ToggleKITOZER KTR-PSM8 Power SPD / Single-Phase Class B+C 20kA
Brand: KITOZER Series: KTR-PSM8 Category: Power Distribution / Surge Protection
Single-phase SPDCombined B+C20kInRemote alarmDIN rail
1. Overview
Lightning electromagnetic pulses and switching surges travel in on the power line and damage UPS, servers and network gear. Protection is staged: a high-energy Class B (Type I) arrester at the building mains, a Class C (Type II) unit at the floor/room distribution, and fine D-class (Type III) protection near equipment. Energy is dissipated stepwise through decoupling distance or chokes so residual voltage drops at each stage. A combined B+C module packs two stages into one device, saving cabinet space and suiting retrofits.
The KITOZER KTR-PSM8 is a single-phase combined B+C power SPD for 230V AC feed, wired L/N/PE. Nominal discharge current In=20kA (8/20us), max Imax=40kA, voltage protection level Up<=1.5kV. It plugs on a DIN rail and shows a status window: green healthy, red failed, with a remote dry contact to the environmental system. Overheated chips thermally disconnect from the grid to prevent fire. Failed modules swap out without rewiring.
Selection confirms single vs three phase (this model is single-phase; choose 3/4-pole for 380V), that In meets this protection stage, that Up stays below the equipment’s impulse withstand, and whether remote signaling is needed. Mount upstream of the UPS or at distribution feeder, keep the ground lead short and thick, and target a bonding resistance of <=1 or <=4 ohm. SPDs wear out; replace when the window turns red.
SPD selection is not just a numbers game on discharge current; the coordination between stages matters just as much. If the upstream Type I arrester and this downstream B+C module are too close together without decoupling inductance, they may share current poorly, and the weaker one can fail prematurely. Install the recommended distance – typically 5-10 meters of cable – or add a dedicated decoupling reactor between the two stages. Also size the protection by the equipment’s impulse withstand: servers commonly tolerate only around 1.5 kV of surge, so an SPD with a higher Up does not protect them even if its kA rating looks impressive. After a nearby lightning event, read the counter or inspect the window, because a heavy strike ages the MOV even if the unit still appears green. Keep a spare module on the shelf so a red window means a 10-minute swap instead of a waiting period. Finally, document the protection architecture on the cabinet door: which stage this module represents, what upstream arrester it coordinates with, and the earth-bonding point, so the next technician is not guessing during an alarm.
2. Key Features
Combined B+C
- Two-stage MOV in one module.
- In=20kA, Imax=40kA (8/20us).
- Up<=1.5 kV residual.
- Saves cabinet space.
Status and signaling
- Green/red visual window.
- Remote dry contact to DCIM.
- Remote failure alarm.
- Quick visual check.
Safety and service
- Thermal disconnection on overheat.
- DIN-rail plug-in, module swap.
- Standard L/N/PE wiring.
- Failure does not cut load.
Stage coordination
- Decouple 5-10 m from upstream Type I.
- Match Up to equipment’s 1.5 kV withstand.
- Read counters after storms.
- Keep a spare module on site.
3. Specifications
| Item | Specification |
|---|---|
| Type | Single-phase B+C power SPD |
| Nominal voltage | 230V AC (single phase) |
| Nominal discharge In | 20 kA (8/20us) |
| Max discharge Imax | 40 kA (8/20us) |
| Voltage protection Up | <= 1.5 kV |
| Wiring | L/N/PE, DIN rail |
| Alarm | Dry contact + window |
| Fail-safe | Thermal disconnector |
| Response time | < 25 ns |
| Environment | -40 to +80 C, indoor |
4. Reference Prices
KTR-PSM8 single-phase B+C module: USD 25~50 (ref. CNY 180~360)
Spare MOV cartridge: USD 11~22 (ref. CNY 80~160)
Status-monitoring base: USD 6~11 (ref. CNY 40~80)
Reference only; final quote applies. 1-year warranty. Bulk pricing available. Certificate and manual included. Exchange: 1 USD ≈ 7.2 CNY.
5. Applications
- Second-level protection in room PDUs.
- UPS upstream surge protection.
- Distribution feeder branches.
- Weak-current rooms and rack fronts.
- Indoor side of outdoor feeds.
6. Installation & Maintenance
Installation
- Clip on DIN rail inside the cabinet.
- Wire L, N, PE to labels.
- Keep ground lead short, <=0.5 m.
- Land the alarm contact to DCIM.
- Keep decoupling distance from upstream B.
- Torque terminals to spec.
- Verify no short before energizing.
Maintenance
- Check the window quarterly.
- Swap the module when red.
- Confirm remote alarms reach DCIM.
- Log surge events after storms.
- Inspect ground lead for looseness.
7. FAQ
- Q: Does B+C replace the mains B arrester?
A: No. Keep the high-energy Type I at the mains; this is the second/third stage inside the room. - Q: Can I keep using it when the window turns red?
A: No. The MOV has failed and protection is lost; replace it promptly. Power continues but surge protection is gone. - Q: What ground resistance is needed?
A: Usually <=1 ohm bonded; <=4 ohm if constrained, with the shortest possible lead. - Q: Can I use it on 3-phase?
A: No. This is 230V single-phase; use a 3/4-pole model for 380V.
8. Trend & Selection
Power protection emphasizes staged, multi-level defense and online SPD health monitoring: event counts and degradation feed into DCIM. As rack currents rise, designers watch not only Up but follow-current and fault isolation. Plug-in modular replacement is the mainstream direction.
9. Delivery & Service
KITOZER ships KTR-PSM8 with module, DIN-rail clip, alarm terminals, certificate and manual. Pole count is ordered to match single/three-phase, with staged-protection review.
10. Notes
A common mistake is installing one SPD and assuming done. Protection works by staging; no single device combines huge energy handling with ultra-low residual.
Another pitfall is a thin, long ground lead; its impedance eats the discharge and raises residual at the equipment. Keep it short, thick, straight.
In short: 230V single-phase, combined B+C, In=20kA, Up<=1.5kV, remote alarm, plug-in. A second-stage protection item.
System-wise, the SPD guards far more expensive UPS and servers; a few hundred CNY is cheap insurance.
Cost-wise, batch-replace degraded modules after storm season beats post-incident repair.
Operationally, a high kA rating is useless if Up exceeds what the server can survive; always check the protection level, not just the discharge current.
Ground the SPD with the shortest possible conductor, because a long, thin earth lead adds impedance that defeats the arrester at the very moment it should conduct. A clean SPD installation pairs a low-Up module, proper stage decoupling and a stout bonding path, and it sits unnoticed for years until a storm proves its worth.
In practice, label each module with install date and expected service interval, and pull the status report after every major thunderstorm so heavily stressed units can be replaced on schedule.