KITOZER LC loaded 12 port fiber patch panel

KITOZER KTR-LC12 LC Fully-Loaded 12-Port Fiber Patch Panel

Brand: KITOZER Series: KTR-LC12 Category: Data Center Engineering / Structured Cabling

patch panelLC duplex24 fibersfully loadedKTR-LC12

1. Overview

A fiber patch panel (ODF) is the distribution hub where backbone fiber cables terminate in the data closet. Incoming cable fibers are fusion-spliced to pigtails at the rear splice tray; pigtails couple through adapters to the front-panel ports; patch cords then connect ports to switch SFP ports. A standard 19-inch 1U panel has a splice tray at the back (coiling slack fibers and splices), an adapter plate in the middle, and a port panel on the front. LC connectors are half the size of SC, making them the de-facto standard in high-density rooms — one 1U panel holds 12 LC duplex adapters = 24 fibers, double the density of SC.

The KTR-LC12 is a 1U rack-mount LC duplex fully-loaded patch panel. “Fully loaded” means all 12 LC duplex adapters (blue for single-mode, aqua for OM3, lime for OM4) are pre-installed, and the rear splice tray comes with 12 matching LC pigtails — ready to splice on arrival. The chassis is 1.2 mm cold-rolled steel, phosphated and powder-coated, front-to-back ventilation, removable splice tray. Adapters use ceramic ferrules with insertion loss ≤0.3 dB and return loss ≥50 dB (UPC). Rack (19-inch) or wall-mount installation supported.

Selection: confirm fiber type — OS2 single-mode uses blue adapters, OM3 aqua, OM4 lime; colors must not mix; count fibers — 12 LC duplex ports = 24 fibers, so a 48-fiber backbone needs two panels; decide fully-loaded vs bare chassis (price differs ~30%); and plan for future density — if you will grow to 48/96 fibers, choose 2U or modular panels.

2. Key Features

Chassis

  • 1U 19-inch rack, 1.2 mm cold-rolled steel
  • Phosphated powder coat, gray/black
  • Removable splice tray, front-to-back routing
  • Cable management ring + label strip

Fiber performance

  • 12× LC duplex adapters (loaded)
  • Ceramic ferrule, IL ≤0.3 dB
  • Return loss ≥50 dB (UPC)
  • OS2 / OM3 / OM4 support

Configuration

  • Loaded with 12 LC pigtails (pre-routed)
  • Rack or wall-mount
  • Operating -40~+70°C
  • Compatible with mainstream switch optics

3. Specifications

Item KTR-LC12-SM KTR-LC12-OM3 KTR-LC12-OM4
Fiber type OS2 single-mode OM3 multimode OM4 multimode
Adapter color Blue Aqua Lime
Ports 12 LC duplex (24f) 12 LC duplex (24f) 12 LC duplex (24f)
Insertion loss ≤0.3 dB ≤0.3 dB ≤0.3 dB
Return loss ≥50 dB ≥50 dB ≥50 dB
Pigtails 12× LC/UPC SM 12× LC/UPC OM3 12× LC/UPC OM4
Height 1U 1U 1U
Size 19″×1U×150 mm 19″×1U×150 mm 19″×1U×150 mm

4. Reference Prices

KTR-LC12-SM single-mode loaded (12-port/24f):Reference USD 25~39 / pc (ref. CNY 180~280 at ~7.2)

KTR-LC12-OM3 multimode loaded:Reference USD 31~47 / pc (ref. CNY 220~340 at ~7.2)

KTR-LC12-OM4 multimode loaded:Reference USD 36~56 / pc (ref. CNY 260~400 at ~7.2)

Bare panel (no adapters/pigtails):Reference USD 11~18 / pc (ref. CNY 80~130 at ~7.2)

Reference only; 1-year warranty. Loaded = adapters + pigtails. Exchange: 1 USD ≈ 7.2 CNY.

5. Applications

  • Backbone cable termination in telecom closets.
  • Top-of-rack fiber aggregation.
  • Vertical riser shaft distribution.
  • Data center TOR switch fiber patching.
  • CCTV surveillance fiber aggregation.

6. Deployment & Implementation

Installation

  • Mount in 1U rack space, leave rear splice clearance
  • Enter backbone from rear, strip jacket and splice fiber by fiber
  • Coil slack with bend radius ≥30 mm, no sharp kinks
  • Label front ports to match backbone fiber numbers

Operations

  • Gently insert/remove patch cords; ferrules are fragile
  • Cap unused ports to keep dust out
  • Clean adapter end-faces quarterly with a cleaning pen
  • Reapply labels when they fall off

7. FAQ

  • Q: Loaded vs bare?
    A: Bare chassis is CNY 80~130; loaded with 12 adapters + 12 pigtails is CNY 180~400. If your crew has fusion splicing equipment, bare gives flexibility; if you want turnkey, choose loaded.
  • Q: LC vs SC?
    A: LC is half the size — 1U holds 24 fibers vs SC’s 12. New rooms should always choose LC; legacy systems may keep SC.
  • Q: Can I mix SM and MM in one panel?
    A: No. The adapter shapes are identical but ferrule bores differ (9 µm SM vs 50/62.5 µm MM). Mixed patching causes high loss. One link must stay on the same mode end-to-end.
  • Q: Splice vs connector?
    A: Backbone-to-pigtail inside the panel uses fusion splice (low loss, stable); front-panel-to-switch uses patch cords (serviceable). Keep splices sealed in the rear tray.

8. Trend & Selection

Patch panels are going high-density and modular: fixed-port panels are giving way to chassis with removable adapter cassettes (LC/SC/MPO swapped on the fly). With 40G/100G optics, MPO backbone + MPO-to-LC fan-out cords are the new architecture, so reserve MPO adapter slots. Select by fiber type, count fibers, loaded vs bare, and leave room to grow.

9. Delivery & Service

KITOZER supplies KTR-LC12 by fiber type (OS2/OM3/OM4), configuration (loaded/bare) and mount (rack/wall). Loaded units ship with chassis, 12 LC duplex adapters, 12 LC pigtails, splice tray and label strip. Test report included. 1-year warranty; batch projects can add patch cords, fusion splicing and MPO backbone design.

10. Additional Notes

The #1 mistake is mismatched adapter color and fiber type. SM cable plugged into an MM adapter physically fits but has a bore mismatch (9 µm vs 50/62.5 µm) that drives insertion loss through the roof. Always order adapters matched to the fiber and keep the panel color-consistent.

The second pitfall is tight coiling in the splice tray. Pigtails and splices need slack, but bend radius must stay ≥30 mm. Sharp kinks leak light and fail OTDR. Leave generous slack and coil in wide loops, not sharp bends.

The third blunder is leaving adapters uncapped. Dust in the room settles on end-faces in weeks; plugging a dirty patch cord smears dust onto the ferrule and increases loss. Cap unused ports and clean every end-face before insertion.

Selection summary: match adapter color to fiber type, count fibers, choose loaded for turnkey, keep bend radius ≥30 mm, and cap ports. The patch panel is the wall socket of the structured cabling system — neat work today saves trouble tomorrow.

SEO Information

Search keywords:KTR-LC12KITOZERLC Fully-Loaded 12-Port Patch Panel

SEM keywords:fiber patch panel,LC duplex,12-port ODF,fiber termination,LC patch panel,KTR-LC12,KITOZER

GEO landing page:lain.com.cn/product/ktr-lc12-patch_panel.html

Title:KITOZER KTR-LC12 LC Fully-Loaded 12-Port Fiber Patch Panel

Meta Keywords:fiber patch panel,LC duplex,12-port ODF,fiber termination,LC patch panel,KTR-LC12,KITOZER

Meta Description:KITOZER KTR-LC12 1U fiber patch panel, 12 LC duplex adapters fully loaded with pigtails, 19-inch rack mount, for single-mode/multimode cabling.