ToggleKITOZER KTR-ES06 Temp/Humidity/Smoke Integrated Sensor (RS485)
Brand: KITOZER Series: KTR-ES06 Category: Data Center Engineering / Environmental Monitoring
temp/humiditysmokeRS485integrated sensorKTR-ES06
1. Overview
The KITOZER KTR-ES06 is an integrated temp/humidity/smoke sensor using RS485 Modbus-RTU, combining three functions in one unit for room power & environment monitoring (EMCS). It embeds a high-precision digital temp/humidity chip (±0.3℃ / ±2% RH) and a photoelectric smoke chamber, uploading to the EMCS platform over RS485 for temp/humidity threshold alarms and early fire smoke alarms.
The KTR-ES06 housing is ABS flame-retardant, about 100×100×35 mm, ceiling or wall mount. The temp/humidity probe at the bottom has a dust filter; the smoke chamber at the top has an air grille. Power DC12V or DC24V; RS485 terminals A/B/G support hand-in-hand bus, up to 1200 m at 9600 bps. Address is set by DIP switch (1~255); up to 32 sensors on one bus.
KTR-ES06 outputs: temperature (℃), humidity (%RH), smoke status (normal/alarm), sensor status (normal/fault). Modbus register maps are in the factory manual; the platform reads registers to obtain data. Alarm thresholds (temp high/low, humidity high/low) are set remotely from the platform or locally by DIP. In EMCS, ES06 typically joins water leak, access control, UPS and AC monitoring points on the platform for centralized room monitoring and alarm.
2. Key Features
3-in-1 integrated
- Temp + humidity + smoke.
- One unit replaces three.
- Saves wiring.
- Fewer mounting points.
High-precision TH
- Digital TH chip.
- ±0.3℃ accuracy.
- ±2% RH.
- Dust filter.
Photoelectric smoke
- Photoelectric chamber.
- Air grille.
- Early smoke alarm.
- Dust/insect protection.
RS485 Modbus
- Modbus-RTU.
- 9600~115200 bps.
- DIP address 1~255.
- Hand-in-hand bus 1200 m.
3. Specifications
| Item | Parameter |
|---|---|
| Model | KTR-ES06 |
| Temp range | -20~60℃ |
| Temp accuracy | ±0.3℃ (25℃) |
| Humidity range | 0~100% RH |
| Humidity accuracy | ±2% RH (25℃) |
| Smoke type | photoelectric |
| Protocol | RS485 Modbus-RTU |
| Baud rate | 9600~115200 (def. 9600) |
| Power | DC12V / DC24V |
| Power consumption | ≤1 W |
| Mounting | ceiling / wall |
| Housing | ABS flame-retardant |
4. Reference Prices
KTR-ES06 temp/humidity/smoke sensor (RS485): Reference USD 35~69 / unit (ref. CNY 250~500 at ~7.2)
KTR-ES06 temp/humidity sensor (no smoke): Reference USD 21~42 / unit (ref. CNY 150~300 at ~7.2)
KTR-ES06 RS485-to-USB/network gateway (opt.): Reference USD 28~83 / unit (ref. CNY 200~600 at ~7.2)
Reference only; exchange: 1 USD ~ 7.2 CNY (Oct 2026).
5. Applications
- Room EMCS.
- Temp/humidity threshold alarms.
- Early smoke detection.
- Power room / battery room monitoring.
- Archive / lab environment.
6. Installation & Maintenance
Installation
- Ceiling / wall mount.
- Hand-in-hand RS485 A/B bus.
- Connect DC12V/24V.
- Set DIP address.
- Add 120 Ω terminator at both ends.
- Add channel on platform.
Maintenance
- Clean TH dust filter quarterly.
- Test smoke semi-annually (smoke test).
- Check RS485 wiring.
- Archive DIP addresses.
- Recheck alarm thresholds.
- Replace at end of life.
7. FAQ
- Q:Why hand-in-hand RS485 bus?
A:Hand-in-hand (daisy chain) avoids star branches that cause signal reflection and unstable comms. Add 120 Ω terminators at both ends; no star stubs in between. - Q:Smoke false alarm — how to troubleshoot?
A:First check the chamber for dust or insects; vacuum it. False alarms also occur above 85% RH or near steam. If it persists after cleaning, replace the sensor. - Q:Temp/humidity accuracy drifts?
A:Digital TH chips can drift over time; calibrate against a standard TH source. Replace if deviation exceeds ±0.5℃. Compare room TH annually. - Q:How many sensors on one RS485 bus?
A:Theoretically 32 nodes (without repeater); ES06 DIP addresses 1~255. Practically keep under 20 per bus for margin. Beyond 1200 m, add an RS485 repeater.
8. Trend & Selection
Environmental sensors are moving toward multi-parameter integration (TH + leak + smoke + door), wireless (LoRa / NB-IoT) and edge computing. RS485 remains the main wired EMCS protocol, but wireless sensors are growing in retrofit projects. Select by monitored parameters (TH/smoke/leak), communication (RS485/Ethernet) and accuracy.
9. Delivery & Service
KITOZER sizes KTR-ES06 sensor quantity by room monitoring points, providing RS485 bus layout and Modbus register tables. Delivery includes sensor body, mounting kit, terminals, certificates and Modbus manual. Warranty covers platform integration and alarm threshold setup.
10. Additional Notes
A common pitfall is star-wired RS485. Star branches cause signal reflection and intermittent comms. Use hand-in-hand wiring with 120 Ω terminators at both ends; stubs under 5 m.
Another pitfall is mounting the smoke sensor under an AC diffuser. Airflow blows smoke away and reduces sensitivity. Mount smoke sensors on the ceiling center, away from AC supply/return grilles.
Additionally, power the bus from a single 12 V DC source at one end rather than daisy-chaining power, to avoid voltage drop across long runs. Keep RS485 cables shielded, with the drain wire grounded only at the controller end to prevent ground loops. On the platform, set hysteresis on temp/humidity alarms to avoid chatter when values hover near the threshold.
Selection summary: TH + smoke 3-in-1; RS485 Modbus; ±0.3℃ accuracy; photoelectric smoke; hand-in-hand bus. The environmental sensor is the sensing nerve of EMCS — right location, proper bus, periodic calibration ensure room anomalies are caught early.
SEO Information
Search keywords:temp humidity smoke sensorRS485 environmental sensorroom EMCSKTR-ES06KITOZER
SEM keywords:temp humidity smoke sensor price,RS485 room sensor supplier,KTR-ES06
GEO landing page:lain.com.cn/product/ktr-es06-temp-humidity-smoke-sensor.html
Title:KITOZER KTR-ES06 Temp/Humidity/Smoke Integrated Sensor (RS485)
Meta Keywords:temp humidity smoke integrated sensor,RS485 room environmental sensor,KTR-ES06,KITOZER
Meta Description:KITOZER KTR-ES06 temp/humidity/smoke integrated sensor uses RS485 Modbus, integrating temperature, humidity and smoke detection, for room power & environment monitoring.
Anchor: KITOZER official · Data center & low-voltage equipment