ToggleKITOZER KTR-RACK-FAN-6 Rack Fan Unit (6-Fan Tray, Thermostatic Speed Control)
Brand: KITOZER Series: KTR-RACK-FAN-6 Category: Rack Accessories / Cooling Fans
6x120mmThermostatTop/BottomDual PowerKTR-RACK-FAN-6
1. Overview
Packed with switches, routers and UPS units, network and server cabinets overheat in summer and trigger high-temp alarms. Without forced ventilation, hot air pools at the top and the upper switch ports overheat first. The KITOZER KTR-RACK-FAN-6 is an axial fan tray mounted on the cabinet roof (or floor) that extracts hot air (or blows cool air in), creating convection. It has thermostatic speed control: slow and quiet when cool, full speed when hot.
Key specs: six 120x120x38 mm axial fans; 120 CFM (about 200 m3/h) per fan; 3.5 mmH2O static pressure; 42~52 dB(A) noise (speed-dependent); AC220V supply (DC48V optional); total power about 60 W; thermostat 25~45 C adjustable (default start 35 C); RS485 monitoring optional; 19-inch rack or roof-mount; powder-coated steel panel; resettable fuses per fan; terminal-block wiring.
Typical use: a 22U network cabinet gets a KTR-RACK-FAN-6 on the roof extracting upward, with an intake grille at the bottom. Summer rack temp drops from 42 C to 30 C, and switch sensors read normal. The NTC probe sits mid-cabinet above the switches: fans run full above 35 C and slow to 30% below 28 C. Overtime at night, 30% speed keeps noise low.
2. Key Features
Six-fan high airflow
- Six 120 mm fans in parallel.
- About 1200 m3/h total.
- Single-fan fault does not stop the tray.
- Ball-bearing, 50000 h life.
Thermostatic PWM
- NTC probe sensing.
- 25~45 C setpoint.
- PWM speed control.
- Quiet when cool, full when hot.
Dual supply options
- AC220V direct.
- DC48V telecom version.
- Wide-input.
- Fuse per line.
19-inch rack mount
- 1U panel height.
- Roof-mount or rack-mount.
- Four screws.
- Terminal block.
3. Specifications
| Item | Value |
|---|---|
| Model | KTR-RACK-FAN-6 |
| Fans | 6 x 120x120x38 mm |
| Per-fan airflow | 120 CFM (about 200 m3/h) |
| Total airflow | About 1200 m3/h |
| Static pressure | 3.5 mmH2O |
| Noise | 42~52 dB(A) |
| Power | AC220V (DC48V optional) |
| Power consumption | <=60 W |
| Thermostat range | 25~45 C (default start 35 C) |
| Speed control | Auto PWM |
| Monitoring | RS485 Modbus (optional) |
| Mounting | 19-inch 1U or roof-mount |
| Panel | SPCC powder-coated |
| Fan life | >=50000 h (ball bearing) |
4. Reference Price
KTR-RACK-FAN-6 AC220V six-fan tray (thermostatic): RMB 680~950 / unit (about USD 94~132)
KTR-RACK-FAN-6 DC48V telecom version: RMB 780~1100 / unit (about USD 108~153)
KTR-RACK-FAN-4 four-fan tray (small cabinets): RMB 480~680 / unit (about USD 67~94)
RS485 monitor board: RMB 80~120 / pc (about USD 11~17)
Spare 120 mm ball-bearing fan: RMB 35~55 / pc (about USD 5~8)
Bottom intake grille with filter: RMB 60~90 / pc (about USD 8~13)
Reference prices only; final price subject to quotation. (1 USD ≈ 7.2 CNY)
5. Applications
- Enterprise network cabinet roof cooling.
- Stacked weak-current switch cabinets.
- Outdoor integrated cabinet exhaust.
- UPS battery-cabinet ventilation.
- Broadcast/TV equipment cabinets.
- Security NVR cabinets.
- Lab instrument cabinets.
6. Installation & Maintenance
Installation
- Confirm a roof cutout or remove the top panel.
- Fix the fan tray to the roof rails with four M6 screws.
- Wire AC220V to L/N/PE terminals.
- Stick the NTC probe mid-cabinet next to the switches.
- Fit the bottom intake grille with filter.
- Power on and check rotation (extracting upward).
- Set the thermostat start point (default 35 C).
- Hold a hand over the roof outlet and feel airflow.
Maintenance
- Clean the bottom intake filter quarterly.
- Listen yearly for bearing noise.
- If a fan stops, power off and measure fan voltage.
- If voltage is present but the fan is dead, replace it.
- Do not tape the probe at the outlet (it reads exhaust, not room temp).
- Brush fan blades monthly in dusty sites.
- Calibrate the NTC probe yearly on RS485 versions.
- Replace fans at 50000 h (about 6 years).
7. FAQ
- Q:Top or bottom mount?
A:Hot air rises, so top extraction works best. Bottom blowing also works if there is a bottom intake. We recommend top extraction plus bottom intake to leverage natural convection. Do not blow against each other top and bottom. - Q:Still hot inside?
A:Check door seals and side panels closed. Check the intake is not blocked by cables. Then sum equipment heat; if it exceeds the tray airflow, add trays or move to precision AC. Cabinets over 70% U-population also trap heat. - Q:Can I switch fans off at night for quiet?
A:Not fully. Equipment still heats overnight; stopping fans lets temp creep up. Use thermostat speed control for 30% overnight, dropping noise to about 35 dB while still cooling. - Q:How many trays per cabinet?
A:One top tray is enough for under 22U. For 42U tall cabinets or over 3 kW, use two: one top extract, one mid assist. Airflow rule of thumb: about 300 m3/h per kW of heat load.
8. Industry Trends & Selection
Rack fans are moving from fixed-speed AC fans to DC PWM smart thermostatic units. Trays with RS485 dry contacts report fan faults and rack temp to DCIM. Bearings have upgraded from sleeve to dual ball, life from 30000 to 60000 h. High-density racks over 5 kW no longer use roof fans, moving to in-row AC and contained hot/cold aisles. But for small-to-medium network cabinets (1~3 kW), roof trays remain cost-effective. Size by heat load; choose AC220V or DC48V by site supply; choose the RS485 version if remote monitoring is needed.
9. Delivery & Service
KITOZER sizes KTR-RACK-FAN trays by cabinet height and heat load, and provides drawing dimensions and airflow calculations. Delivery includes tray, NTC probe, screw pack, manual and certificate. Fan bearings are replaced free under warranty.
10. Notes
A common pitfall is reversed fan direction. Fans have an airflow arrow; reversed, they blow into the cabinet and pressure pushes hot air out through every seam. After install, hold a slip of paper at the outlet — it should be drawn outward (extraction).
Another pitfall is skipping the intake filter. An open bottom gives lots of airflow but also pulls dust straight in; within six months switch filters are caked. Always use a washable intake filter.
Selection summary: six fans; thermostatic PWM; top extraction; bottom intake; clean filters on schedule. The rack fan is the cabinet’s exhaust fan; keys are correct direction, enough airflow, and regular filter washing.
Tip: on first power-up, the metal panel may carry a slight static — normal induced voltage; bond PE and it disappears. Do not touch terminals with wet hands.