KITOZER KYN28A-12 metalclad withdrawable switchgear is the standard 10kV indoor switchboard used in distribution substations, industrial plants, and commercial buildings. It houses a vacuum circuit breaker on a withdrawable truck, with segregated compartments for bus, cable, and relay rooms. KYN28A is the most widely adopted medium voltage switchgear type, offering high reliability, easy maintenance, and full protection coordination. It is the default choice for any new 10kV indoor switchroom project.
Table of Contents
ToggleProduct Overview
The switchgear is a steel sheet cubicle divided into four compartments: busbar compartment, breaker truck compartment, cable compartment, and relay compartment. Shutters close automatically over the bus contacts when the truck is racked out, isolating live parts. Mechanical interlocks prevent incorrect operations. A pressure relief duct at the top directs internal arc gases away from personnel. Breaker trucks are interchangeable between panels, allowing fast swap during maintenance. The relay compartment on the front of the panel houses protection relays, meters, and terminal blocks, with its own gland plate for secondary cables.
Technical Specifications
Rated voltage 12kV, rated frequency 50/60Hz, rated current up to 1250A or 1600A, rated short-time withstand 25kA for 4s, peak withstand 63kA, power frequency withstand 42kV for 1 minute, lightning impulse 75kV peak. Breaker VCB 1250A 25kA. Protection class IP2X for accessible surfaces. Internal arc classification IAC AFLR for 1s optional. Compliance with IEC 62271-200 and GB 3906. Panel width 800mm, depth 1500mm, height 2300mm. The busbar compartment is partitioned vertically so a fault in one section does not propagate to adjacent panels. Cable compartment fits up to 3 cable terminals per phase.
Applications
KYN28A panels are used as the main 10kV switchboard in industrial plants, commercial towers, hospital substations, data centers, and water pumping stations. Typical lineups include incoming panel, bus tie panel, transformer feeder panel, capacitor bank feeder, and motor feeder panels. The withdrawable breaker allows fast maintenance and easy spare truck handling. It is the default choice for new 10kV indoor switchrooms. In industrial plants, each production line has its own feeder panel. In data centers, the lineup includes incoming, transformer feeder, and standby generator breaker panels.
Advantages
Metalclad segregation ensures that a fault in one compartment does not propagate. Withdrawable breaker truck allows maintenance without de-energizing the main bus. Interlock logic prevents human error. Pressure relief duct protects operators during internal arc faults. Standard dimensions fit most switchroom layouts. Rich accessory options include PT, CT, arresters, and earth switches. Long service life and large installed base mean local support is readily available. Because the truck is interchangeable, one spare truck covers the whole switchroom, which is a major cost saving compared with dedicated breakers per panel.
Installation and Maintenance
Assemble panels on a common busbar duct, connect the horizontal busbar, and verify the earthing bus. Commissioning includes breaker functional tests, protection relay injection, interlock verification, and dielectric tests. Maintain annually by inspecting shutters, interlocks, and cable glands; measure contact resistance and vacuum integrity on breakers every three years. Keep one spare breaker truck for critical substations. Train operators on racking procedure and interlock bypass rules. After an internal arc event, inspect the affected compartment and busbar before re-energization, and replace any damaged shutters or insulators.
KYN28A panels are often the heart of a plant electrical room, so a structured maintenance plan pays off. Every year, inspect the shutters for smooth movement and check that they close automatically when the truck is withdrawn. Every three years, perform a vacuum interrupter withstand test on each breaker and measure contact travel. Keep the relay compartment clean and dry, and verify the anti-condensation heater. When a breaker trips on fault, record the fault current and inspect the interrupter before re-energization. Operators should be trained on the interlock sequence and only use the bypass key under controlled conditions. A spare breaker truck is the single most valuable spare part in the switchroom.
When ordering a KYN28A lineup, specify whether each panel should have a local indicator, a multifunction meter, or a protection relay, because the relay compartment layout depends on the selected devices. The cable compartment should have adequate space for the selected cable bending radius, and cable glands must be rated for the cable size. Include an earthing switch on cable feeders so the cable can be safely earthed when isolated. The pressure relief duct at the top must vent to outside the switchroom, not into a ceiling void, to protect personnel during an internal arc event.
Ordering and Support
Ordering requires the one line diagram, breaker ratings, CT and PT configurations, protection relay models, and meter requirements. KITOZER supplies the KYN28A lineup fully assembled and factory tested, with type test certificates, wiring diagrams, and as built drawings. One spare breaker truck is recommended for critical substations. Technical support covers protection coordination, commissioning, and operator training. The switchgear is backed by a one year on site warranty and a five year warranty on the busbar system.