Table of Contents
ToggleKITOZER KTR-OS47 Horizontal Dual-Tank Oil Separator / High-Flow Parallel Separation
Brand: KITOZER Series: KTR-OS47 Category: Data Center Engineering / Oil Separator
dual-tankhorizontalhigh flowparallelKTR-OS47
1. Overview
KITOZER KTR-OS47 is a horizontal dual-tank oil separator designed for large data center chillers and multi-compressor parallel refrigerant racks. When a single compressor’s discharge exceeds one vessel’s capacity, or several compressors share a common discharge header, a single vessel runs too fast for droplets to settle and separation efficiency drops. The dual-tank design splits inlet gas into two parallel vessels, each taking half the flow; lower gas velocity gives droplets time to settle by gravity and inertia, then multi-stage filter cartridges capture the mist.
The two horizontal drums sit side by side on a common skid: an inlet manifold distributes discharge evenly to both vessels, and an outlet manifold combines cleaned vapor before it goes to the condenser. Each drum has its own bottom sump and return port for independent or common oil return. This parallel skid is essentially two single separators in one frame, taking less footprint than two standalone units with fewer welded joints.
In data center plants, a centrifugal chiller or multiple screw compressors share a large discharge header. The KTR-OS47 doubles capacity without increasing drum diameter, suiting high-capacity oil-loop protection. Paired with a liquid receiver and drier-filter, it forms the oil-management and liquid-buffer package on the refrigeration side.
2. Key Features
Dual parallel vessels
- Two horizontal drums double capacity.
- Inlet manifold splits flow evenly.
- Lower velocity keeps separation stable.
Skid integration
- Common base with integrated manifolds.
- Smaller footprint than two units.
- Fewer welded joints and leak points.
Staged separation
- Baffles give inertia/gravity pre-separation.
- Replaceable cartridges capture micron mist.
- Bottom sump settles droplets.
Return & monitoring
- Independent sump per drum, single or common return.
- Side sight glass for oil level.
- Top pressure tap, bottom drain.
3. Specifications
| Item | KTR-OS47-200 | KTR-OS47-300 | KTR-OS47-400 |
|---|---|---|---|
| Gas flow (m³/h) | ~2200 | ~3300 | ~4500 |
| Vessels | 2 parallel | 2 parallel | 2 parallel |
| Port size | DN150 flange | DN200 flange | DN250 flange |
| Separation | baffle+cartridge | baffle+cartridge | baffle+cartridge |
| Working pressure (MPa) | 3.0 | 3.0 | 3.0 |
| Working temp (℃) | -20~120 | -20~120 | -20~120 |
| Oil return | float+solenoid | float+solenoid | solenoid |
| Mounting | horizontal skid | horizontal skid | horizontal skid |
4. Reference Prices
KTR-OS47-200 small dual-tank (DN150, cartridges, sight glass): Reference USD 1,778~3,000 / unit (ref. CNY 12,800~21,600 at ~7.2)
KTR-OS47-300 medium dual-tank (DN200, common sump, gauge): Reference USD 3,111~5,111 / unit (ref. CNY 22,400~36,800 at ~7.2)
KTR-OS47-400 large dual-tank (DN250, solenoid return, skid base): Reference USD 5,361~8,611 / unit (ref. CNY 38,600~62,000 at ~7.2)
Reference only; by gas flow, port size and vessel config. Piping and installation excluded. Exchange: 1 USD ~ 7.2 CNY (Oct 2026).
5. Applications
- Discharge-header separation for large chillers.
- Shared oil separation for parallel compressors.
- Central plant refrigeration skids.
- Retrofits where a single vessel is undersized.
- High-capacity centrifugal/screw loops.
6. Installation & Maintenance
Installation
- Locate between discharge header and condenser.
- Level the skid; orient ports to flow.
- Connect inlet manifold to header, outlet to condenser.
- Run oil return to crankcase or common sump.
- Fit drain valve to oil drum.
- Connect top pressure gauge.
- Pressure-test, charge and run.
Maintenance
- Check sight glass on each drum.
- Track filter dp; change when high.
- Annually swap cartridges and clean drums.
- Verify solenoid return valve operation.
- Drain oil and sludge regularly.
- Check manifold for uneven flow split.
7. FAQ
- Q: Dual-tank or large single vessel?
A: Choose dual-tank parallel where flow is high but headroom is limited (smaller drums, lower profile); choose a large single vessel where height allows and you want to save one drum. Dual also allows one drum serviced while the other runs. - Q: Will flow split unevenly?
A: A symmetric manifold is nearly balanced; if one cartridge clogs, dp rises and flow shifts. Change cartridges by dp to keep both vessels balanced. - Q: How often to change cartridges?
A: By pressure differential; rising dp means saturation. Generally 1~2 years with compressor service. - Q: Can one drum be a standby?
A: Add isolation valves on the manifold; one drum can be serviced while the other runs at half capacity and reduced load.
8. Trend & Selection
Data center cooling moves toward high capacity and parallel compressors, pushing separators from single vessels to parallel dual-tank skids that boost throughput without enlarging drum diameter and cut field welding. Size by total header flow with 1.2x headroom, match header diameter, choose dual-tank where height is constrained, balance both vessels, pick float+solenoid return, and change cartridges by dp.
9. Delivery & Service
KITOZER selects dual-tank separators by compressor count, total header flow, port size, refrigerant and layout space, configuring vessel count, manifolds, return method and cartridges. We provide a skid piping drawing and pressure rating sheet. Delivery includes two drums, manifold base, spare cartridges, sight glass, return/drain ports and flange bolts. Warranty covers installation guidance and leak re-check.
10. Additional Notes
The common pitfall is sizing by header diameter rather than total discharge. Header is DN200 so a DN200 dual-tank is picked, but all parallel compressors at full load exceed its capacity and each drum still runs too fast. Add up all compressor discharge volumes and size the dual-tank by the total flow.
Another pitfall: replacing cartridges on only one drum. One new and one old cartridge create a resistance mismatch that shifts flow, overloading the new drum and starving the old. Replace both at the same time to keep resistance equal.
Selection summary: size by total header flow with headroom; dual-tank suits high-flow, low-headroom spots; skid manifolds cut field welding; swap both cartridges together; follow the flow arrow; pressure-test and watch the sight glass. The separator keeps oil in under high flow, and the compressors last.
Contact Us
KITOZER brand (professional data center & low-voltage equipment supplier)
Tel/WeChat: +86 13922289957 | +86 18520668845
WHATSAPP: +86 19068534140