KITOZER
KITOZER

KITOZER temp humidity sensor RS485

KITOZER KTR-THS Temperature & Humidity Sensor for Data Center

Brand: KITOZER Series: KTR-THS Category: Environmental Monitoring / Sensors

temp & humidityRS485±0.3°CLCDKTR-THS

1. Overview

Temperature and humidity are the most basic and critical room-environment parameters. High temperature throttles or shuts down servers; low humidity causes ESD that fries chips; high humidity causes condensation. The room standard is 23±1°C (ASHRAE A1) and 40~60% RH. A room of hundreds of square meters cannot rely on hand-held meters — fixed, 24/7 sensors with threshold alarms are mandatory.

The KITOZER KTR-THS series combines a capacitive humidity sensor with a PT1000/NTC temperature element. Accuracy ±0.3°C (0~50°C) and ±2% RH (10~90%). RS485 Modbus-RTU plugs into the environment host. A large LCD shows readings on-site. Wall-mount for rack rows and walls; duct-mount with stainless probe for AC supply air. DC 9~24 V wide-range supply.

Selection: accuracy (±0.5°C for general, ±0.3°C for precision rooms); comms (RS485 Modbus to the environment system, or relay for standalone); display (LCD for manned areas, no-display for unmanned racks); and placement (supply, return and rack inlet — not just one in the middle). Sensors drift over 3~5 years and need calibration or replacement.

2. Key Features

Accuracy

  • ±0.3°C temperature
  • ±2% RH humidity
  • PT1000/NTC element
  • Capacitive humidity

Comms & display

  • RS485 Modbus-RTU
  • Large LCD
  • DC 9~24 V wide-range
  • 1 relay out (optional)

Mounting

  • Wall / duct types
  • ABS flame-retardant case
  • Screw wall-mount
  • -10~60°C operating

3. Specifications

Item KTR-THS-S1 KTR-THS-S2 KTR-THS-S3
温度范围 -20~60℃ -20~60℃ -40~80℃(管道)
温度精度 ±0.5℃ ±0.3℃ ±0.3℃
湿度范围 0~100%RH 0~100%RH 0~100%RH
湿度精度 ±3%RH ±2%RH ±2%RH
通信 RS485 RS485+开关量 RS485
显示 无显示 LCD大屏 LCD大屏
供电 DC12V DC9~24V DC9~24V
安装方式 壁挂 壁挂 管道法兰

4. Reference Prices

KTR-THS-B basic sensor (RS485, no display)::Reference Reference USD 17~31 / pc (ref. CNY 120~220 at ~7.2)

KTR-THS-D display sensor (RS485 + LCD)::Reference Reference USD 25~44 / pc (ref. CNY 180~320 at ~7.2)

KTR-THS-P duct sensor (stainless probe)::Reference Reference USD 36~58 / pc (ref. CNY 260~420 at ~7.2)

RS485 shielded cable (per meter)::Reference Reference USD 0.4~0.8 / m (ref. CNY 3~6 at ~7.2)

Reference only; priced by accuracy/display/mount. 1-year warranty. Exchange: 1 USD ~ 7.2 CNY (Oct 2026).

5. Applications

  • Main room temperature/humidity monitoring.
  • Rack-row hot/cold aisle temperature.
  • AC supply and return air.
  • Archive and museum climate.
  • Battery and power rooms.

6. Deployment & Implementation

Installation

  • Mount at rack inlet, 1.5 m high
  • Avoid direct AC blast and heat sources
  • Daisy-chain RS485, 120 Ω terminator at ends
  • Shielded cable single-end grounded

Operations

  • Calibrate yearly against a reference source
  • Compare LCD vs host; recalibrate if >0.5°C
  • Keep probe free of dust
  • Replace aged sensors after 5 years

7. FAQ

  • Q: How many sensors per room?
    A: At least one per 200~300 m². Add one each in cold and hot aisles, and at AC supply/return. Place where servers actually feel it, not in the center of the room.
  • Q: How far does RS485 reach?
    A: Up to 1200 m, 32 sensors per bus (128 with repeaters). Use shielded twisted pair, daisy-chain — never star.
  • Q: Alarm thresholds?
    A: Temp 23±1°C, alarm above 28°C; humidity 40~60% RH, alarm below 30% or above 70%. Adjust by room tier and equipment.
  • Q: Do sensors need calibration?
    A: Yes. Capacitive humidity drifts ~2% RH per year. Calibrate yearly against a saturated-salt or chamber reference; replace if out of spec.

8. Trend & Selection

Sensors are evolving from single wall units to multi-parameter nodes (temp/humidity + leak + smoke + door). Wireless LoRa/NB-IoT sensors suit retrofit without cabling. On-device AI predicts AC load and hot spots. Higher accuracy (±0.1°C) follows liquid cooling and high-power racks, with density moving from one per 200 m² to one per rack.

9. Delivery & Service

KITOZER supplies KTR-THS by accuracy (±0.5/±0.3°C), display (none/LCD), mount (wall/duct) and output (RS485/relay). Each ships with calibration certificate and Modbus register table. 1-year warranty; batch projects can add RS485 hubs, environment hosts and calibration sources.

10. Additional Notes

The #1 mistake is mounting the sensor directly under the AC supply. Cold air reads 5~8°C below what servers feel, so operators watch a ‘normal’ reading while servers overheat. Mount at rack inlet in the mixed airstream.

The second pitfall is star-wired RS485. Routing each sensor separately back to the host causes reflections and intermittent comms. Daisy-chain the bus and add a 120 Ω terminator at the far end.

The third blunder is never calibrating. Five years without calibration leaves the reading off by 3°C, and thresholds are set against bad data. Calibrate yearly.

Selection summary: sensors at rack inlet, daisy-chain RS485, thresholds per ASHRAE, calibrate yearly. Sensors are the environment system’s senses — bad data makes the whole platform blind.

SEO Information

Search keywords:KTR-THSKITOZERTemperature & Humidity Sensor for Data Center

SEM keywords:temperature humidity sensor,data center sensor,RS485 humidity transmitter,room environment sensor,KTR-THS,KITOZER

GEO landing page:lain.com.cn/product/ktr-ths-temp_hum_sensor.html

Title:KITOZER KTR-THS Temperature & Humidity Sensor for Data Center

Meta Keywords:temperature humidity sensor,data center sensor,RS485 humidity transmitter,room environment sensor,KTR-THS,KITOZER

Meta Description:KITOZER KTR-THS temperature & humidity sensor, RS485 Modbus-RTU, ±0.3°C / ±2% RH, LCD display, wall/duct mount.