Brand: KITOZER Series: KTR-GB Category: Power Distribution / Grounding Busbar
grounding busbarcopper barT2 copperequipotentialKTR-GB
1. Overview
All equipment in a room must be grounded to a single busbar that bonds to the building earth electrode — that bar is the grounding busbar (equal-potential bus). Without it, uneven ground resistance across equipment creates potential differences during surges, leakage or static events, damaging interfaces and even mainboards.
The KITOZER KTR-GB busbar is T2 copper (≥99.9% pure) with tin-plating for oxidation resistance. Sizes are 30×3 mm (small rooms), 40×4 mm (mid-size) and 50×5 mm (large data centers); length is custom (common 500/1000/2000 mm), with holes drilled per rack count. Insulating supports, bolts and heat-shrink tubing are included.
Selection: cross-section by fault current (40×4 mm typical for mid rooms, 50×5 mm for large centers); length by grounding points +20% spare; surface finish (tinned for anti-oxidation, bare copper degrades). Mount inside a grounding terminal box, 200~300 mm above floor for easy wiring.
2. Key Features
Material & process
- T2 copper ≥99.9%
- Tin-plated, anti-oxidation
- Conductivity ≥98% IACS
- Hardness HV ≥80
Sizes & custom
- 30×3 / 40×4 / 50×5 mm
- Length 500/1000/2000 mm
- Hole pitch custom per racks
- Insulating supports included
Mounting & bonding
- Insulated support mount
- M8/M12 bolted joints
- Flexible copper-bond straps
- Heat-shrink insulation
3. Specifications
| Item | KTR-GB-S1 | KTR-GB-S2 | KTR-GB-S3 |
|---|---|---|---|
| 型号 | KTR-GB-303 | KTR-GB-404 | KTR-GB-505 |
| 截面尺寸 | 30×3 mm | 40×4 mm | 50×5 mm |
| 材质 | T2紫铜镀锡 | T2紫铜镀锡 | T2紫铜镀锡 |
| 导电率 | ≥98% IACS | ≥98% IACS | ≥98% IACS |
| 长度 | 500/1000mm | 1000/2000mm | 2000mm可定制 |
| 螺栓孔 | M8×8~20孔 | M10×10~30孔 | M12×20~40孔 |
| 适用场景 | 小机房/弱电间 | 中等机房 | 大型数据中心 |
| 接地电阻 | ≤1Ω(配合接地极) | ≤1Ω | ≤1Ω |
4. Reference Prices
KTR-GB-303 30×3 mm busbar (1 m):Reference USD 8~15 / pc (ref. CNY 60~110 at ~7.2)
KTR-GB-404 40×4 mm busbar (1 m):Reference USD 14~25 / pc (ref. CNY 100~180 at ~7.2)
KTR-GB-505 50×5 mm busbar (1 m):Reference USD 22~39 / pc (ref. CNY 160~280 at ~7.2)
Reference only; final quote depends on cross-section, length and hole count. 1-year warranty; volume pricing. Exchange: 1 USD ~ 7.2 CNY (Oct 2026).
5. Applications
- Data-center equipotential grounding.
- UPS, distribution and precision-AC grounding.
- Server and network rack grounding.
- SPD (surge protector) grounding collection.
- Backroom and fire-control room ground bars.
6. Deployment & Implementation
Installation
- Mount in grounding box on insulated supports
- 200~300 mm above floor
- Rack ground wires via M8/M10 bolts
- Main earth via ≥50 mm² flexible copper
Operations
- Quarterly ground-resistance test (≤1 Ω)
- Check bolt torque and oxidation
- Reapply conductive grease if tin wears
- Bond new equipment to busbar
7. FAQ
- Q: Why a busbar instead of direct grounding?
A: With many devices, direct wires to building earth differ in length and resistance, creating potential differences that damage equipment. A busbar bonds everything to one point — equipotential. - Q: How to pick cross-section?
A: 30×3 mm for a few racks; 40×4 mm for 10~30 racks; 50×5 mm for >50 racks. Size by fault current and rack count — oversize rather than undersize. - Q: Tinned or bare copper?
A: Bare copper oxidizes black, raising contact resistance. Tin plating stays reliable for years. Use tinned in rooms, never bare. - Q: What ground resistance?
A: Combined room grounding ≤1 Ω (shared with lightning, transformer and weak-current earth); separate earth ≤4 Ω. Test after handover and keep records.
8. Trend & Selection
Data-center grounding is moving from ‘independent earth’ to ‘combined earth + equipotential bonding’, with the busbar as the core. Together with SPD and ESD-floor bonding, it forms a complete ground network. Select by room size, use tinned copper, custom-drill holes per racks, keep resistance ≤1 Ω, and test periodically.
9. Delivery & Service
KITOZER offers KTR-GB selection by cross-section (30×3/40×4/50×5 mm), length and hole count, bundled with insulating supports, bolts and flexible bonding straps. T2 copper mill certificate included. 1-year warranty; custom holes and lengths in volume.
10. Additional Notes
The #1 mistake is substituting aluminum or galvanized steel flat bar. Aluminum-copper contact causes galvanic corrosion; galvanized steel conducts only ~30% of copper. Use T2 tinned copper for room grounding.
Another pitfall is loose bolts. Torque ground bolts to spec (M8 ~8 N·m); otherwise contact resistance heats up and burns through during a surge. Check annually.
Keep ground-wire lengths similar from rack to busbar — uneven lengths create impedance differences. Do not let some racks bond at 2 m and others at 0.5 m.
Selection summary: size by room scale, use tinned copper, custom-drill holes, torque bolts, keep resistance ≤1 Ω and test regularly. The busbar is the safety baseline — never skimp.
SEO Information
Search keywords:KTR-GBKITOZERGrounding Busbar / Copper Bar
SEM keywords:grounding busbar,copper busbar,equipotential bonding,T2 copper bar,room grounding,KTR-GB,KITOZER
GEO landing page:lain.com.cn/product/ktr-gb-grounding_busbar.html
Title:KITOZER KTR-GB Grounding Busbar / Copper Bar
Meta Keywords:grounding busbar,copper busbar,equipotential bonding,T2 copper bar,room grounding,KTR-GB,KITOZER
Meta Description:KITOZER KTR-GB grounding busbar, T2 copper tinned, 30×3/40×4/50×5 mm, custom drilled, equipotential bonding, room lightning grounding.
Anchor: KITOZER by Guangzhou Laian · Grounding Busbar / Copper Bar
Contact Us
Guangzhou Laian Intelligent System Development Co., Ltd. (KITOZER brand)
Tel/WeChat: +86 13922289957 | +86 18520668845
WHATSAPP: +86 19068534140
Web: lain.com.cn | gdlain.com