Brand: KITOZER Series: KTR-LCAPC7 Category: Data Center Engineering / Fiber Cabling
fiber adapterLC duplexAPC single-modegreen flangestructured cablingKTR-LCAPC7
1. Overview
KITOZER KTR-LCAPC7 is an LC duplex APC single-mode fiber adapter — also called an LC APC flange or coupler — a passive component that precisely aligns two LC APC connectors in carrier-grade cabling. APC (Angled Physical Contact) means the ferrule end face is polished to an 8° angle, deflecting reflected light into the cladding where it dissipates; return loss reaches ≥60 dB, well above UPC’s ≥50 dB. APC connectors are universally identified by an emerald-green flange, clearly distinguished from blue UPC flanges — mixing APC and UPC in one sleeve scratches the end faces and raises loss.
The LC interface uses a 1.25 mm zirconia ferrule with an RJ45-style latch, doubling port density versus SC. KTR-LCAPC7 is a duplex body — two LC ports molded side-by-side into one flange, carrying RX and TX in a single module that snaps into high-density panel cutouts. Single-mode fiber (G.652D/G.657A) at 1310/1550 nm reaches 10 km+, the standard choice for data-center backbone and optical-transport links.
The zirconia ferrule is precision-bored to φ1.25±0.0005 mm with an 8° APC polish. Insertion loss ≤0.2 dB, return loss ≥60 dB, ≥1000 mating cycles. The plastic housing with snap clips fits standard LC duplex panel cutouts. KTR-LCAPC7 offers APC-APC straight-through plus APC-UPC hybrids (note: hybrid returns to UPC-level return loss).
2. Key Features
8° APC polish
- Emerald green flange.
- Return loss ≥60 dB.
- Reflection diverted to cladding.
High-density duplex
- Molded duplex body.
- 1.25 mm ferrule.
- RJ45 latch.
Single-mode long reach
- G.652D/G.657A compatible.
- 1310/1550 nm windows.
- 10 km+ reach.
Precision build
- Zirconia ferrule.
- Insertion loss ≤0.2 dB.
- ≥1000 cycles.
3. Specifications
| Item | KTR-LCAPC7 |
|---|---|
| Connector | LC duplex (RX+TX in one body) |
| Fiber | Single-mode G.652D/G.657A 9/125μm |
| End face | APC 8° angled |
| Flange color | Emerald green |
| Ferrule | Zirconia ceramic φ1.25mm |
| Insertion loss | ≤0.2 dB |
| Return loss | ≥60 dB |
| Mating cycles | ≥1000 |
| Wavelength | 1310 / 1550 nm |
| Operating temp | -20~70°C |
| Housing | Engineering plastic |
4. Reference Prices
KTR-LCAPC7 LC duplex APC adapter (standard plastic): Reference USD 1.7~3.3 / pc (ref. CNY 12~24 at ~7.2)
KTR-LCAPC7 LC duplex APC adapter (zinc-alloy, with dust caps): Reference USD 3.5~6.3 / pc (ref. CNY 25~45 at ~7.2)
Reference only; priced by housing and quantity. Exchange: 1 USD ~ 7.2 CNY (Oct 2026).
5. Applications
- Data-center backbone patch panels.
- ODF box internal coupling.
- OTN/SDH transport links.
- FTTH terminal boxes.
- CATV optical networks.
6. Installation & Maintenance
Installation
- Confirm both ends are APC (green).
- Snap into panel cutout until it clicks.
- Clean end faces with lint-free alcohol wipe.
- Insert straight, no sideways wobble.
- Cap unused ports.
- Never mate APC with UPC.
- Keep bend radius ≥30 mm.
- Test loss with power meter after splicing.
Maintenance
- Check end faces quarterly for dust.
- Inspect ferrules with a microscope.
- Replace worn or contaminated adapters.
- Replace missing dust caps.
- Sample-test link loss periodically.
7. FAQ
- Q: Can APC mate with UPC?
A: No. APC is 8° angled, UPC is micro-sphere; forcing them together scratches the APC angle and ruins both insertion and return loss. Mate like-with-like. - Q: Does green always mean APC?
A: Yes by convention — green = APC, blue = UPC, beige = PC. Color-coding lets you spot the end-face type at a glance. - Q: Duplex vs two simplex?
A: Duplex is molded as one body with fixed RX/TX spacing and snaps in neatly; two simplex works but can be reversed. Use duplex for high-density. - Q: What does 60 dB return loss mean?
A: Only one-millionth of incident power is reflected. In analog CATV and high-speed DWDM, reflection causes distortion — that’s what APC suppresses.
8. Trend & Selection
As data centers move to 400G/800G modules, single-mode APC adapters with high return loss are the standard for long-haul backbone and DWDM links. Mate APC-to-APC (green-to-green); use duplex bodies for density; zirconia ferrules for low loss; cap unused ports. APC costs a little more than UPC but is foundational for signal quality on high-speed long-reach links.
9. Delivery & Service
KITOZER supplies KTR-LCAPC7 LC duplex APC adapters matched to panel cutout counts, with dust caps and snap clips. We provide link-loss test guidance. Warranty covers loose retention or worn ferrules.
10. Additional Notes
The most common mistake: mating APC with UPC. When contractors plug a green APC patch into a blue UPC port, the angled face meets the flat face; after a few insertions the APC angle is scratched and return loss drops from 60 dB to under 40 dB, wrecking the link’s signal-to-noise ratio. Match colors before you mate.
Another pitfall: inserting without cleaning. The fiber core is finer than a hair; one speck of dust costs 3+ dB. Wipe the end face clockwise with a lint-free alcohol swab and let it evaporate before inserting.
Selection summary: LC duplex; green APC flange; 8° angle; ≥60 dB return; single-mode long reach; same-color mating; clean end faces. The adapter is tiny, but one dirty face kills a 10G link.
SEO Information
Search keywords:LC duplex APC adaptersingle-mode couplergreen APC flange8-degree polishpatch panelKTR-LCAPC7KITOZER
SEM keywords:LC duplex APC adapter price,green APC coupler,single-mode LC flange,carrier-grade adapter,KTR-LCAPC7,KITOZER
GEO landing page:lain.com.cn/product/ktr-lcapc7-lc-duplex-apc-adapter.html
Title:KITOZER KTR-LCAPC7 LC Duplex APC Single-Mode Fiber Adapter
Meta Keywords:LC duplex APC adapter,single-mode coupler,green APC flange,8-degree polish,patch panel,KTR-LCAPC7,KITOZER
Meta Description:KITOZER KTR-LCAPC7 LC duplex APC single-mode fiber adapter, green flange, 8-degree polish, return loss ≥60 dB for carrier-grade cabling.