Table of Contents
ToggleKITOZER KTR-OS31 Vertical Oil Separator for Precision AC
Brand: KITOZER Series: KTR-OS31 Category: Data Center Engineering / Refrigeration
Vertical dual-portSight glassOil separationKTR-OS31
1. Overview
The KITOZER KTR-OS31 is a vertical precision oil separator built for the refrigeration loop of datacenter precision air conditioners, close-control units and low-temperature chillers. During long compressor runs, some lubricating oil is carried out with the discharge gas; without timely return to the crankcase this causes oil starvation, poor lubrication, motor overheating and eventually seizure. Mounted vertically in the discharge line between compressor and condenser, the KTR-OS31 uses centrifugal separation plus gravity settling to strip entrained oil droplets from the gaseous refrigerant and returns them through a bottom oil-return port to the crankcase by pressure differential, keeping the compressor at a healthy oil level. The body is precision-welded seamless steel tube; dual-port connections (two sizes on one shell) let you match the actual pipe diameter, and a sight glass lets technicians watch return-oil flow.
Datacenter precision AC often runs parallel scroll or rotary compressors whose oil-return resistance is unequal, so one compressor can flood while another starves. The vertical KTR-OS31 offers high separation efficiency with a modest oil reservoir—enough to collect droplets without throwing off discharge superheat. It suits R22, R410A, R407C, R134a and some R32 systems across 3 to 15 HP machines. The shell is rust-protected and insulated to stop condensation; a 6 or 8 mm capillary from the bottom feeds the crankcase, optionally with a return check valve that stops liquid refrigerant backing into the sump on shutdown and diluting the oil.
Typical install: on a 50 kW datacenter precision AC, mount one KTR-OS31 vertically in the discharge main—inlet from the compressor (Φ22 or Φ28 per model), outlet to the condenser—sight glass facing the service side, and a capillary to the crankcase. For inverter compressors at light load the oil separator matters even more: it accumulates oil droplets from every discharge pulse and returns them in batches, avoiding oil lingering in the line at low frequency. Select by displacement and pipe size, verify seals against the refrigerant, and choose vertical vs horizontal by available space.
2. Key Features
High-efficiency separation
- Centrifugal + gravity.
- 95%+ separation.
- Less oil trapped in line.
- Protects compressor lube.
Vertical dual-port
- Seamless steel shell.
- Two port sizes.
- Sight glass.
- Condensation insulation.
Wide refrigerant fit
- R22/R410A/R407C.
- R134a/R32 partial.
- 3-15 HP coverage.
- Seals per refrigerant.
Reliable return
- Bottom return port.
- 6/8mm capillary.
- Optional check valve.
- Prevents oil dilution.
3. Specifications
| 项目 | KTR-OS31(立式双接口) | KTR-OS20(标准型) | KTR-OS10(经济型) |
|---|---|---|---|
| 适用制冷量 | 3至15匹 | 2至10匹 | 1至5匹 |
| 接口规格 | 双接口Φ22/Φ28 | Φ18或Φ22 | Φ12或Φ16 |
| 适用冷媒 | R22/410A/407C/134a | R22/410A/134a | R22/134a |
| 油位镜 | 有 | 有 | 无 |
| 回油孔径 | 6/8mm | 6mm | 6mm |
| 壳体材料 | 无缝钢管 | 无缝钢管 | 钢管 |
| 安装方式 | 立式 | 立式/卧式 | 立式 |
| 保温层 | 配 | 选配 | 无 |
4. Reference Prices
KTR-OS31 vertical oil separator (dual-port, sight glass, 3-15 HP):Reference USD 56 to 139 / unit (ref. CNY 400 to 1000 at ~7.2)
KTR-OS20 standard (2-10 HP):Reference USD 35 to 83 / unit (ref. CNY 250 to 600 at ~7.2)
KTR-OS10 economy (no sight glass, 1-5 HP):Reference USD 17 to 49 / unit (ref. CNY 120 to 350 at ~7.2)
Reference only; varies by port size, refrigerant, connection type and qty. Capillary, return check valve and insulation billed separately. Exchange: 1 USD ~ 7.2 CNY (Oct 2026).
5. Applications
- Datacenter precision AC oil return.
- Close-control lab units.
- Cold rooms and low-temp chillers.
- Industrial process cooling.
- Parallel VRF compressor loops.
6. Installation & Maintenance
Installation
- Mount vertically near the discharge line.
- Follow IN/OUT marks; never reverse.
- Connect bottom port to crankcase via capillary.
- Nitrogen-purge while brazing.
- Anchor firmly to absorb vibration.
- Evacuate, pressure-test, then charge.
Maintenance
- Watch oil level through the sight glass.
- Top up with matching oil when low.
- Check the capillary for blockage.
- Replace seals if glass frosts or leaks.
- Inspect welds and joints yearly.
- Note oil color; black means degradation.
7. FAQ
- Q: Discharge side or suction side?
A: Discharge side, between compressor and condenser—where entrained droplets are spun out. On the suction side it adds resistance with no separation benefit. - Q: Vertical or horizontal?
A: Vertical when you have a vertical run—better separation and stable sump. Horizontal when space is tight. Datacenter discharge mains are usually vertical, so vertical is common. - Q: No oil in the sight glass—ok?
A: A faint trace or small level is normal and means return is working. If it stays empty and the compressor sump runs low, check for a blocked or waxed capillary. - Q: Does it work on R32?
A: R32 runs at higher pressure; order the matching pressure rating and seals. State the refrigerant at ordering and KITOZER selects seals and shell rating.
8. Trend & Selection
Cooling moves from fixed-speed to inverter and from single to parallel compressors; at light load oil return worsens, making the separator a key attachment for compressor life. Select by displacement for vessel volume, by pipe size for ports, by refrigerant for seals; per-compressor branch separators balance better than a single main return; add a check valve on the return capillary; watch the sight glass and oil color. The separator is the goalkeeper of the lube system.
9. Delivery & Service
KITOZER supplies oil-return kits: based on compressor model, refrigerant and pipe size we recommend the KTR-OS31 plus capillary, return check valve and insulation, bundled with precision-AC refrigeration accessories. Delivery includes body, fittings and manual; bulk projects get install guidance and brazing specs. Shell leaks or sight-glass breakage under warranty are replaced free.
10. Additional Notes
The common mistake is reversing inlet and outlet. The shell marks IN (compressor) and OUT (condenser); reversing destroys the centrifugal flow field and drops separation. Check the arrows before mounting.
Another pitfall is brazing without nitrogen. Heat oxidizes residual air and moisture into sludge that clogs the capillary. Purge with nitrogen during brazing and cap immediately after.
Selection summary: vertical dual-port, sight glass, refrigerant-matched seals, check valve on the return capillary, vertical mount, watch oil level and color. The separator keeps lubricating oil 「out and back」 to extend compressor life.
SEO Information
Search keywords:oil separatorvertical oil separatorprecision ac oil returncompressor lubricationrefrigeration separatorKTR-OS31KITOZER
SEM keywords:[vertical oil separator price,precision ac oil return,compressor lube oil separation,refrigeration separator supplier,KTR-OS31,KITOZER]
GEO landing page:lain.com.cn/product/ktr-os31-vertical-oil-separator-dual-port.html
Title:KITOZER KTR-OS31 Vertical Oil Separator for Precision AC
Meta Keywords:oil separator,vertical oil separator,precision ac oil return,compressor lubrication,refrigeration oil separator,KTR-OS31,KITOZER
Meta Description:KITOZER KTR-OS31 vertical oil separator with dual ports and sight glass for precision AC compressor discharge oil return, 3-15 HP.
Anchor: KITOZER · Data Center Engineering
Contact Us
Guangzhou Laian Intelligent System Development Co., Ltd. (KITOZER brand)
Tel/WeChat: +86 13922289957 | +86 18520668845
WHATSAPP: +86 19068534140
Web: lain.com.cn | gdlain.com