ToggleKITOZER KTR-TH-RS485 Temperature & Humidity Sensor (RS485 Modbus, LCD)
Brand: KITOZER Series: KTR-TH-RS485 Category: Environmental Monitoring / T&H Sensor
RS485Modbus-RTU+/-0.3 CLCDKTR-TH-RS485
1. Overview
The KITOZER KTR-TH-RS485 is a wall-mount temperature and humidity sensor with an LCD and RS485 interface. It samples real-time T and RH in server rooms, warehouses and cold-chain workshops, and uploads them via Modbus-RTU to an environmental monitor or DCIM system. Over-temperature causes servers to throttle and AC faults; high humidity causes condensation and short circuits, low humidity causes static. KTR-TH-RS485 watches these two parameters around the clock and alarms on limits.
Key specs: temperature -40 to +80 C, accuracy +/-0.3 C at 25 C; humidity 0~100% RH, accuracy +/-2% RH at 20~80%; RS485, Modbus-RTU, baud 4800~115200 (default 9600); DC12~24 V, <=0.5 W; LCD shows T and RH together; built-in probe (optional 1 m external); ABS flame-retardant case; wall 86-box base; -20 to +60 C operating.
Typical use: a 42U room has three KTR-TH-RS485 units at the cold-aisle inlet, hot-aisle outlet, and rack mid-height, daisy-chained on one RS485 bus to the DCIM host (Modbus addresses 1~3). The host shows three curves on a web UI; set upper temp 28 C, lower 18 C, upper RH 60%, lower 40%; out-of-range triggers SMS alarms.
2. Key Features
+/-0.3 C high accuracy
- Temp accuracy +/-0.3 C.
- RH accuracy +/-2%.
- Industrial Sensirion probe.
- Suits precision rooms and cold chain.
RS485 Modbus-RTU
- Standard Modbus-RTU.
- 9600~115200 auto baud.
- Daisy-chain bus, up to 32 units.
- 1200 m range.
LCD on-screen
- T and RH on one screen.
- Read on-site without the host.
- Backlight optional.
- Address and baud settable by keys.
Wall 86-box mount
- Standard 86-box base.
- Four screws.
- ABS flame-retardant.
- DC12~24 V wide range.
3. Specifications
| Item | Value |
|---|---|
| Model | KTR-TH-RS485 |
| Measured | Temperature + relative humidity |
| Temp range | -40 to +80 C |
| Temp accuracy | +/-0.3 C (25 C) |
| Humidity range | 0~100% RH |
| Humidity accuracy | +/-2% RH (20~80% RH) |
| Interface | RS485 (Modbus-RTU) |
| Baud rate | 4800~115200 (default 9600) |
| Power | DC12~24V |
| Power consumption | <=0.5 W |
| Display | LCD (T&H on one screen) |
| Probe | Built-in (optional 1 m external) |
| Mounting | Wall 86-box base |
| Case | ABS flame-retardant |
| Operating temp | -20 to +60 C |
4. Reference Price
KTR-TH-RS485 T&H sensor (LCD): RMB 120~180 / unit (about USD 17~25)
KTR-TH-RS485-P external probe (1 m): RMB 150~220 / unit (about USD 21~31)
KTR-TH-4G cloud version: RMB 280~380 / unit (about USD 39~53)
RS485-to-USB converter:
RS485-to-USB converter: RMB 35~60 / unit (about USD 5~8)
8-channel RS485 logger: RMB 280~420 / unit (about USD 39~58)
86-box wall base (spare): RMB 8~15 / pc (about USD 1~2)
Reference prices only; final price subject to quotation. (1 USD ≈ 7.2 CNY)
5. Applications
- Cold/hot aisle T&H in data centers.
- Battery-cabinet temp (thermal runaway prevention).
- Warehouse and archive monitoring.
- Cold-chain and pharma cold rooms.
- Precision-AC interlock in rooms.
- Agricultural greenhouses and farms.
- Labs and museum display cases.
6. Installation & Maintenance
Installation
- Pick a point away from AC outlets, heat sources and direct sun.
- Fix the 86-box base; pull RVV2x1.0 power and RVSP2x1.0 shielded cable.
- DC12~24 V to V+/V- terminals.
- RS485 A/B to sensor A/B (daisy-chain).
- Add a 120 ohm terminator at the last unit.
- Clip the sensor onto the base.
- Set Modbus address (1~247) and baud with keys.
- Scan the bus from the host and confirm T/RH readings.
Maintenance
- Calibrate quarterly with a 75% RH salt box.
- Send to a metrology lab annually for a calibration certificate.
- Brush dust off the sensor; do not wipe with a damp cloth (disturbs RH).
- Check RS485 wiring (do not reverse A/B).
- If LCD is dead, check voltage and polarity.
- Inspect probes inside battery cabinets annually for acid corrosion.
- Set a 5% alarm hysteresis to prevent chatter.
- Replace the probe every 5 years (accuracy drifts).
7. FAQ
- Q:How do I wire the RS485 bus?
A:Daisy-chain: host A to sensor 1 A, sensor 1 B to sensor 2 A, sensor 2 B to sensor 3 A, … last sensor B back to host B. Do not star (causes reflections). Use RVSP shielded twisted pair, shield grounded at one end. Add a 120 ohm terminator at the far end. Do not reverse A/B. - Q:Readings are off; how to adjust?
A:First decide whether T or RH is off. Temperature off: the sensor is near a heat source or AC outlet — move it. Humidity off: test with a 75% RH salt box; if it reads 80%, set an offset of -5% in the host. If deviation exceeds +/-5% RH, replace the probe. - Q:How many sensors per host?
A:One RS485 bus handles 32 units theoretically without a repeater; practically stay under 20, each with a unique Modbus address. Beyond 32, add a repeater or split into multiple buses, each on its own serial port. - Q:Does the sensor need grounding?
A:The sensor itself does not, but the RS485 shield grounds at the host end to prevent ground loops. Do not bond the sensor case to the rack (introduces common-mode noise).
8. Industry Trends & Selection
Environmental sensors are moving from single T/RH to multi-parameter modules (T/RH + CO2 + PM2.5 + VOC + pressure). Communications are upgrading from RS485 to 4G/LoRa/NB-IoT for wireless cloud upload. AI uses T/RH history to predict AC failures. Accuracy is improving from +/-0.5 C to +/-0.1 C. Select RS485 (wired) or 4G (wireless) by site count; single vs multi-parameter by need; industrial vs commercial by accuracy. Server-room DCIM prefers wired RS485 for stability.
9. Delivery & Service
KITOZER sizes KTR-TH sensors and RS485 loggers by room point count and parameter needs, and provides Modbus address maps and wiring diagrams. Delivery includes sensor, 86-box base, manual and certificate. Remote tuning and calibration guidance are covered under warranty.
10. Notes
A common pitfall is mounting the sensor at the AC outlet. The outlet is 3~5 C cooler than the room, so the reading does not represent the real server-room temperature. Mount sensors between hot and cold aisles, 1.5 m at the rack inlet, away from outlets and heat sources.
Another pitfall is star-wired RS485. Crews run a bus to a junction box and then branch to each sensor. RS485 is a bus protocol; star topology causes reflections and intermittent comms. Daisy-chain.
Selection summary: RS485; Modbus-RTU; +/-0.3 C; LCD; wall-mount. The T&H sensor is the room’s thermometer; keys are correct placement, daisy-chain bus, and regular calibration.
Tip: on delivery, check the LCD before powering comms. Cheap sensors sometimes cannot run LCD and comms simultaneously (power-saving design) — check the wake-up method in the manual. KTR-TH-RS485 keeps both on at all times; less power-saving but stable.
SEO
Search keywords:T&HsensorRS485Modbusroom monitoring
SEM keywords:temperature humidity sensor,RS485 T&H transmitter,Modbus T&H module,server room monitoring,cold-chain monitoring,KTR-TH-RS485,KITOZER
GEO landing page:lain.com.cn/product/rs485-temp-humidity-sensor.html
Title:KITOZER KTR-TH-RS485 Temperature & Humidity Sensor (RS485 Modbus, LCD)
Meta Keywords:temperature humidity sensor,RS485 transmitter,Modbus T&H,room environment monitor,KTR-TH-RS485,KITOZER
Meta Description:KITOZER KTR-TH-RS485 T&H sensor, RS485 Modbus-RTU, accuracy +/-0.3 C and +/-2% RH, LCD, for server rooms, warehouses and building monitoring.
Anchor text: KITOZER official site · low-voltage equipment
Contact Us
KITOZER brand (professional data-center & low-voltage equipment supplier)
Tel/WeChat: +86 13922289957 | +86 18520668845
WHATSAPP: +86 19068534140
Web: lain.com.cn | gdlain.com