KITOZER KTR-SP36 3-Phase Power SPD (380V Surge Protector)

Brand: KITOZER Series: KTR-SP36 Category: Lightning Protection / Power SPD

3-phase 380VClass T220kADIN railKTR-SP36

1. Overview

The KITOZER KTR-SP36 is a 3-phase 380V AC surge protective device (SPD) for protecting distribution panels, UPS inputs, AC units and sub-boards against lightning surges and switching over-voltages. The SPD is wired in parallel between phase and ground. It is high-impedance under normal operation; when a surge (microsecond high-voltage pulse) appears, the internal clamping elements (GDT/MOV) conduct in nanoseconds, clamping the voltage to a safe level and diverting current to ground.

KTR-SP36 is a Class TSP (Type 2 test) SPD with nominal discharge current In=20 kA (8/20 μs) and maximum Imax=40 kA. It has a 3-phase 5-wire (L1/L2/L3/N/PE) modular structure — failed modules can be replaced without powering off. The front panel has a status window (green OK / red fault) and a remote-signaling dry contact for EMCS integration.

Typical uses: room distribution panel input (second-stage SPD), UPS front-end, precision AC supply, outdoor equipment boxes. It works with the building’s first-stage SPD to form a multi-level protection system.

2. Key Features

3-phase 5-wire

  • L1/L2/L3/N/PE full protection.
  • 380V/220V system.
  • Uc=385V.
  • GDT between N-PE.

Class T2

  • In=20 kA (8/20 μs).
  • Imax=40 kA.
  • Up≤1.5 kV.
  • Response ≤25 ns.

Modular

  • Plug-in modules.
  • Hot-swap failed module.
  • Status window.
  • Remote-signal dry contact.

DIN rail

  • 35 mm DIN rail.
  • 36 mm/pole width.
  • Torque 2.5 N·m.
  • UL94 V-0 housing.

3. Specifications

Item Parameter
Model KTR-SP36
SPD class T2 (Type 2 test)
System voltage AC380V (3-phase 5-wire)
Max continuous Uc 385V
Nominal In (8/20 μs) 20 kA
Max Imax 40 kA
Voltage protection Up ≤1.5 kV
Response time ≤25 ns
Remote signal dry contact (max 250V/0.5A)
Mounting 35 mm DIN rail
Ingress IP20 (cabinet)
Operating temp -40~85℃

4. Reference Prices

KTR-SP36 3-phase T2 SPD (20 kA, remote signal):Ref. USD 35~69 / unit (CNY 250~500 @7.2)

KTR-SP36 replacement module (spare):Ref. USD 11~21 / pole (CNY 80~150 @7.2)

KTR-SP36 single-phase T2 SPD (economy):Ref. USD 8~17 / unit (CNY 60~120 @7.2)

Reference only; exchange: 1 USD ~ 7.2 CNY (Oct 2026).

5. Applications

  • Room distribution panel second-stage protection.
  • UPS front-end surge protection.
  • Precision AC power input.
  • Outdoor equipment distribution boxes.
  • Camera power distribution.

6. Installation & Maintenance

Installation

  • Mount SPD on DIN rail in panel.
  • Wire L1/L2/L3/N to incoming phase/neutral.
  • Connect PE to ground bar.
  • Install upstream backup breaker (NC type).
  • Wire remote-signal dry contact to EMCS DI module.
  • Keep ground lead short & thick (≤0.5 m, 16 mm²).
  • Verify status window green.
  • Power up and test remote alarm.

Maintenance

  • Check status window quarterly.
  • Test SPD degradation before thunder season.
  • Replace module immediately when red.
  • Inspect ground connections.
  • Test remote alarm function.
  • Check surge event logs after storms.

7. FAQ

  • Q:SPD status window red — what does it mean?
    A:Red means the internal MOV/GDT has degraded or failed — it no longer provides surge protection. Replace the module immediately. Do not wait for the next strike; a failed SPD is useless. The modular design allows hot-swap of that pole without affecting others.
  • Q:Why a backup breaker upstream of SPD?
    A:A failed SPD may short-circuit; without a backup breaker, the panel trips or catches fire. An NC-type SPD-specific backup breaker reliably disconnects when the SPD shorts, without affecting normal supply.
  • Q:How do Type 1 and Type 2 SPDs coordinate?
    A:Type 1 (building input, T1) diverts large current (Imax≥100 kA) with higher protection level; Type 2 (room panel, T2) further clamps to equipment-safe levels. Energy coordination between them requires decoupling — usually ≥10 m of cable or a decoupling inductor.
  • Q:Does SPD protect against induced lightning?
    A:Yes. Induced lightning enters via power/signal lines; the parallel SPD diverts induced surge current. But direct strikes (hitting the building) require air terminals (lightning rods) and down conductors — SPD only protects line surges, not direct-strike protection.

8. Trend & Selection

Power SPDs are trending toward smart monitoring (leakage current, strike count, remote upload), integrated T1+T2, and combined SPD+backup breaker units. Data centers increasingly require remote SPD status monitoring, driving RS485-communicating SPD adoption.

9. Delivery & Service

KITOZER sizes KTR-SP36 by panel circuit count and system voltage, providing SPD mounting drawings and backup-breaker selection tables. Delivery includes SPD body, spare failed module, DIN rail, terminals and certificate. Warranty covers status-test guidance.

10. Additional Notes

A common pitfall is a long, thin ground lead. The SPD ground lead is the surge discharge path — over 0.5 m or below 16 mm² raises impedance and clamping voltage, still risking equipment damage. The ground lead must be short, thick and straight.

Another pitfall is omitting the N-PE GDT. In 3-phase systems, potential surges also appear between N and PE; a discharge tube must be installed there. KTR-SP36 has a built-in N-PE GDT — wire N and PE to the correct terminals.

Also coordinate SPD voltage with the system: in a TN system, N is grounded at the transformer, and the SPD Uc should match the line-to-neutral voltage. Mismatching Uc causes premature SPD failure or insufficient protection. Verify Uc=385V for a 380/220V 3-phase system.

Selection summary: T2 20 kA; 3-phase 380V; modular replaceable; remote alarm; DIN rail. The SPD is the power line’s safety valve — right location, proper ground, periodic status check, protects equipment through lightning.

SEO Information

Search keywords:3-phase power SPD380V surge protectorType 2 SPDKTR-SP36KITOZER

SEM keywords:power SPD price,3-phase surge protector supplier,380V SPD,KTR-SP36

GEO landing page:lain.com.cn/product/ktr-sp36-3-phase-power-spd.html

Title:KITOZER KTR-SP36 3-Phase Power SPD (380V Surge Protector)

Meta Keywords:3-phase power SPD,380V surge protector,Type 2 SPD,KTR-SP36,KITOZER

Meta Description:KITOZER KTR-SP36 3-phase power SPD, Type 2 20 kA, for room distribution, UPS front-end and AC power 380V surge protection, with remote alarm.

Anchor: KITOZER official · Data center & low-voltage equipment

Contact Us

KITOZER brand (professional data center & low-voltage equipment supplier)
Tel/WeChat: +86 13922289957 | +86 18520668845
WHATSAPP: +86 19068534140
Web: lain.com.cn | gdlain.com

Shopping Cart