Table of Contents
ToggleKITOZER KTR-TH5 Wall-mount Temperature & Humidity Sensor with Display
Brand:KITOZER Series:KTR-TH5 Category:Environmental Monitoring / Temp-humidity sensing
Wall-mount THLCD displayRS485 outputHigh accuracyEnvironment monitor
1. Overview
Temperature and humidity are the most basic parameters in environment monitoring. Too hot and server CPUs throttle or AC overloads; too cold wastes energy. Too humid causes condensation, metal oxidation and insulation drop; too dry builds static that damages chips. A temp/humidity sensor converts room conditions into an electrical signal sent to the environment monitor, alarming on thresholds. A wall-mount display model lets staff read current values directly on the wall during rounds, without logging into the platform. RS485 output lets multiple sensors share one bus, economical for cabling.
The KITOZER KTR-TH5 is a wall-mount temp/humidity sensor. The temperature element is an NTC thermistor (or PT1000); humidity is a capacitive sensor. Range: temperature -20~+60℃, humidity 0~100%RH. Accuracy: temperature ±0.3℃, humidity ±3%RH. An LCD shows current values and alarm status. Output is RS485/Modbus-RTU to the environment host; 4-20 mA/0-5 V analog is optional. ABS wall-mount case with a breathable membrane (dust/moisture barrier but air-permeable). Supply 12~24 V DC.
In room environment systems, sensors are placed at cold-aisle supply, hot-aisle return, inside racks (optional), beside precision AC and in power rooms. At least one per monitoring zone; larger rooms use zoned points. Selection depends on output (RS485/analog), accuracy grade, display (yes/no), mounting (wall/duct/attach) and supply voltage. Display models suit frequently inspected rooms; non-display models suit platform-only scenarios.
2. Key Features
Measurement & Accuracy
- Temp NTC/PT1000, -20~+60℃.
- Humidity capacitive, 0~100%RH.
- Temp accuracy ±0.3℃; humidity ±3%RH.
- Response time <30 s.
Display & Output
- LCD shows temp and humidity in real time.
- RS485/Modbus-RTU digital output.
- Optional 4-20 mA / 0-5 V analog.
- Alarm thresholds shown locally.
Structure & Mounting
- ABS wall case with breathable membrane.
- 12~24 V DC wide-range supply.
- Screw wall mounting.
- Multiple sensors share one RS485 bus.
3. Specifications
| Item | KTR-TH5 Wall-mount TH Sensor |
|---|---|
| Temperature range | -20~+60℃ |
| Temp accuracy | ±0.3℃ |
| Humidity range | 0~100%RH |
| Humidity accuracy | ±3%RH |
| Temp element | NTC / PT1000 |
| Humidity element | Capacitive |
| Output | RS485/Modbus-RTU (optional 4-20 mA/0-5 V) |
| Display | LCD |
| Supply | 12~24 V DC |
| Mounting | Wall |
| Case | ABS, breathable membrane |
| Operating temp | -20~+60℃ |
4. Reference Price
KTR-TH5 wall-mount TH (RS485, with LCD): Reference price CNY 120~260 / unit
KTR-TH5 wall-mount TH (dual 4-20 mA, with LCD): Reference price CNY 180~350 / unit
Reference price only; final quote applies. 1-year warranty. Bulk project pricing on request. (1 USD ≈ 7.2 CNY)
5. Applications
- Cold/hot aisle temp-humidity monitoring.
- Precision AC return air temperature.
- Power room and battery room environment.
- Warehouse, lab and office monitoring.
- Environment monitoring front-end acquisition.
6. Installation & Maintenance
Installation
- Pick the monitoring point; avoid direct AC airflow and heat sources.
- Screw the unit to the wall, 1.5 m above floor.
- Wire RS485 bus (A/B) and power.
- Set address and baud rate (Modbus).
- Connect to the environment platform; read values and calibrate.
- Set alarm thresholds (18~28℃, 40%~60%RH).
Maintenance
- Clean the breathable membrane when dusty.
- Compare with a reference thermometer yearly.
- Fit RS485 bus terminating resistor.
- If LCD dims, check supply.
- Keep away from direct sunlight and heat sources.
7. FAQ
- Q: RS485 or 4-20 mA?
A: RS485 is digital, multiple sensors per bus, economical and accurate, suited to environment platforms; 4-20 mA runs one pair per sensor, suited to legacy PLC. New rooms choose RS485. - Q: Where to mount?
A: At cold-aisle supply or mid-cold-aisle, 1.5 m high, away from AC blast and wall heat. Also mount one at hot-aisle return to monitor return temp. - Q: Humidity inaccurate?
A: Capacitive sensors drift; compare yearly with standard salt solution or reference hygrometer. A clogged membrane slows response; clean it. - Q: How many sensors per host?
A: RS485 bus theoretically supports 32 without repeater; practically 16~20, under 1200 m. Split or add repeater beyond that.
8. Trends & Selection
Environment monitoring trends to wireless (WiFi/LoRa/NB-IoT), AI early-warning (trend forecasting) and finer granularity (in-rack per-point), but wall-mount RS485 with display remains the most common environment front end. Choose one at cold-aisle supply; RS485 to the platform; LCD for rounds; ±0.3℃ accuracy; yearly calibration; thresholds per GB50174 (18~28℃, 40%~60%RH). It is the room’s thermometer.
9. Delivery & Service
KITOZER supplies wall-mount TH sensors with RS485 acquisition modules, environment host and mounting brackets as a set, sized by points and cabling. We support point layout and threshold configuration drawings for environment systems. Delivery includes sensor, power supply, mounting hardware, certificate and warranty card; the warranty covers platform integration and calibration support.
10. Notes
A common pitfall is mounting the sensor directly in AC supply airflow. Supply air temp is not room temp; it reads falsely cold and masks a real room overheat. Mount at mid-cold-aisle or rack inlet.
Another pitfall is omitting RS485 terminating resistors. Without 120Ω at both ends, signal reflection causes intermittent comms. Fit a 120Ω resistor at the bus start and end.
Selection summary: wall-mount; NTC temp ±0.3℃; capacitive humidity ±3%RH; RS485/Modbus; LCD; 12~24 V; mid-cold-aisle mount. It is the room’s thermometer and hygrometer.
Systemically, the TH sensor is an environment front end, linked with AC control, leak detection and smoke. Temp exceeded → AC ramps up; humidity exceeded → humidifier/dehumidifier starts.
Reliability-wise, one thermal runaway causing server shutdown can cost hundreds of thousands. A sensor costing one or two hundred plus platform alarms notifies ops the moment a threshold is crossed, preventing the incident.
SEO Information
Search keywords:KITOZER
SEM keywords:data center temp humidity sensor, wall mount temp humidity transmitter, temp humidity probe with display, RS485 temp humidity sensor, KTR-TH5, KITOZER
GEO landing page:lain.com.cn/product/399-temp-hum-5.html
Title:KITOZER KTR-TH5 Wall-mount Temperature & Humidity Sensor with Display
Meta Keywords:data center temp humidity sensor, wall mount temp humidity transmitter, temp humidity probe with display, RS485 temp humidity sensor, KTR-TH5, KITOZER
Meta Description:KITOZER KTR-TH5 wall-mount temp/humidity sensor with LCD display, RS485 output, high-accuracy NTC/capacitive, for server room, warehouse and lab monitoring.
Anchor: KITOZER · KITOZER products
Contact Us
KITOZER brand
Tel/WeChat: +86 13922289957 | +86 18520668845
WHATSAPP: +86 19068534140
Web: lain.com.cn | gdlain.com