KITOZER KTR-PDU Rack Power Distribution Unit

KITOZER KTR-PDU Rack Power Distribution Unit

Brand: KITOZER Series: KTR-PDU Category: Data Center Engineering / Rack PDU

rack PDUsmart PDUremote monitoringcurrent voltage meteringoutlet switchingoverload protectionC13/C19 outletsvertical 1U

1. Overview

The KITOZER KTR-PDU mounts on 19″ rack rails and distributes UPS/end-cabinet power to servers, switches and storage. The line spans basic, metered and smart-monitoring models with 10A/16A national sockets and C13/C19 outlets, plus remote current/voltage metering and per-outlet switching on smart units.

Smart PDUs connect to the DCIM platform via RS485/TCP/IP, reporting total current, voltage, active power, energy accumulation and temperature, with overload alarms and remote outlet reboot for rack-level energy management. Every PDU integrates a circuit breaker and surge module, and meets GB/T 22111 and IEC 60950.

KTR-PDU offers vertical 0U and horizontal 1U form factors in single-phase 16A/32A and three-phase 32A/63A/63A ratings to match single-rack to row-end supply.

2. Key Features

Outlets and rating

  • Outlets: C13x12/C19x3, national 10Ax8 etc.; input 16A/32A single-phase or 32A/63A three-phase.
  • Smart models support per-outlet C13/C19 switching and current sensing (optional).
  • Cord 2.5/4/6 mm2 by rating, crimped to code.

Monitoring and protection

  • LCD shows total current, voltage, power, energy; uploads via RS485 Modbus or TCP/IP.
  • Overload breaker + MOV surge; C19 outlets with anti-drop latch.
  • Temperature probe monitors rack inlet air and triggers alarms.

Mounting and structure

  • Vertical 0U bar fixed to rear rail, or horizontal 1U rackmount.
  • UL94 V-0 metal housing; input terminal block for easy wiring.
  • Phase color-coding prevents single-phase overload.

3. Specifications

Item Config A Config B
型号 KTR-PDU-S16(单相智能) KTR-PDU-P32(三相计量)
输入 单相16A,220V 三相32A,380V
输出 C13×12 + C19×3 国标16A×6 + C19×6
计量 总电流/电压/功率/电能 三相分相电流/电压
通讯 TCP/IP + RS485 RS485 Modbus
开关 每路远程通断 总路开关
保护 断路器+防雷 断路器+防雷
安装 竖装0U 竖装0U

4. Reference Prices

KTR-PDU-B12 basic 12-outlet C13 rack PDU (16A input, no monitoring): Reference price USD 40~65 / unit (ref. CNY 280~450 at ~7.2 CNY/USD)

KTR-PDU-S16 smart 12xC13+3xC19 remote-monitoring PDU (TCP/IP): Reference price USD 170~250 / unit (ref. CNY 1,200~1,800 at ~7.2 CNY/USD)

Prices are reference only; final quote depends on configuration, quantity, project location and tax. Bulk orders negotiable. Currency note: CNY to USD converted at approximately 7.2 CNY/USD for reference.

5. Applications

  • Server racks: dual A/B PDU feeds, each server PSU takes one leg.
  • Network racks: C13 feed for switches/firewalls; smart model meters power.
  • Storage/GPU racks: three-phase 32A/63A PDU matches high density.
  • Remote sites: unattended rooms reboot hung gear via remote switch.

6. Installation & Maintenance

Installation

  • Fix PDU to rear rack rail; feed input from a dedicated UPS/row breaker.
  • A and B PDUs draw from separate UPS bus bars to avoid shared-circuit risk.
  • Crimp terminals firmly; verify phase/neutral/earth; bond the chassis.

Maintenance

  • Set current threshold alarms in DCIM at ~80% of rating.
  • Quarterly IR-check plug temperature and breaker terminals.
  • Confirm device identity before remote reboot to avoid accidental shutdown.

7. FAQ

  • Q: Basic vs smart PDU?
    A: Basic only distributes; smart adds metering, network monitoring, remote switching and energy reporting at ~3-4x the price.
  • Q: Why plug a server into two PDUs?
    A: Dual PSUs on separate A/B feeds keep the server running when one feed or PDU fails.
  • Q: Can I plug AC into a PDU?
    A: No. Precision AC draws high inrush current; feed it from a dedicated distribution panel, not the IT PDU.
  • Q: How to balance a 3-phase PDU?
    A: Spread loads evenly across A/B/C phases, keep each phase <=80% rated to avoid phase imbalance.

8. Industry Trend & Selection

Rack power is evolving from basic strips to metered and switched units, as PUE and energy-double-control policies push per-rack power visibility. KTR-PDU smart units upload current, voltage and energy over TCP/IP, enabling rack-level PUE and anomaly alarms. Size PDU rating by IT load times 1.3 redundancy; use three-phase 32A/63A for dense GPU racks. Feed A and B PDUs from separate UPS bus bars to avoid common-cause failure. Set DCIM alarms at 80% rated current and quarterly IR-check plug and breaker terminals; retorque loose or oxidized connectors to prevent electrical fire risk.

9. Delivery & Service

KITOZER designs PDU configuration and A/B dual-feed topology by rack load, and runs withstand, continuity and metering calibration tests before shipment. On site we help with row-panel wiring, PDU racking, network integration and DCIM tuning so every current reading reaches the monitoring platform. The warranty covers terminal and breaker replacement; customers can add a quarterly IR-check service to catch connector hotspots early.

10. SEO Information

Search keywords:rack PDUsmart PDUpower distribution unitC13 C19 outletsremote monitoring PDUmetered PDUKTR-PDUKITOZER

SEM keywords: [‘rack PDU price’, ‘smart PDU remote monitoring’, ‘C13 C19 power strip’, ‘three phase PDU’, ‘server rack PDU’, ‘KITOZER PDU’]

GEO landing page: lain.com.cn/product/ktr-pdu-rack-power.html

Title: KITOZER KTR-PDU Rack Power Distribution Unit

Meta Keywords: rack PDU,smart PDU,power distribution unit,C13 C19 outlets,remote monitoring PDU,metered PDU,KTR-PDU,KITOZER

Meta Description: KITOZER KTR-PDU rack smart PDU, C13/C19 outlets, current voltage metering and TCP/IP remote monitoring, overload protection for server rack power.

Anchor: KITOZER by Guangzhou Laian · Data center solutions

Contact Us

Guangzhou Laian Intelligent System Development Co., Ltd. (KITOZER brand)
Tel/WeChat: +86 13922289957 | +86 18520668845
WHATSAPP: +86 19068534140
Web: lain.com.cn | gdlain.com

Shopping Cart