ToggleKITOZER KTR-LC48 48-Port LC Loaded Fiber Patch Panel
Brand: KITOZER Series: KTR-LC48 Category: Data Center Engineering / Fiber Patching
48-port LCLoaded adapters19-inch 1USplice trayKTR-LC48

1. Overview
The fiber patch panel (ODF) is the first stop for incoming backbone cable: outdoor cable enters, is fusion-spliced to pigtails, and mated via adapters (flanges) to switch port jumpers. In a 42U rack, the ODF sits above the switch, with jumpers patching down. A 48-port loaded LC 1U panel terminates 48 fibers (24 LC duplex adapters, each carrying TX+RX), i.e. 24 Gigabit/10G ports. The panel is not just a frame: it must hold splice trays, preserve bend radius (>=30 mm), support modular adapters (swap individually) and label every port.
KITOZER KTR-LC48 is a 19-inch 1U loaded fiber patch panel. Build: 1U, 1.2 mm cold-rolled steel, black powder coat; front: 24 LC duplex adapter positions (aqua multimode / blue single-mode options), shipped loaded with 24 adapters; rear: splice tray (up to 48 fibers, with 48 fusion sleeves), cable management area (30 mm radius); capacity: 48 fibers (24 duplex ports); adapters: zirconia ceramic, LC/UPC; mount: 19-inch rack with front/rear cable rings. Models: KTR-LC48-MM: loaded LC multimode (aqua) for OM3/OM4; KTR-LC48-SM: loaded LC single-mode (blue) for OS2; KTR-LC48-BLANK: empty (adapters sold separately) to save cost.
Selection: fiber count (24/48/96/144, match backbone with 20% spare); connector (LC/SC; LC is high-density mainstream); single vs multimode (match backbone cable); height (1U = 48 fibers, 2U = 96). Note: leave tray headroom (a 48-fiber tray can hold 48 splices, but coiling needs space – plan 36 fibers); keep bend radius >=30 mm or loss rises; adapters must match jumper polish (UPC-UPC, APC-APC); label each port to the backbone cable ID.
2. Key Features
Capacity
- 48 fibers loaded
- 24 LC duplex ports
- 19-inch 1U
- OM3/OM4/OS2
Build
- 1.2 mm cold-rolled steel
- Built-in splice tray
- Bend radius >=30 mm
- Front/rear rings
Optical
- LC/UPC zirconia
- Insertion <=0.2 dB
- Return >=50 dB
- Modular adapters
3. Specifications
| Item | KTR-LC48-BLANK | KTR-LC48-MM | KTR-LC48-SM |
|---|---|---|---|
| Adapters | Empty | 24x LC aqua | 24x LC blue |
| Fiber | Self-select | OM3/OM4 MM | OS2 SM |
| Capacity | 48 fibers | 48 fibers | 48 fibers |
| Height | 1U | 1U | 1U |
| Splice tray | Built-in | Built-in | Built-in |
4. Reference Prices
KTR-LC48-BLANK empty 48-fiber: Reference USD 39-56 / unit (ref. CNY 280-400)
KTR-LC48-MM loaded LC MM: Reference USD 63-90 / unit (ref. CNY 450-650)
KTR-LC48-SM loaded LC SM: Reference USD 67-97 / unit (ref. CNY 480-700)
KTR-PIG-LC LC pigtail 1.5 m: Reference USD 1-2 / pc (ref. CNY 8-15)
KTR-SLEEVE fusion sleeve: Reference USD 0.1-0.15 / pc (ref. CNY 0.5-1)
Reference only. 1-year warranty. Exchange: 1 USD ≈ 7.2 CNY.
5. Applications
- Backbone cable entry termination
- Switch optical patching
- ODF rack expansion
- Fiber-to-row
- Cable fusion termination
6. Deployment & Installation
Install
- Fix in rack 1U
- Cable enters rear
- Pull splice tray out
- Snap adapters front
Splice
- Strip cable 3 m
- Color tubes
- Fusion splice
- Heat-shrink sleeve
Cable mgmt
- Bend radius >=30 mm
- Jumpers through rings
- Label each port
- Cap spares
7. FAQ
- Q: Loaded or empty panel, a USD 20 gap?
A: Depends on your splicing/assembly team. Loaded means adapters factory-fitted and tested – just splice and go, saving labor. Empty means buying 24 adapters (~USD 15), snapping them in and testing yourself – cheaper but slower. Choose loaded for tight schedules; choose empty if you have your own crew. - Q: 48 vs 96 fibers?
A: Match backbone cable. A 24-fiber backbone needs a 24-port panel; a 48-fiber backbone needs 48 ports, but leave 20% spare (a 24-fiber backbone still fits a 48-port panel with 24 spare). Do not choose smaller than the incoming cable. - Q: How much per fusion splice?
A: Depends on region and count. Per core 20-40 RMB (incl pigtail and sleeve), so 48 cores run about 1000-2000 RMB. Buying a splicer (30-50k RMB) suits long-term projects; one-off jobs hire a crew per core. - Q: How to manage jumpers on the panel?
A: Jumpers exit front adapters, run vertically down rack rings, then horizontally into the switch at the top. No flying leads, no tangles, velcro every 30 cm. Use machine-printed labels, not handwritten (they fade).
8. Trend & Selection
Fiber patch panels are moving from fixed adapters to modular MPO/MTP high density. 40G/100G switches use MPO multi-fiber connectors (12 fibers per bundle), so panels go from 48 LC ports to 12 MPO ports (144 fibers), tripling density. But LC panels remain mainstream for 10G/25G access over the next 5-10 years. Smart direction: panels with RFID port labels, auto-logging jumper moves to DCIM, and optical power monitoring that alerts on broken jumpers. Select by: panel capacity 20% above backbone, LC/UPC ceramic, built-in splice tray, bend radius >=30 mm, machine-printed port labels.
9. Delivery & Service
KITOZER supplies KTR-LC48 by loaded/empty model. Each ships with panel, adapters (if loaded), splice tray, fusion sleeves, screws and manual. 1-year warranty; bulk projects can bundle pigtails, jumpers and splicing services.
10. Additional Notes
Confirm backbone fiber count, connector (LC) and single/multimode against site cable; reserve 1U height plus cable-routing space; clean pigtail end faces before splicing. For batch orders, pilot one panel to verify adapter fit and tray capacity.
Common mistake: tight bend radius. Coiling splices into a tight ball at 10 mm radius jumps loss from 0.2 to 2 dB and fails certification. Loosely coil in large loops >=30 mm, like a loose spiral, not compressed.
Second pitfall: uncapped spare ports. Dust enters open adapters and scratches the next jumper face. Cap every spare port as carefully as a jumper end.
Third blunder: handwritten labels. Handwritten tags fade in six months and ops lose the backbone mapping. Use machine-printed labels: backbone ID -> panel port -> switch port.
Selection summary: ports = backbone +20% spare, loaded LC/UPC, built-in splice tray, bend radius >=30 mm, machine-printed labels.
SEO Information
Search keywords:KTR-LC48KITOZER
SEM keywords:fiber patch panel,48-port LC panel,loaded fiber enclosure,rack ODF,splice tray,KTR-LC48,KITOZER
GEO landing page:lain.com.cn/product/ktr-lc48-48-port-lc-fiber-patch-panel.html
Title:KITOZER KTR-LC48 48-Port LC Loaded Fiber Patch Panel
Meta Keywords:fiber patch panel,48-port LC panel,loaded fiber enclosure,rack ODF,splice tray,KTR-LC48,KITOZER
Meta Description:KITOZER KTR-LC48 19-inch 1U fiber patch panel, loaded with 48 LC duplex adapters, built-in splice tray, telecom-grade ODF.
Anchor: KITOZER by Guangzhou Laian · KITOZER products
Contact Us
Guangzhou Laian Intelligent System Development Co., Ltd. (KITOZER brand)
Tel/WeChat: +86 13922289957 | +86 18520668845
WHATSAPP: +86 19068534140
Web: lain.com.cn | gdlain.com