KITOZER KTR-WC9 8-zone Locating Leak Controller for Datacenter

KITOZER KTR-WC9 8-zone Locating Leak Controller for Datacenter

Brand: KITOZER Series: KTR-WC9 Category: Environmental Monitoring / Leak Detection

8-zone locating≤1m accuracySensing cableRS485/relayKTR-WC9

1. Overview

KITOZER KTR-WC9 is an 8-zone locating leak controller used with a locating sensing cable laid under precision air conditioners, near water valves, humidifier pipes and water tanks. On a leak, the controller not only alarms but pinpoints the zone and distance to the leak point. Datacenters fear water: AC condensate leaks, humidifier hose bursts, hidden seepage under the floor — water under live gear causes short circuits and fires. A leak system is the room’s water sentry.

KTR-WC9 has 8 locating inputs, each up to 100m of sensing cable, accuracy ≤1m. The LCD shows which zone and how many meters out; relay output (NO/NC) and RS485 Modbus upload to the DCIM. Zones are independent, suiting multiple A/C positions. Powered DC 12~24V, wall or rack mount. The locating cable has two sensing conductors whose resistance changes on water; secured by clips, terminated at the far end.

Used in datacenter rooms, UPS rooms, battery rooms, labs and warehouses. Typical layout: loop one cable around the base of each precision A/C, split across 8 zones; add cables near tanks, humidifier pipes and valves. Cables run under anti-static flooring or on the floor along likely leak paths. On leak, the controller beeps, the DCIM pops up and texts staff, and the A/C water inlet valve closes.

2. Key Features

8-zone locating

  • 8 independent zones.
  • Accuracy ≤1m.
  • ≤100m cable per zone.
  • LCD shows zone + distance.

Locating cable

  • 4-core sensing cable.
  • Resistance-change locating.
  • Wipe-and-reuse.
  • End terminator.

Multiple outputs

  • Relay NO/NC.
  • RS485 Modbus.
  • Sound/light alarm.
  • DCIM linkage.

Flexible install

  • Wall/rack mount.
  • DC 12~24V.
  • Cable cuttable.
  • Clips/adhesive mount.

3. Specifications

Item KTR-WC9 KTR-WC4
Zones 8 4
Accuracy ≤1m ≤1m
Cable/zone ≤100m ≤100m
Output Relay+RS485 Relay+RS485
Display LCD LCD
Power DC 12~24V DC 12~24V
Alarm Sound/light+upload Sound/light+upload
Mount Wall/rack Wall/rack
Op. temp -10~60℃ -10~60℃

4. Reference Prices

KTR-WC9 8-zone locating controller (LCD, relay+RS485): Reference USD 111~278 / pc (ref. CNY 800~2000 at ~7.2)

KTR-WC4 4-zone economy (small rooms): Reference USD 69~167 / pc (ref. CNY 500~1200 at ~7.2)

Reference only; price varies by zones and quantity. Locating cable (per meter), clips, terminators and DCIM host billed separately. Exchange: 1 USD ~ 7.2 CNY (Oct 2026).

5. Applications

  • Under-A/C leak monitoring.
  • Humidifier/condensate pipe runs.
  • Around tanks and valves.
  • Seepage under raised floor.
  • DCIM-linked alarm.

6. Installation & Maintenance

Installation

  • Wall-mount or DIN-rail the controller.
  • Lay cable along A/C base and pipe routes.
  • Fix with clips/adhesive; don’t tension it.
  • One end to controller, the other to terminator.
  • RS485 to DCIM acquisition module.
  • Power on self-test; simulate a drip to test.

Maintenance

  • Simulate a drip test quarterly.
  • Wipe cable dust/oil dry.
  • Check for rodent bites/breaks.
  • Verify end terminator contact.
  • Close the alarm loop.

7. FAQ

  • Q: Locating vs non-locating?
    A: Non-locating point probes only know ‘somewhere leaks’; locating cable shows the meter distance. Large rooms with many A/C units need locating; small rooms can use point probes.
  • Q: Can the cable be cut shorter?
    A: Yes, trim to the route. Terminate the controller end properly, and always fit the end terminator — otherwise false alarms or no alarm.
  • Q: Too many false alarms?
    A: Often the cable is dusty/oily, condensing, or lying on a damp floor. Clean it, elevate it, and avoid condensation spots to cut false alarms.
  • Q: How much cable per room?
    A: Along likely paths: ~2~3m loop around each A/C base plus pipe runs. A 10-A/C room needs ~30~50m, split into 4~8 zones.

8. Trend & Selection

Leak detection is moving from point probes to locating cable plus zoning, deeply integrated with DCIM/BMS. Trends are wireless LoRa sensing cable to cut wiring, cable integrated with temp/humidity, and AI trend prediction. Choose 8-zone locating for large multi-A/C rooms; 4-zone for small rooms; ≤100m per zone; ≤1m accuracy; RS485 to DCIM; quarterly drip test; keep cable spares.

9. Delivery & Service

KITOZER supplies the leak system: based on A/C count, pipe routes and area, we recommend controller model and cable length. Bundled with DCIM host, temp/humidity and A/C linkage. Delivery includes controller, sensing cable (by meter), clips, terminators and manual; bulk orders include on-site laying guidance. Warranty covers replacement.

10. Additional Notes

The most common leak problem is a cable laid without an end terminator. The terminator is a matching resistor; without it the controller false-alarms or fails to alarm. Fit it on every cable end until it clicks.

Another pitfall: cable resting on a persistently damp floor. Constant condensation causes continuous alarms; staff go numb and miss the real leak. Elevate the cable slightly, avoid permanently damp spots, and run it only along likely leak paths.

Selection summary: 8-zone locating, ≤1m accuracy; ≤100m per zone; fit end terminators; elevate off damp; quarterly drip test; link to DCIM. The leak controller is the room’s water sentry — an accurate sentry catches leaks early.

SEO Information

Search keywords:leak controllerlocating leak8-zone monitordatacenter leaksensing cableKTR-WC9KITOZER

SEM keywords:leak controller price,locating leak detector supplier,8-zone leak monitor,datacenter leak cable,water leak detection,KTR-WC9,KITOZER

GEO landing page:lain.com.cn/product/ktr-wc9-8zone-locating-leak-controller.html

Title:KITOZER KTR-WC9 8-zone Locating Leak Controller for Datacenter

Meta Keywords:leak controller,locating leak detection,8-zone leak monitor,datacenter leak sensor,locating leak cable,water leak detection,KTR-WC9,KITOZER

Meta Description:KITOZER KTR-WC9 8-zone locating leak controller, accuracy ≤1m, with sensing cable, for datacenter under-A/C and water-pipe leak monitoring.

Anchor: KITOZER by Guangzhou Laian · Environmental monitoring

Contact Us

Guangzhou Laian Intelligent System Development Co., Ltd. (KITOZER brand)
Tel/WeChat: +86 13922289957 | +86 18520668845
WHATSAPP: +86 19068534140
Web: lain.com.cn | gdlain.com

Shopping Cart