Table of Contents
ToggleKITOZER KTR-SD-3P-100KA 3-Phase Power SPD (380V, 100kA, DIN-rail)
Brand: KITOZER Series: KTR-SD-3P-100KA Category: SPD / 3-Phase Surge Protector
3-phase 380V100kADIN-railremote contactKTR-SD-3P-100KA
1. Overview
The KITOZER KTR-SD-3P-100KA is a 3-phase surge protective device (SPD) installed at the low-voltage main incomer (380 V 3-phase 5-wire) of a power distribution room. It diverts transient overvoltages from lightning or grid switching to earth, protecting downstream distribution boards, UPS and server rooms. A nearby lightning strike induces spikes of several to tens of kV on the power lines; these travel indoors and fry power supplies, switches and servers. KTR-SD-3P-100KA is connected in parallel across the 3-phase busbar: it is high-impedance in normal operation, and in nanoseconds switches to low impedance during a surge, diverting up to 100 kA to earth and clamping the busbar voltage to a safe level (about 1.5 kV) for downstream equipment.
Specs: rated voltage 380 V AC (3-phase); nominal discharge current In 50 kA (8/20 us); max discharge current Imax 100 kA (8/20 us); voltage protection level Up <=1.5 kV; response time <=25 ns; poles 3P+N (three phases plus neutral); 35 mm DIN-rail mounting; visual status window (green OK / red failed); remote contact for failure alarm; flame-retardant plastic; plug-in replaceable modules. It sits at a different point from item 845 (single-phase 2P 40 kA SPD for 220 V sub-boards) and item 853 (RJ45 signal SPD for network cables): KTR-SD-3P-100KA is the high-current 3-phase first stage at the main incomer, 845 is the lower-current second stage, and 853 protects signal lines.
Typical uses: factory low-voltage main incomer; data center distribution board after the main breaker; building main distribution; base-station / telecom room mains; outdoor cabinet power input. Per the staged protection scheme, a class-I SPD (KTR-SD-3P-100KA, Imax 100 kA) goes at the building main, a class-II SPD (item 845, Imax 40 kA) at floor/rack distribution, and a class-III SPD (socket level) at the equipment. The class-I carries the large surge, the class-II limits residual voltage, and the class-III protects sensitive electronics.
2. Key Features
3-phase high current
- 3P+N 3-phase 5-wire.
- Imax 100 kA (8/20 us).
- In 50 kA.
- Class-I main incomer.
Low protection level
- Up <=1.5 kV.
- Response <=25 ns.
- Nanosecond diversion.
- Protects downstream UPS / servers.
Status + remote contact
- Visual window (green / red).
- Dry contact for failure alarm.
- Remote reporting to EMCS.
- Plug-in module swap without power-off.
DIN-rail mount
- 35 mm DIN rail.
- Fits inside distribution boards.
- UL94-V0 flame retardant.
- Terminal screw connection.
3. Specifications
| Item | Parameter |
|---|---|
| Model | KTR-SD-3P-100KA |
| Type | 3-phase power SPD |
| Rated voltage | 380 V AC (3-phase 5-wire) |
| Poles | 3P+N |
| Nominal current In | 50 kA (8/20 us) |
| Max current Imax | 100 kA (8/20 us) |
| Voltage protection Up | <=1.5 kV |
| Response time | <=25 ns |
| Mounting | DIN rail, screw terminals |
| Status | Window (green OK / red failed) |
| Remote contact | Dry contact (failure alarm) |
| Enclosure | UL94-V0 flame retardant |
| Operating temp | -40 to +80 C |
| Rail | 35 mm DIN |
4. Reference Prices
KTR-SD-3P-100KA class-I (3P+N, 100kA): Ref. USD 85~125 / pc (CNY 600~900 at 7.2)
KTR-SD-3P-60KA mid (60kA): Ref. USD 55~85 / pc (CNY 400~600 at 7.2)
KTR-SD-3P-150KA high (150kA): Ref. USD 125~180 / pc (CNY 900~1300 at 7.2)
KTR-SD-2P-40KA single-phase class-II (item 845): Ref. USD 17~25 / pc (CNY 120~180 at 7.2)
KTR-SD-RJ45 signal SPD (item 853): Ref. USD 5.5~10 / pc (CNY 40~70 at 7.2)
Shielded alarm wire (5m): Ref. USD 2~3.5 / pc (CNY 15~25 at 7.2)
Reference only; 1 USD ~ 7.2 CNY (Oct 2026).
5. Applications
- Factory low-voltage main incomer.
- Data center main breaker output.
- Building main distribution.
- Base-station / telecom room mains.
- Outdoor cabinet power input.
- Hospital / school / mall main board.
6. Installation & Maintenance
Installation
- Mount after the main breaker on the busbar (parallel connection).
- Wire L1/L2/L3 and N to the correct terminals.
- Connect PE to the earth bar (keep the lead short, under 0.5 m).
- Add a backup breaker (32 A C-curve) between the main breaker and the SPD.
- Clip onto the 35 mm DIN rail.
- Wire the remote contact to the EMCS (NO/NC selectable).
- Power up; check the window shows green.
- De-energize before wiring.
Maintenance
- Check the window quarterly (must be green).
- Red window means the module has failed; replace it.
- Wire the remote alarm to the EMCS so failure alerts automatically.
- Inspect after thunderstorms (the SPD may have sacrificed itself).
- Swap the plug-in module (same type; pull old, push new).
- Tighten the earth lead if loose (a broken earth lead makes the SPD useless).
7. FAQ
- Q:How do class-I and class-II SPDs coordinate?
A:Per GB 50057, use a class-I SPD at the main incomer (Imax >=100 kA, e.g. KTR-SD-3P-100KA), a class-II at floor/rack distribution (Imax 40 kA, e.g. item 845), and a class-III at the socket (10 kA). The two stages must be at least 10 m apart or have a decoupling inductor; otherwise they conduct together and the class-I cannot carry the surge. Do not mount both stages in the same cabinet. - Q:What happens when an SPD fails?
A:The metal-oxide varistor (MOV) inside ages a little every time it diverts a surge. After repeated strikes it short-circuits. The window turns red and the remote contact alarms. If you do not replace it, the next strike is unprotected and equipment can be destroyed. The good news is the module is plug-in: swap one module (about 200 to 300 RMB) instead of replacing the whole SPD. - Q:How thick should the earth lead be?
A:Use >=16 mm2 multi-strand copper from SPD to earth bar, as short as possible (under 0.5 m). A long lead adds inductance and the surge cannot be diverted fast enough, raising residual voltage. The lead does not carry working current, but it must carry a 100 kA pulse, so it must be thick and short. Earth resistance should be <=4 ohm (data center <=1 ohm). - Q:Does an SPD prevent lightning damage?
A:No. The SPD diverts surges that enter on the power line; it does not stop a direct strike on the building. Direct strikes are handled by the air-termination rod and earth grid. The SPD is internal protection that works with external protection. Also protect signal lines (network, coax, feeder) with a signal SPD (item 853); otherwise a surge on the Ethernet cable still fries the NIC.
8. Trend & Selection
SPDs move from plain MOV to thermally protected MOV (built-in thermal fuse that disconnects on failure), reducing fire risk. They move from power-only to combined power+signal protective boxes. Smart SPDs with RS485 (counting discharges, leakage current, temperature) become standard in data centers. Class-I testing with Iimp (10/350 us, direct-strike waveform) becomes more common for high-lightning-risk buildings.
9. Delivery & Service
KITOZER sizes KTR-SD-3P-100KA by lightning-protection class and distribution system, providing the three-stage coordination diagram and earthing requirements. Delivery includes the SPD, backup breaker, manual and certificate. Warranty covers module replacement and remote-contact integration.
10. Additional Notes
A common pitfall is a long earth lead. Running 2 m from SPD to earth bar adds inductance and pushes residual voltage from 1.5 kV to 4 kV; downstream equipment still dies. The earth lead must be short, thick and straight, with no loops.
Another pitfall is omitting the backup breaker. When an SPD fails short, without a backup breaker the busbar burns or catches fire. Always put a 32 A C-curve breaker (or fuse) in series with the SPD.
Selection summary: 3-phase 380 V; 3P+N; Imax 100 kA; Up 1.5 kV; DIN rail with remote contact. The 3-phase SPD is the first surge barrier at the main board; the keys are a short thick earth, a backup breaker, and staged coordination.
Extra tip: an SPD is not a consumable, but it must be checked. Many projects install it and forget; after a storm the module may have failed (red window) without anyone noticing. Wire the remote contact to the EMCS for automatic alarm; do not rely on manual walk-downs.
Contact Us
KITOZER brand (professional data center & low-voltage equipment supplier)
Tel/WeChat: +86 13922289957 | +86 18520668845
WHATSAPP: +86 19068534140
Web: lain.com.cn | gdlain.com