ToggleKITOZER KTR-WC9 8-zone Locating Leak Controller for Datacenter
Brand: KITOZER Series: KTR-WC9 Category: Environmental Monitoring / Leak Detection
8-zone locating≤1m accuracySensing cableRS485/relayKTR-WC9
1. Overview
KITOZER KTR-WC9 is an 8-zone locating leak controller used with a locating sensing cable laid under precision air conditioners, near water valves, humidifier pipes and water tanks. On a leak, the controller not only alarms but pinpoints the zone and distance to the leak point. Datacenters fear water: AC condensate leaks, humidifier hose bursts, hidden seepage under the floor — water under live gear causes short circuits and fires. A leak system is the room’s water sentry.
KTR-WC9 has 8 locating inputs, each up to 100m of sensing cable, accuracy ≤1m. The LCD shows which zone and how many meters out; relay output (NO/NC) and RS485 Modbus upload to the DCIM. Zones are independent, suiting multiple A/C positions. Powered DC 12~24V, wall or rack mount. The locating cable has two sensing conductors whose resistance changes on water; secured by clips, terminated at the far end.
Used in datacenter rooms, UPS rooms, battery rooms, labs and warehouses. Typical layout: loop one cable around the base of each precision A/C, split across 8 zones; add cables near tanks, humidifier pipes and valves. Cables run under anti-static flooring or on the floor along likely leak paths. On leak, the controller beeps, the DCIM pops up and texts staff, and the A/C water inlet valve closes.
2. Key Features
8-zone locating
- 8 independent zones.
- Accuracy ≤1m.
- ≤100m cable per zone.
- LCD shows zone + distance.
Locating cable
- 4-core sensing cable.
- Resistance-change locating.
- Wipe-and-reuse.
- End terminator.
Multiple outputs
- Relay NO/NC.
- RS485 Modbus.
- Sound/light alarm.
- DCIM linkage.
Flexible install
- Wall/rack mount.
- DC 12~24V.
- Cable cuttable.
- Clips/adhesive mount.
3. Specifications
| Item | KTR-WC9 | KTR-WC4 |
|---|---|---|
| Zones | 8 | 4 |
| Accuracy | ≤1m | ≤1m |
| Cable/zone | ≤100m | ≤100m |
| Output | Relay+RS485 | Relay+RS485 |
| Display | LCD | LCD |
| Power | DC 12~24V | DC 12~24V |
| Alarm | Sound/light+upload | Sound/light+upload |
| Mount | Wall/rack | Wall/rack |
| Op. temp | -10~60℃ | -10~60℃ |
4. Reference Prices
KTR-WC9 8-zone locating controller (LCD, relay+RS485): Reference USD 111~278 / pc (ref. CNY 800~2000 at ~7.2)
KTR-WC4 4-zone economy (small rooms): Reference USD 69~167 / pc (ref. CNY 500~1200 at ~7.2)
Reference only; price varies by zones and quantity. Locating cable (per meter), clips, terminators and DCIM host billed separately. Exchange: 1 USD ~ 7.2 CNY (Oct 2026).
5. Applications
- Under-A/C leak monitoring.
- Humidifier/condensate pipe runs.
- Around tanks and valves.
- Seepage under raised floor.
- DCIM-linked alarm.
6. Installation & Maintenance
Installation
- Wall-mount or DIN-rail the controller.
- Lay cable along A/C base and pipe routes.
- Fix with clips/adhesive; don’t tension it.
- One end to controller, the other to terminator.
- RS485 to DCIM acquisition module.
- Power on self-test; simulate a drip to test.
Maintenance
- Simulate a drip test quarterly.
- Wipe cable dust/oil dry.
- Check for rodent bites/breaks.
- Verify end terminator contact.
- Close the alarm loop.
7. FAQ
- Q: Locating vs non-locating?
A: Non-locating point probes only know ‘somewhere leaks’; locating cable shows the meter distance. Large rooms with many A/C units need locating; small rooms can use point probes. - Q: Can the cable be cut shorter?
A: Yes, trim to the route. Terminate the controller end properly, and always fit the end terminator — otherwise false alarms or no alarm. - Q: Too many false alarms?
A: Often the cable is dusty/oily, condensing, or lying on a damp floor. Clean it, elevate it, and avoid condensation spots to cut false alarms. - Q: How much cable per room?
A: Along likely paths: ~2~3m loop around each A/C base plus pipe runs. A 10-A/C room needs ~30~50m, split into 4~8 zones.
8. Trend & Selection
Leak detection is moving from point probes to locating cable plus zoning, deeply integrated with DCIM/BMS. Trends are wireless LoRa sensing cable to cut wiring, cable integrated with temp/humidity, and AI trend prediction. Choose 8-zone locating for large multi-A/C rooms; 4-zone for small rooms; ≤100m per zone; ≤1m accuracy; RS485 to DCIM; quarterly drip test; keep cable spares.
9. Delivery & Service
KITOZER supplies the leak system: based on A/C count, pipe routes and area, we recommend controller model and cable length. Bundled with DCIM host, temp/humidity and A/C linkage. Delivery includes controller, sensing cable (by meter), clips, terminators and manual; bulk orders include on-site laying guidance. Warranty covers replacement.
10. Additional Notes
The most common leak problem is a cable laid without an end terminator. The terminator is a matching resistor; without it the controller false-alarms or fails to alarm. Fit it on every cable end until it clicks.
Another pitfall: cable resting on a persistently damp floor. Constant condensation causes continuous alarms; staff go numb and miss the real leak. Elevate the cable slightly, avoid permanently damp spots, and run it only along likely leak paths.
Selection summary: 8-zone locating, ≤1m accuracy; ≤100m per zone; fit end terminators; elevate off damp; quarterly drip test; link to DCIM. The leak controller is the room’s water sentry — an accurate sentry catches leaks early.