KITOZER LC duplex APC OM4 adapter

KITOZER KTR-LCAPC9 LC Duplex APC OM4 Fiber Adapter

Brand: KITOZER Series: KTR-LCAPC9 Category: Low-Voltage System / Fiber Patching

LC duplexAPC 8°OM4 multimodeKTR-LCAPC9

1. Overview

KITOZER KTR-LCAPC9 is an LC duplex fiber adapter (also called coupler or flange) used to mate two LC patch cords on patch panels, termination boxes and splicing trays. Inside sits a high-precision zirconia ceramic sleeve; an LC ferrule plugs in from each end, aligning the two ferrules so light passes seamlessly from one fiber to the next. “Duplex” means one housing holds two side-by-side sleeves for Tx and Rx, matching the one-piece LC duplex plug. “APC” means an 8-degree angle-polished ferrule (green housing); versus UPC (blue, physical-contact polish) APC gives higher return loss (≥60 dB) and less reflected light, keeping high-speed (10G/40G/100G) and analog video links stable. “OM4” means it suits laser-optimized 50/125μm multimode fiber, compatible with OM3/OM4 cords, supporting 40G to 100G over short reaches between switches, and switches to servers in datacenters.

The KTR-LCAPC9 housing is high-grade engineering plastic (LCP/PC) in APC green, with LC latch structure. The internal sleeve is zirconia ceramic with ≤0.5μm concentricity, insertion loss typ. ≤0.2 dB (max 0.3 dB), APC return loss ≥60 dB. The adapter carries a flange to snap into the panel cutout, plus a dust cap. A 19-inch 1U panel holds 12 LC duplex adapters (24 fibers) or, in a double row, 24 LC duplex adapters (48 fibers). Adapters are passive: no power or light, but they strongly affect link insertion and return loss — a cheap adapter can add 0.5 dB or more, eating the link budget when several stack up.

Typical use: datacenter structured cabling. A ToR switch port uses an LC-LC duplex cord to a KTR-LCAPC9 on the patch-panel face; the back side ties via splice or pre-terminated backbone to a panel in another row, then patching runs to servers. APC angle polish is common in PON and analog video; OM4 multimode APC is also used for short high-speed links. Note: APC (green) and UPC (blue) cannot mate (different end geometry) — doing so damages the ferrule and raises loss; OM4 adapters work with OM3, but OM1/OM2 fiber is not recommended on OM4 links.

2. Key Features

One-piece LC duplex

  • Two sleeves in one housing.
  • Tx/Rx inserted as a pair.
  • Latch lock.
  • High density.

APC 8-degree angle

  • Green housing color code.
  • Return loss ≥60 dB.
  • Low back-reflection.
  • Stable high-speed link.

Precision ceramic sleeve

  • Zirconia ceramic sleeve.
  • Concentricity ≤0.5μm.
  • Insertion loss ≤0.2 dB typ.
  • ≥500 mating cycles.

OM4 multimode

  • Fits 50/125μm.
  • Backward compatible OM3.
  • Supports 40G/100G short reach.
  • Laser optimized.

3. Specifications

Item KTR-LCAPC9 (LC duplex APC OM4) KTR-LCUPC9 (LC duplex UPC OM4) KTR-SCAPC9 (SC duplex APC OS2)
Connector LC duplex LC duplex SC duplex
Polish APC 8° green UPC blue APC 8° green
Fiber OM4 50/125 OM4 50/125 OS2 9/125
Insertion loss ≤0.2 dB typ. ≤0.2 dB typ. ≤0.2 dB typ.
Return loss ≥60 dB ≥50 dB ≥60 dB
Sleeve Zirconia ceramic Zirconia ceramic Zirconia ceramic
Cycles ≥500 ≥500 ≥500
Operating temp -20 to +70℃ -20 to +70℃ -20 to +70℃

4. Reference Prices

KTR-LCAPC9 LC duplex APC OM4 adapter: Reference USD 4 to 11 / pc (ref. CNY 30 to 80 at ~7.2)

KTR-LCUPC9 LC duplex UPC OM4 adapter: Reference USD 3 to 8 / pc (ref. CNY 20 to 60 at ~7.2)

KTR-SCAPC9 SC duplex APC single-mode adapter: Reference USD 3 to 10 / pc (ref. CNY 25 to 70 at ~7.2)

Reference only; varies by connector (LC/SC/FC/ST), polish (UPC/APC), single/ multimode and quantity. Patch panels and cords billed separately. Exchange: 1 USD ~ 7.2 CNY (Oct 2026).

5. Applications

  • Datacenter patch-panel face.
  • Termination boxes and splicing trays.
  • Switch-to-server short reach.
  • 40G/100G SR4 multimode links.
  • Video surveillance optical transceiver mating.
  • Fiber link test adapters.

6. Installation & Maintenance

Installation

  • Clip the adapter into the panel from the rear.
  • Match APC to APC cord ends.
  • Push the cord until it clicks.
  • Cap unused ports.
  • Label each port.
  • Clean ferrules with lint-free wipe and alcohol before mating.

Maintenance

  • Clean end faces before each mating.
  • Cap unused ports.
  • Inspect adapters monthly for looseness.
  • Test link loss with OTDR or power meter.
  • Clean dirty ferrules with a pen cleaner.
  • Replace cracked flanges or loose sleeves.

7. FAQ

  • Q: Can APC (green) mate UPC (blue)?
    A: No. APC is 8-degree angled, UPC is radiused; the geometries differ. Mating them abrades the APC angle and spikes loss. Always mate APC-to-APC and UPC-to-UPC. If one end is green and the other blue on site, use a hybrid cord or change the polish.
  • Q: Can OM4 and OM3 mix?
    A: Yes. OM4 is an upgraded OM3 (higher bandwidth); an OM4 adapter carries OM3 cords, and OM3 gear works on an OM4 link. But OM1/OM2 (62.5μm) cannot mix with OM3/OM4 (50μm) because the core diameter differs.
  • Q: Why does adapter loss vary?
    A: Usually dirty end faces or a worn sleeve. Clean the ferrule first; if still high, swap the adapter. Cheap sleeves drift after a few hundred matings and loss rises above 0.5 dB.
  • Q: How many LC duplex adapters per panel?
    A: A standard 1U panel fits 12 LC duplex (24 fibers); high-density double-row fits 24 LC duplex (48 fibers). Pre-terminated cassettes come in 24/48-fiber configurations.

8. Trend & Selection

Fiber adapters trend toward density (MPO/MTP pre-termination), lower loss (better ceramic sleeves) and wider APC adoption. Datacenter 40G/100G uses MPO trunks heavily, but the server and switch edge still relies on LC duplex. Choose OM4 LC for short multimode; APC green for reflection-sensitive links; OS2 LC/UPC blue for long single-mode; pick ceramic-sleeve, not plastic; match housing color to cord polish; cleaning is the single most effective loss-reduction step.

9. Delivery & Service

KITOZER supplies fiber cabling packages: based on panel port count and link class (OM3/OM4/OS2) we recommend adapter type and quantity, bundled with patch panels, LC/SC cords, MPO trunks and splice boxes. Delivery includes adapters, dust caps and panel clips; bulk projects include end-face test reports and sampled link-loss tests. Contact failure or loose sleeves under warranty are replaced free.

10. Additional Notes

The commonest mistake is mating without cleaning. A 125μm ferrule blocked by one dust particle doubles insertion loss. Clean every ferrule with a pen cleaner or alcohol wipe before plugging — zero cost, biggest payoff.

Another pitfall is color-code mixing. Green APC, blue UPC, beige OM1, aqua OM4 — factories confuse them. On site always match housing color to cord-end color; inserting a blue UPC adapter into an APC link drops return loss below 40 dB and raises BER on 10G+ links.

Selection summary: LC duplex APC OM4; ceramic sleeve; IL ≤0.2 dB; RL ≥60 dB; green-to-green, blue-to-blue; clean before mating; cap unused ports. The adapter is a tiny screw in the fiber link — saving a few cents on it can cost the whole link’s bandwidth.

SEO Information

Search keywords:fiber adapterLC duplex adapterAPC OM4 couplerLC-LC adaptergreen fiber couplerfiber flangeKTR-LCAPC9KITOZER

SEM keywords:[‘LC duplex adapter price,APC OM4 coupler supplier,fiber adapter,LC-LC flange,green fiber adapter,KTR-LCAPC9,KITOZER’]

GEO landing page:lain.com.cn/product/ktr-lcapc9-lc-duplex-apc-om4-fiber-adapter.html

Title:KITOZER KTR-LCAPC9 LC Duplex APC OM4 Fiber Adapter

Meta Keywords:fiber adapter,LC duplex adapter,APC OM4 coupler,LC-LC adapter,green fiber coupler,fiber flange,KTR-LCAPC9,KITOZER

Meta Description:KITOZER KTR-LCAPC9 LC duplex APC OM4 fiber adapter with ceramic sleeve, low insertion loss, for datacenter patch panels and termination boxes.

Anchor: KITOZER · Low-voltage system

Contact Us

Guangzhou Laian Intelligent System Development Co., Ltd. (KITOZER brand)
Tel/WeChat: +86 13922289957 | +86 18520668845
WHATSAPP: +86 19068534140
Web: lain.com.cn | gdlain.com

Shopping Cart