KITOZER KTR-SPDRJ45 RJ45 Network Signal SPD (Gigabit)

KITOZER KTR-SPDRJ45 RJ45 Network Signal SPD (Gigabit)

Brand: KITOZER Series: KTR-SPDRJ45 Category: Surge Protection / Network Signal SPD

RJ45Gigabit 1000Mbpssignal SPDDIN railKTR-SPDRJ45

1. Overview

The KITOZER KTR-SPDRJ45 is an RJ45 network signal surge protective device, designed to protect Ethernet ports of switches, routers, servers and network cameras from lightning surges and switching overvoltage. The SPD is in-line on the Ethernet cable, using a multi-stage TVS plus gas discharge tube (GDT) circuit, nominal discharge current 5 kA (8/20 microseconds), insertion loss below 0.5 dB, with RJ45 feed-through for Gigabit cables.

KTR-SPDRJ45 transmission speed 1000 Mbps Gigabit, supports PoE IEEE802.3af/at, RJ45 female-to-female feed-through. Operating voltage 6 V, maximum continuous operating voltage 8 V, response time below 1 ns. DIN-rail mount on 35 mm rail, metal shielded housing, M4 grounding terminal. Operating temperature -40 to 85 degrees C, about 40 by 25 by 95 mm.

Typical uses: room switch port surge protection; outdoor network camera cable entry protection; wireless AP and bridge entry; building weak-current room network entry; media converter port protection. Signal SPDs are in-line ahead of the protected device; the ground wire should be short and thick, no longer than 0.5 m and at least 6 mm2.

2. Key Features

Multi-stage protection

  • TVS plus GDT.
  • 5 kA nominal discharge.
  • Response below 1 ns.
  • Insertion loss below 0.5 dB.

Gigabit

  • 1000 Mbps speed.
  • PoE support.
  • RJ45 female to female.
  • Cat5e and Cat6 compatible.

DIN rail

  • 35 mm rail clip.
  • Metal shielded case.
  • M4 ground terminal.
  • 40 by 25 by 95 mm.

Environment

  • -40 to 85 C.
  • Dust and moisture proof.
  • Visible ground status.
  • Over 1000 discharge cycles.

3. Specifications

Item Parameter
Model KTR-SPDRJ45
Interface RJ45Bus-Bus
Speed 1000Mbps(Gigabit)
PoE support IEEE802.3af/at
Max continuous voltage 8V
Nominal discharge current 5kA
Max discharge current 10kA
Response time <1ns
Insertion loss <0.5dB
Protection circuit TVS+GDTMulti-Level
Mounting 35mm DINDIN Rail
Ground terminal M4
Operating temp -40~85℃
Dimensions Approx.40×25×95mm

4. Reference Prices

KTR-SPDRJ45 Gigabit RJ45 SPD:Ref. USD 11~21 / pc (CNY 80~150 at 7.2)

KTR-SPDRJ45 100M economy:Ref. USD 6~11 / pc (CNY 40~80 at 7.2)

M4 ground wire 1 m, 6 mm2:Ref. USD 1.4~2.8 / pc (CNY 10~20 at 7.2)

DIN rail 1 m:Ref. USD 2~4 / pc (CNY 15~30 at 7.2)

Reference only; exchange: 1 USD ~ 7.2 CNY (Oct 2026).

5. Applications

  • Room switch port surge protection.
  • Outdoor camera cable entry protection.
  • Wireless AP and bridge entry.
  • Building weak-current room network entry.
  • Media converter port protection.

6. Installation & Maintenance

Installation

  • Fix SPD on DIN rail in weak-current room.
  • Run outdoor cable to SPD IN port.
  • Run equipment cable to SPD OUT port.
  • Connect M4 ground to 6 mm2 wire.
  • Bond to equipotential ground bar.
  • Keep ground wire short, no longer than 0.5 m.
  • Verify IN and OUT wiring order.
  • Power on and test network connectivity.

Maintenance

  • Check ground terminal tightness quarterly.
  • Inspect SPD status after thunderstorm season.
  • Check network after lightning strikes.
  • Replace corroded ground wire.
  • Replace SPD as a unit when failed.
  • Log lightning events and replacement dates.

7. FAQ

  • Q:Signal SPD vs power SPD?
    A:Signal SPD KTR-SPDRJ45 is in-line on the Ethernet cable, protecting signal lines with low current capacity 5 kA but low insertion loss. Power SPD is in-line on 220 V or 380 V power lines, with high current capacity 20 to 40 kA protecting supply. Rooms should use both power SPD in distribution cabinet and signal SPD on Ethernet lines, forming three-stage protection.
  • Q:What happens if IN and OUT are reversed?
    A:IN is for outdoor cable (lightning side), OUT for equipment. Reversed wiring usually still works (protection components are symmetric), but affects failure indication and maintenance. Correct: outdoor to IN, equipment to OUT. The housing usually has an arrow IN to OUT; follow the arrow.
  • Q:Why must the ground wire be short and thick?
    A:Surge current of thousands of amperes through a long or thin ground wire creates higher inductance and resistance, raising residual voltage at the equipment end. The ground wire should be short no longer than 0.5 m, thick at least 6 mm2, and straight with few bends, to discharge surge current quickly to the ground bar. Coiled wire increases inductance and must be straight.
  • Q:Does the SPD have a service life?
    A:Yes. The internal GDT and TVS age with each surge discharge, gradually losing capacity. Designed life exceeds 1000 nominal discharge impulses. Frequent-thunder regions should replace every 3 to 5 years. Status window: green normal, red failed. Replace when red.

8. Trend & Selection

SPDs trend toward modular full DIN-rail series for signal, power and antenna feeds, smart remote failure alarm, and low residual voltage. Room equipotential grounding works with three-stage lightning protection (power, signal, antenna) for a complete system. PoE adoption requires network SPDs to support both Gigabit and high-power PoE.

9. Delivery & Service

KITOZER sizes KTR-SPDRJ45 by network entry count and PoE power, providing SPD layout and grounding topology. Delivery includes SPD, DIN rail clip and certificate. Warranty covers grounding and failure replacement guidance.

10. Additional Notes

A common pitfall is a long coiled ground wire. Coiled ground wire creates inductance; surge current through it generates high residual voltage and damages the equipment instead. The ground wire must be short and straight, no longer than 0.5 m and at least 6 mm2, running directly from the M4 terminal to the equipotential bar, with no joints or coils.

Another pitfall is installing only signal SPD without power SPD. Most lightning surges enter via power lines; signal lines are secondary. Without power protection, power surges still damage equipment. Power SPD in the distribution cabinet and signal SPD on Ethernet must both be configured, sharing the same equipotential ground bar.

Selection summary: RJ45 Gigabit, 5 kA discharge, TVS plus GDT, DIN rail, short thick ground. The network signal SPD is the Ethernet insurance; in-line entry, short thick ground, periodic window checks keep equipment safe through thunderstorm season.