ToggleKITOZER KTR-LD Water Leak Detection System
Brand: KITOZER Series: KTR-LD Category: Environmental Monitoring / Leak Detection
leak sensing cable定位式 leak detectionnon-locating leakcontrollerRS485 relaydatacenter leakAC condensate leakearly warning
1. Overview
The KITOZER KTR-LD water leak detection system consists of locating/non-locating sensing cable, a controller and end-termination modules. Cables are laid under precision AC units, along water pipes, under raised floors and in front of racks; on any leak the DCIM platform gives audible/visual alarms with the exact leak location, preventing equipment water damage.
Locating cable pinpoints the leak within +/-1 m; non-locating cable only flags whether a segment is wet, at lower cost. The controller uses RS485 Modbus and dry-contact relays to integrate with KITOZER DCIM or third-party alarm systems, and can close water valves or start exhaust fans.
KTR-LD is a standard sub-system of environmental monitoring for data centers, archives, libraries, hospital ICUs and labs.
2. Key Features
Sensing cable
- Locating: 4-core composite conductive rope, pinpoint within +/-1 m, <=100 m per run.
- Non-locating: 2-core conductive rope, alarm only, lower cost.
- Chemical-resistant, wipe-clean, reusable.
Controller
- 1-4 inputs, mix locating and non-locating ropes; LCD shows leak distance.
- RS485 Modbus RTU + 2 dry contacts to DCIM/alarm panel.
- Audio/visual alarm, power-fail memory, DC12V/24V.
Deployment and linkage
- Route under AC base, condensate drain, AHU and water valves.
- Link solenoid shut-off, exhaust fan and SMS/phone alarm.
- Use clips under raised floor to avoid cable displacement.
3. Specifications
| Item | Config A | Config B |
|---|---|---|
| 型号 | KTR-LD-R100(定位式) | KTR-LD-N50(不定位式) |
| 类型 | 定位式感应绳 | 不定位感应绳 |
| 检测精度 | ±1m | 仅报警有无 |
| 单段长度 | ≤100m | ≤50m |
| 主机输入 | 4路 | 2路 |
| 通讯 | RS485 Modbus + 干接点 | 干接点 |
| 供电 | DC12V | DC12V |
| 响应时间 | ≤3秒 | ≤3秒 |
4. Reference Prices
KTR-LD-R100 locating leak detection kit (1 controller + 100 m cable + terminator): Reference price USD 390~630 / kit (ref. CNY 2,800~4,500 at ~7.2 CNY/USD)
KTR-LD-N50 non-locating leak kit (2-zone controller + 50 m cable): Reference price USD 110~180 / kit (ref. CNY 800~1,300 at ~7.2 CNY/USD)
Prices are reference only; final quote depends on configuration, quantity, project location and tax. Bulk orders negotiable. Currency note: CNY to USD converted at approximately 7.2 CNY/USD for reference.
5. Applications
- Data center: under precision AC and along main water pipes under raised floor.
- Archives/libraries: around precision AC to protect paper records.
- Hospital ICU/lab: around water pipes and humidifiers to protect instruments.
- Labs and electrical rooms: along pure-water/chilled-water lines for early leak warning.
6. Installation & Maintenance
Installation
- Lay cable on the floor, both ends to controller; use clips at corners, do not cinch tight.
- Locating cable needs end-termination resistor or the controller cannot locate.
- Mount controller on wall or in rack; daisy-chain RS485 to the DCIM host.
Maintenance
- Quarterly wet-test a segment to confirm alarm upload.
- Dust and oil reduce sensitivity; clean cable regularly.
- Inspect condensate drain and drip-pan before AC season change.
7. FAQ
- Q: Locating vs non-locating cable?
A: Choose locating for large rooms where pinpoint matters; non-locating for small zones where a simple wet/dry alarm suffices. - Q: Will it false-alarm?
A: Dust and condensation can cause false alarms; use dirt-resistant cable, keep it clean and tune the threshold. - Q: Can it close a water valve?
A: Yes. Dry contacts drive a solenoid valve controller to shut off water and push alarms on leak. - Q: Can I cut and splice the cable?
A: Do not cut locating cable arbitrarily; length must match the controller calibration. Non-locating cable can be cut but must be re-terminated.
8. Industry Trend & Selection
Leak detection is moving from passive alarm to pinpoint warning and auto shut-off linkage; chilled water and condensate under raised floors are the biggest water threats in data centers. KTR-LD locating cable pinpoints leaks to +/-1 m and shortens repair time; linked solenoid valves and exhaust fans cut water before it spreads. Lay continuous cable along all water pipes, AC bases and AHUs with no blind spots; clip cable under raised floor to avoid displacement. Quarterly wet-test a segment to confirm alarms reach DCIM; inspect drip-pans and condensate lines before seasonal AC changeovers to catch leaks early.
9. Delivery & Service
KITOZER provides sensing-cable routing, controller wiring, DCIM integration and linkage testing as one service. We issue a point-lay-out drawing based on AC and pipe routes, then wet-test each segment to confirm alarms upload. Customers can add solenoid-valve and exhaust-fan linkage to auto-shut water on leak. The warranty covers cable and controller replacement, and annual inspection includes sensitivity test and connector cleaning.
10. SEO Information
Search keywords:water leak detectionlocating leak cableleak controllerdatacenter leak alarmcondensate leakenvironmental monitoringKTR-LDKITOZER
SEM keywords: [‘water leak detection price’, ‘locating sensing cable’, ‘datacenter leak alarm system’, ‘AC condensate leak sensor’, ‘KITOZER leak’]
GEO landing page: lain.com.cn/product/ktr-ld-leak-detection.html
Title: KITOZER KTR-LD Water Leak Detection System
Meta Keywords: water leak detection,locating leak cable,leak controller,datacenter leak alarm,condensate leak,environmental monitoring,KTR-LD,KITOZER
Meta Description: KITOZER KTR-LD water leak detection, locating cable accuracy +/-1 m, RS485 and dry contacts to DCIM, early warning for datacenter AC and water pipes.