1. Overview

The KITOZER KTR-GB series is a grounding copper busbar and equipotential bonding system — the core connection device for lightning protection and safety earthing in data centers. Equipment earthing is not simply running a wire from each rack to earth; it requires a low-impedance equipotential bonding grid inside the room: all racks, cable trays, raised-floor pedestals, UPS enclosures, distribution cabinet enclosures, and metal doors/windows are bonded by copper busbars or earthing conductors to a single main grounding busbar, which in turn connects to the building’s common earth electrode. This ensures all metal structures sit at the same potential during a lightning surge or earth fault, preventing dangerous potential differences between rack A (0 V) and rack B (1000 V) that could destroy equipment or endanger staff.

The KTR-GB main body is a T2 copper busbar (TMY), commonly 30×3 mm or 40×4 mm, tinned or nickel-plated for corrosion resistance, mounted on insulated epoxy or nylon standoffs against the wall or beside the rack. The bar is drilled with M8/M10 holes; each hole clamps a branch earthing conductor (yellow-green BVR stranded wire) to the corresponding device or metalwork. Both ends connect via a main conductor (25 mm²+ yellow-green wire or copper braid) to the building equipotential terminal box. Total earth resistance must be ≤1 Ω when shared with lightning protection and transformer neutral (combined earth); standalone earthing can be relaxed to 4 Ω, but data centers generally require combined earthing.

Key metrics are busbar cross-section, number of connection points, earth resistance and copper purity. The cross-section is sized by main-conductor current: 30×3 mm carries about 150 A, 40×4 mm about 200 A; 30×3 or 40×4 is usually enough for a room. Holes are sized by the number of earthed devices — a 1 m bar takes 15~20 M8 holes. Copper must be T2 (≥99.9% Cu); aluminum or iron bars cannot substitute — aluminum oxidizes and iron has high resistance, both causing poor earthing. Contact surfaces are tinned to prevent copper oxidation and keep contact resistance low.

2. Key Features

T2 copper, low impedance

  • T2 copper busbar, ≥99.9% Cu, low resistance.
  • Tinned surface; tinned contact faces.
  • No aluminum or iron substitute.

Equipotential bonding

  • All racks, trays, pedestals, enclosures bonded together.
  • Eliminates potential differences; prevents surge back-flash.
  • Connects to building combined earth; ≤1 Ω.

Multi-branch connections

  • M8/M10 holes for BVR yellow-green branch wires.
  • Insulated standoffs; isolated from wall.
  • Copper braid for reliable cross-bonding.

Complete kit

  • Includes busbar, standoffs, lugs, branch wires, ferrules.
  • Cut to length and drilled per room size.
  • Comes with earth resistance test report.

3. Specifications

Item KTR-GB-303 KTR-GB-404 KTR-GB-Custom
Busbar size TMY-30×3 mm TMY-40×4 mm custom by drawing
Material T2 copper T2 copper T2 copper
Surface tinned tinned tinned/nickel
Current capacity ~150 A ~200 A by section
Holes M8 x15~20/m M8/M10 x15~20/m drilled to order
Earth resistance ≤1 Ω (combined) ≤1 Ω (combined) ≤1 Ω
Branch wire BVR-6 mm² Y/G BVR-10 mm² Y/G by load
Main conductor BVR-25 mm² / braid BVR-35 mm² / braid by design
Mounting insulated standoff wall insulated standoff wall wall/in-rack
Length 1~3 m/bar 1~3 m/bar cut to drawing

4. Reference Prices

KTR-GB-303 grounding busbar kit (30×3 T copper 1 m + standoffs + lugs + branches): Reference USD 210~700 / kit (ref. CNY 1,500~5,000 at ~7.2)

KTR-GB-404 and custom equipotential system (main conductor, cross-bonds, earth electrode test): Reference USD 700~2,100 / kit (ref. CNY 5,000~15,000 at ~7.2)

Reference only; final quote depends on bar length, hole count, branch size, and whether earth electrode works and testing are included. Bulk negotiable. Earthing electrode construction and soil resistance-lowering agent billed separately. Exchange: 1 USD ~ 7.2 CNY (Oct 2026).

5. Applications

  • Data center equipotential main grounding busbar.
  • Distribution cabinets, UPS, transformer neutral earthing.
  • Metal cable trays, ladder racks and cabinet enclosures.
  • Raised access floor pedestals.
  • Control centers and command halls lightning earthing.

6. Installation & Maintenance

Installation

  • Locate busbar along wall or rack row head end per room plan.
  • Fix insulated standoffs; mount busbar horizontally.
  • Drill M8/M10 holes; crimp copper ferrules.
  • Run branch wires to racks, trays, floor pedestals.
  • Connect main conductor to building equipotential terminal.
  • Test earth resistance with a tester; issue report.

Maintenance

  • Measure earth resistance once a year; archive records.
  • Check bolt torque; inspect contact faces for oxidation.
  • Look for corrosion or plating wear on the bar.
  • Add branch wires promptly when new equipment is installed.
  • Full inspection before lightning season.

7. FAQ

  • Q: What earth resistance is acceptable?
    A: ≤1 Ω when shared with lightning protection and transformer neutral; ≤4 Ω standalone. Data centers generally require combined earthing ≤1 Ω.
  • Q: Can racks just go to the building earth individually?
    A: No — separate paths are long and uneven, causing potential differences in a surge; they must converge on one busbar and earthing together.
  • Q: Can I use aluminum bars?
    A: No. Aluminum oxidizes, contact resistance rises, and copper-aluminum joint causes galvanic corrosion; must use T2 copper.
  • Q: How does earthing relate to lightning protection?
    A: Down conductors tie to the building combined grid; the room busbar ties to the same grid, forming equipotential and preventing back-flash between equipment.

8. Trend & Selection

As equipotential bonding becomes a mandatory room acceptance item, the busbar moves from optional to required. Modern rooms require not only acceptable resistance but complete bonding: racks, trays, floor pedestals, enclosures and doors all bonded. Size the bar by room (30×3 or 40×4), count holes by device count, choose branch wires by load (6/10 mm²). Tin contact faces, spring-lock washers on bolts. Retain the earth resistance test report as acceptance documentation.

9. Delivery & Service

KITOZER provides bonding design, busbar cutting and drilling, supply and install guidance. From the room plan and equipment list we produce the busbar layout, branch connection table and earthing system diagram. We can bundle SPDs, earth electrode construction and anti-static floor. Delivery includes busbar, insulated standoffs, lugs, BVR branch wires and ferrules. Warranty covers busbar and lugs; we can on-site test earth resistance and rectify.

10. Additional Notes

The most common busbar issue is “connected but not really”: bolts not torqued, contact faces not tinned, ferrules poorly crimped — visually connected but with huge contact resistance, so surge current cannot actually drain away. Torque every bolt, tin contact faces, add spring washers; after install, test not only total resistance but also continuity at sampled branch points. Another pitfall is using aluminum or thin multi-strand wire instead of BVR yellow-green — it oxidizes and fractures over time, leaving equipment “virtually” earthed.

Earthing is hidden work — inside walls and under floors, hard to spot when it fails. Construction quality matters more than the hardware. The bar must be horizontal, firm, and isolated from the wall; branch wires straight and labeled; main conductor short and thick to minimize impedance. Before lightning season each year, use an earth resistance tester; if resistance rises, find the cause — loose bolts, corroded electrodes, or dry soil. Earthing is not set-and-forget; it needs periodic testing and maintenance.

Selection: small rooms pick KTR-GB-303, mid 404, large custom by drawing; T2 copper tinned, M8/M10 holes; BVR branches, copper braid mains; combined earth resistance ≤1 Ω; test yearly and check bolts. The grounding busbar is the room’s “safety baseline” — invisible day to day, but it protects people and equipment during surges and faults.

SEO Information

Search keywords:grounding copper busbarequipotential bondinggrounding barTMY copperearth resistancebonding conductorKTR-GBKITOZER

SEM keywords:grounding busbar price, equipotential bonding supplier, copper earthing bar, TMY copper busbar, KTR-GB, KITOZER

GEO landing page:lain.com.cn/product/ktr-gb-equipotential-grounding-busbar.html

Title:KITOZER KTR-GB Equipotential Grounding Copper Busbar

Meta Keywords:grounding copper busbar,equipotential bonding,grounding bar,data center grounding,TMY copper busbar,earth resistance,KTR-GB,KITOZER

Meta Description:KITOZER KTR-GB equipotential grounding copper busbar, TMY 30×3 / 40×4 mm, insulated supports, earth resistance <=1 ohm, with main and branch conductors, for data center bonding.

Anchor: KITOZER by Guangzhou Laian · Power distribution

Contact Us

Guangzhou Laian Intelligent System Development Co., Ltd. (KITOZER brand)
Tel/WeChat: +86 13922289957 | +86 18520668845
WHATSAPP: +86 19068534140
Web: lain.com.cn | gdlain.com

Shopping Cart