ToggleKITOZER KTR-FC Fiber Optic Cabling System
Brand: KITOZER Series: KTR-FC Category: Data Center Engineering / Fiber Cabling
single-mode fiberOM3/OM4 multimodefiber patch cordODF patch panelfiber closureMPO trunksplice loss<=0.05dBLCP termination
1. Overview
The KITOZER KTR-FC fiber cabling system covers cable, patch cords, ODF patch panels, fiber closures and MPO trunks, delivering low-loss, high-bandwidth links for data centers, campus backbones and vertical risers. Single-mode OS2 serves long-reach backbones (>=10 km), while OM3/OM4 multimode handles in-rack 10G/40G/10GBASE-SR short-reach links.
All links are terminated to TIA-568 and YD/T standards; fusion splice loss <=0.05 dB per point, connector loss <=0.3 dB, and each link ships with an OTDR report. Rackmount 19" ODF panels ship with LC/SC adapters and modular splice trays for easy growth.
KTR-FC also offers pre-terminated MPO-12/24 trunks for to-rack switch-to-switch high-density plug-and-play cabling, cutting on-site splicing and accelerating cut-over.
2. Key Features
Cable selection
- Outdoor: GYTA/GYTS armored OS2 single-mode, 2-144 cores, aerial/duct/direct-burial options.
- Indoor: OM3/OM4 multimode or OS2 tight-buffered, LSZH jacket.
- Data center: MPO-12/24 pre-terminated trunk, supports 40G/100G SR4.
Patching and termination
- 19″ rackmount ODF in 12/24/48/72/96-core configurations, LC/SC duplex adapters.
- Fusion splicing <=0.05 dB; LCP fast-connector for emergency repair.
- Patch cords color-coded: OS2 yellow, OM3 aqua, OM4 magenta.
Test and acceptance
- Bidirectional OTDR + light source/power-meter loss test with report.
- Return loss >=50 dB (PC/UPC), >=60 dB (APC).
- Four-level labeling: building-floor rack-port for maintainability.
3. Specifications
| Item | Config A | Config B |
|---|---|---|
| 型号 | KTR-FC-OS2(室外单模) | KTR-FC-OM4(室内多模) |
| 光纤类型 | OS2 G.652D单模 | OM4 50/125多模 |
| 芯数 | 2/4/12/24/48/96/144芯 | 12/24芯 |
| 护套 | GYTA铠装,PE | LSZH低烟无卤 |
| 适用距离 | 10G LR:10km / 100G LR4:2km | 10G SR:150m / 40G SR4:100m |
| 成端 | LC/SC/FC | LC双工/MPO-12 |
| 熔接损耗 | ≤0.05dB/点 | ≤0.1dB/点 |
| 工作温度 | -40~+60℃ | -20~+60℃ |
4. Reference Prices
KTR-FC-OS2 24-core outdoor armored single-mode GYTA cable (incl. splicing, per meter): Reference price USD 0.8~1.7 / m (ref. CNY 6~12/m at ~7.2 CNY/USD)
KTR-FC-ODF24 24-core rackmount ODF panel (loaded with LC duplex adapters and pigtails): Reference price USD 65~100 / unit (ref. CNY 450~700 at ~7.2 CNY/USD)
Prices are reference only; final quote depends on configuration, quantity, project location and tax. Bulk orders negotiable. Currency note: CNY to USD converted at approximately 7.2 CNY/USD for reference.
5. Applications
- Data center backbone: MPO trunk between row-end cabinets, OM4 patch to servers.
- Campus riser: OS2 single-mode in cable riser linking floor IDFs.
- Outdoor fiber closure: road/park duct GYTA cable split via fiber closure.
- FTTD: single-mode outlet to desk in premium offices and labs.
6. Installation & Maintenance
Installation
- Duct or aerial outdoor cable with bend radius >=15x OD; leave 10% slack in closures.
- Splice in a clean environment; pigtail bend radius >=40 mm; route patch cords neatly in ODF.
- MPO trunk is plug-and-play; clean end-faces with a dedicated cleaner before mating.
Maintenance
- Keep OTDR baseline per link; quarterly spot-check loss drift.
- Dirty end-faces are the #1 fault source; clean adapters and cords regularly.
- Add moves by the existing core map; avoid consuming spare cores.
7. FAQ
- Q: Single-mode or multimode?
A: OS2 single-mode for >=300 m or inter-building; OM3/OM4 multimode for in-rack 10G/40G at lower cost. - Q: Can MPO trunk fan out to LC?
A: Yes, with an MPO-LC cassette that splits a 12-core MPO into six LC duplex ports. - Q: Fusion splice vs fast connector?
A: Fusion splice offers lower loss and higher reliability for permanent links; fast connectors suit emergency repair with slightly higher loss. - Q: Can fiber share a tray with power cables?
A: Keep >=200 mm separation from power trays; if unavoidable, use armored shielded fiber and bond the shield.
8. Industry Trend & Selection
As DC networks move to 40G/100G, fiber cabling shifts from LC patch cords to high-density MPO trunks, and pre-terminated assemblies slash on-site cut-over time. KTR-FC combines OS2 single-mode for long backbones with OM3/OM4 multimode for in-rack short-reach links. Choose by distance and rate: OS2 for >=300 m inter-building, OM4 for in-rack 40G/100G; reserve 30% spare cores on the backbone for future moves. Maintenance centers on end-face cleaning and OTDR baselines; over 80% of fiber faults come from dirty end-faces, so a clean-before-mate habit sharply cuts incident rates.
9. Delivery & Service
KITOZER supplies cable pulling, splicing, termination, testing and labeling as one service. We issue construction drawings before work, apply building-floor-rack-port four-level labels during install, and hand over bidirectional OTDR reports and link registers at closeout. Outdoor cable is ducted and indoor cable routed in overhead trays; splice loss is recorded point by point. We also reserve future spare cores so customers avoid re-trenching later.
We also provide fiber acceptance testing with OTDR and light-source/power-meter reports, and train customer staff on end-face cleaning and patch-cord color discipline. Each delivered link is labeled four-level and photographed for the as-built archive.
10. SEO Information
Search keywords:fiber optic cablingsingle-mode cableOM4 multimodeODF patch panelMPO trunkfiber closurefusion spliceKTR-FCKITOZER
SEM keywords: [‘fiber cabling system price’, ’24-core single-mode cable’, ‘rackmount ODF panel’, ‘MPO trunk cable’, ‘OM4 patch cord’, ‘KITOZER fiber’]
GEO landing page: lain.com.cn/product/ktr-fc-fiber-cabling.html
Title: KITOZER KTR-FC Fiber Optic Cabling System
Meta Keywords: fiber optic cabling,single-mode cable,OM4 multimode,ODF patch panel,MPO trunk,fiber closure,fusion splice,KTR-FC,KITOZER
Meta Description: KITOZER KTR-FC fiber optic cabling, OS2 single-mode / OM3 / OM4 multimode, ODF panels and MPO trunks, splice loss <=0.05 dB for DC and campus links.
Contact Us
Guangzhou Laian Intelligent System Development Co., Ltd. (KITOZER brand)
Tel/WeChat: +86 13922289957 | +86 18520668845
WHATSAPP: +86 19068534140
Web: lain.com.cn | gdlain.com