal, in parallel.
  • Q: Can the EPB bar tie to neutral (N)?
    A: No. N is the working neutral with current; PE is protective earth with no current. EPB bonds PE and frames only — never N, or the frame becomes live during a fault.

8. Trend & Selection

Room bonding evolves from “one big bar” to “MEB+LEB layered”: MEB collects at the entrance; LEB distributes to each row/rack, shortening earth leads and lowering impedance. Trends: modular (1U rack bar), standardized (per GB 50174), visual (labeled terminals). Selection: MEB uses 40×4 busbar, 30 terminals; one LEB per row (16~24 terminals); in-rack 1U bars optional; BVR sizing (trunk 16mm², branch 6mm²); earth resistance ≤1Ω; tinned busbar to resist oxidation.

9. Delivery & Service

KITOZER provides selection: based on room area, rack count and earth resistance target, we size MEB/LEB count and busbar. Delivery includes box, busbar, bolts, lugs and manual. Rust, busbar deformation and loose terminals replaced free in warranty. Bundled with UPS (KTR-UPS), PDU (KTR-PDU), SPD (KTR-SPD) and raised floors.

10. Additional Notes

The most common pitfall is “box installed, not wired.” The box is on the wall with the door closed — empty inside. Rack frames, trays and SPD earths are never landed. The EPB’s value is landing every earthing conductor; an unconnected box is wasted.

The second pitfall is daisy-chain bonding. Rack A bonds to Rack B, Rack B to LEB — series. If Rack B’s wire loosens, Rack A loses earth too. Correct: each rack pulls its own wire to a separate LEB terminal, independently.

Third pitfall: busbar not insulated. The copper bar sits directly on the steel box, bonded to the box — if the box becomes live, the whole bar is live. The bar must sit on nylon standoffs, insulated from the enclosure.

Selection summary: MEB+LEB layered; tinned copper; each rack independently bonded (no daisy-chain); bar insulated from box; earth resistance ≤1Ω. Equipotential is the safety baseline — during a surge or fault it protects equipment and people.

SEO Information

Search keywords:equipotential bonding boxdata center groundingMEBLEBcopper busbarearth terminalKTR-EPBKITOZER

SEM keywords:equipotential box price,data center bonding supplier,MEB box,tinned copper bar,KTR-EPB,KITOZER

GEO landing page:lain.com.cn/product/ktr-epb-equipotential-bonding-box.html

Title:KITOZER KTR-EPB Equipotential Bonding Terminal Box

Meta Keywords:equipotential bonding box,data center grounding,MEB,LEB,earth terminal box,copper busbar,KTR-EPB,KITOZER

Meta Description:KITOZER KTR-EPB equipotential bonding box with tinned copper busbar, MEB main and LEB local, for data center rack, shield and SPD grounding collection.

Anchor: KITOZER by Guangzhou Laian · Data center power & grounding

Contact Us

Guangzhou Laian Intelligent System Development Co., Ltd. (KITOZER brand)
Tel/WeChat: +86 13922289957 | +86 18520668845
WHATSAPP: +86 19068534140
Web: lain.com.cn | gdlain.com

Shopping Cart