Table of Contents
ToggleKITOZER KTR-WS2 Water Leak Sensing Cable with Localization
Brand: KITOZER Series: KTR-WS2 Category: Environmental Monitoring / Leak Detection
Locating leak cableRS485 Modbus1 m accuracyNon-conductive liquidKTR-WS2
1. Overview
Water leaks are the most common – and most preventable – data center incident. Precision AC chilled-water pipes, humidifier lines and condensate drains run under the raised floor; a loose or aged joint floods under the floor, soaking UPS batteries and switch power supplies, even shorting into a fire. A leak sensing cable is a flat ribbon laid under the floor along pipes. When dry, two sense wires are insulated and the controller sees no continuity; when water touches the ribbon, it bridges the wires, the controller detects the resistance change and alarms – and a locating model computes how far the leak is from the host (about 1 m accuracy). Rooms use locating cables: a non-locating alarm only says “leak” without telling you where, and hunting for a leak under hundreds of square meters of floor is too slow.
KITOZER KTR-WS2 is a locating leak sensing cable system. Three parts: KTR-WS2-J controller host (in-rack, DC12-24 V, RS485 Modbus or Ethernet to EM, screen shows leak distance in meters, buzzer); KTR-WS2-L sensing ribbon (4-core flat, PVC jacket, flexible, cut to length, priced per meter, both ends to the host and end-of-line resistor); KTR-WS2-5 point probe (for AC unit bottoms, drain outlets – local points where you do not run a ribbon). Working principle: four conductors in the ribbon – two sense wires, two reference wires – are normally high-resistance; a water film bridges them below a threshold, and the host measures the resistance gradient along the run (TDR time-domain reflectometry) to compute distance. The ribbon detects water and most non-conductive liquids (chilled/condensate water; it does not detect diesel – oil is insulating, use a dedicated oil ribbon KTR-OS; this series is mainly for water). One run max 100 m; beyond that add segment controllers.
Selection: locating vs non-locating (rooms must use locating – non-locating only says “leak” and you cannot find it fast; non-locating suits tiny single-point rooms); cable length (run a loop along every possible pipe – around precision ACs, along chilled lines, under humidifiers; a 100 m² room typically uses 30-50 m); ribbon + points combo (ribbon along pipes, point probes at AC bottoms); comm (RS485 Modbus to EM; Ethernet for standalone small sites); mounting (lay the ribbon on the floor directly under the pipe, clip every meter, do not suspend it, do not run it under floor pedestals that block water); termination (the far end must have the 120 ohm end resistor or the host cannot locate). Note: do not cut a ribbon shorter than 3 m (locating fails); dust on the ribbon does not alarm (needs real water); after install, pour a cup of water to verify localization.
2. Key Features
Locating
- TDR reflectometry
- +/-1 m accuracy
- Up to 100 m/run
- Meter readout
Sensing
- Water/non-conductive
- 4-core ribbon
- PVC jacket
- Cut-to-length
Connectivity
- RS485 Modbus
- Ethernet option
- Buzzer alarm
- EM upload
3. Specifications
| Item | Item | KTR-WS2-L | KTR-WS2-P | KTR-WS2-5 | KTR-WS2-J |
|---|---|---|---|---|---|
| Type | Locating cable | Locating cable | Point sensor | Cable controller | |
| Accuracy | +/-1 m | +/-1 m | Single point | Host locates | |
| Liquid | Water/non-conductive | Water/non-conductive | Water | Connects WS2-L | |
| Comm | RS485 Modbus | RS485 Modbus | Dry/RS485 | RS485/Ethernet | |
| Cable length | Up to 100 m | Up to 100 m | Probe 2 m | Host | |
| Power | DC12-24 V | DC12-24 V | DC12 V | DC12-24 V |
4. Reference Prices
KTR-WS2-L locating cable (per meter): Reference USD 8-13 / m (ref. CNY 60-90)
KTR-WS2-P locating cable (PVC jacket): Reference USD 8-13 / m (ref. CNY 60-90)
KTR-WS2-5 point leak probe: Reference USD 11-17 / pc (ref. CNY 80-120)
KTR-WS2-J locating controller host: Reference USD 111-167 / pc (ref. CNY 800-1200)
KTR-WS2-ACC clip/terminator/end resistor: Reference USD 1-4 / set (ref. CNY 10-30)
Reference only. 1-year warranty. Exchange: 1 USD ≈ 7.2 CNY.
5. Applications
- Under AC condensate line
- Under-floor pipe run
- UPS battery room
- Fresh-water/plumbing
- Room low points
6. Deployment & Installation
Route
- Directly under pipe
- Clip every meter
- Loop around AC
- Not under pedestals
Wiring
- Near end to host
- Far end 120 ohm
- Daisy-chain RS485
- Single-end shield ground
Test
- Pour a cup of water
- Read distance
- EM receives alarm
- Wipe dry to reset
7. FAQ
- Q: How much ribbon per room?
A: Route along every pipe that can leak. Mainly around precision ACs (condensate tray, humidifier lines), along chilled-water pipes, and at fresh-air-unit drains. One AC loop is ~5-8 m, pipe runs add a point every 5 m. A 100 m² room with 4 ACs and chilled water needs ~30-50 m. Lay a loop along the bottom of UPS racks (battery electrolyte leaks are detected too). - Q: Does the ribbon detect oil?
A: KTR-WS2 detects water and non-conductive liquids (low water resistance bridges the wires); diesel and oil are insulating and not detected. Oil spills need a dedicated oil-sensing cable (conductive hydrocarbon ribbon KTR-OS). In rooms, UPS battery leakage is dilute sulfuric acid (conductive, WS2 detects it); diesel tank farms need the oil ribbon. - Q: How to maintain a ribbon under the floor?
A: No routine maintenance (passive detection). Once a year, do a water test (pour a small cup on the ribbon, check the host alarms and the distance is right). Ribbon life is 5-8 years (PVC ages, insulation drops, false alarms) – replace wholesale at end of life. Do not step on it or stack gear on it. - Q: Why a 120 ohm end resistor?
A: Locating uses TDR: the host sends an electrical pulse down the ribbon. A 120 ohm matching resistor at the far end (equal to the cable characteristic impedance) prevents end reflection; a leak changes impedance, and the reflected return time converts to distance. No resistor or a wrong value garbles the reflection and the distance is wrong or missing. Use the factory terminator – do not substitute a generic resistor.
8. Trend & Selection
Leak detection is evolving from ribbon point sensing toward multi-sensor and video linkage. Trends: wireless leak sensors (battery-powered, stuck under AC units, no ribbon, for retrofits); ribbon + T/H combo (a T/H node every 5 m on the ribbon, dual-use); linkage with precision AC (a leak alarm auto-closes that zone’s inlet solenoid to reduce spill); mapped localization (EM draws a room plan, the leak lights up as a red dot); distributed fiber sensing (DTS fiber measures temperature and leak over very long pipe galleries). Traditional locating ribbons remain mainstream along AC water lines. Select by: locating +/-1 m, route along pipes, 120 ohm end, RS485 to EM, annual water test, replace ribbon every 5-8 years.
9. Delivery & Service
KITOZER KTR-WS2 ships by host, ribbon (cut per meter) and point probe, each with controller, ribbon segment, terminator, clips and manual. 1-year warranty; bulk projects can bundle EM integration software, solenoid interlocks and shielded cable.
10. Additional Notes
Confirm leak-prone points (around ACs, along pipes), ribbon length (pipe length + 20% margin), comm (RS485 to EM), and valve interlock. For batch orders, lay a trial segment, pour water to verify the distance reading, then run the full loop.
Common mistake: running the ribbon on top of floor pedestals. Pedestals block water, which flows around them and misses the ribbon. Lay the ribbon under the floor, on the ground directly below the pipe, so water reaches it.
Second pitfall: no end terminator. Cutting the ribbon and leaving the far end open makes the host report “cable fault” or jump distances. The far end must take the factory 120 ohm terminator.
Third blunder: star-wiring the RS485 bus. Pulling each leak host back to the EM host in a star makes RS485 intermittent. Daisy-chain, with terminators at both bus ends.
Selection summary: locating, on the floor under pipes, 120 ohm end, daisy-chain bus, annual water test, replace ribbon every 5-8 years.
SEO Information
Search keywords:KTR-WS2KITOZER
SEM keywords:water leak sensing cable,locating leak wire,data center leak detection,water leak sensor,locating leak detection,KTR-WS2,KITOZER
GEO landing page:lain.com.cn/product/ktr-ws2-water-leak-sensing-cable-localization.html
Title:KITOZER KTR-WS2 Water Leak Sensing Cable with Localization
Meta Keywords:water leak sensing cable,locating leak wire,data center leak detection,water leak sensor,locating leak detection,KTR-WS2,KITOZER
Meta Description:KITOZER KTR-WS2 locating water leak sensing cable, RS485 Modbus, 1 m accuracy, detects non-conductive liquids, under-floor / AC pipe leak detection.
Anchor: KITOZER by Guangzhou Laian · KITOZER products
Contact Us
Guangzhou Laian Intelligent System Development Co., Ltd. (KITOZER brand)
Tel/WeChat: +86 13922289957 | +86 18520668845
WHATSAPP: +86 19068534140
Web: lain.com.cn | gdlain.com