KITOZER
KITOZER

KITOZER leak detection controller locate

KITOZER KTR-LD Leak Detection Location Controller

Brand: KITOZER Series: KTR-LD Category: Environmental Monitoring / Leak Detection

leak detectionlocation controllersensing cableRS485KTR-LD

KITOZER KTR-LD Leak Detection Location Controller

1. Overview

AC condensate pipes, chilled-water lines and humidifier hoses in a room — a single leak can flood racks within hours. Leak detection is the last line of defense: sensing cable runs along pipes and under AC units, alarming instantly and locating the leak so staff can shut the valve within minutes.

The KITOZER KTR-LD line comes in two types: locating (points to the leak within ±1 m) and non-locating (alarm only). Locating kits pair with sensing cable (cut by the meter) connected to the controller; point sensors sit under AC units and at pipe joints. The controller has an LCD, relay dry contacts for the environment system, RS485 to the platform, and audible/visual alarm.

Selection: locating vs non-locating (long runs need locating; small areas use point sensors); cable length by pipe route +2 m spare; output (RS485 to DCIM, relay for local alarm). Cable cannot be cut shorter than 1 m and must not run parallel to power cables.

2. Key Features

Detection & location

  • ±1 m location accuracy
  • Sensing cable up to 100 m
  • Point sensors in parallel
  • Response ≤3 s

Controller & output

  • LCD display
  • Relay dry contacts
  • RS485 Modbus-RTU
  • Audible/visual alarm

Mounting & reliability

  • Cable along pipes
  • Point sensors under AC
  • IP65 housing
  • DC12V/24V power

3. Specifications

Item KTR-LD-S1 KTR-LD-S2 KTR-LD-S3
型号 KTR-LD-P KTR-LD-L KTR-LD-LPRO
类型 点式报警 定位型 定位型+大屏
检测精度 只有/没有 ±1米定位 ±0.5米定位
感应绳长度 — 最长100米 最长200米
点式传感器 支持4路 支持8路 支持16路
输出 继电器 继电器+RS485 继电器+RS485+网口
显示 LED指示 LCD屏 LCD+声光
适用场景 小机房/单点 中等机房长管路 大型数据中心

4. Reference Prices

KTR-LD-P point leak alarm (4-channel):Reference USD 39~76 / pc (ref. CNY 280~550 at ~7.2)

KTR-LD-L locating controller (incl. 30 m cable):Reference USD 118~222 / pc (ref. CNY 850~1,600 at ~7.2)

KTR-LD-LPRO locating large-display controller (50 m cable + 16 points):Reference USD 250~445 / pc (ref. CNY 1,800~3,200 at ~7.2)

Reference only; final quote depends on location accuracy, cable length and channel count. 1-year warranty; volume pricing. Exchange: 1 USD ~ 7.2 CNY (Oct 2026).

5. Applications

  • Under-AC leak monitoring in data centers.
  • Chilled-water and condensate pipe runs.
  • Humidifier and water-treatment rooms.
  • Under-floor pipe and cable-tray leaks.
  • Warehouse and archive flood warning.

6. Deployment & Implementation

Installation

  • Run sensing cable along pipes and under AC
  • No knots or dead bends under floor tiles
  • Place point sensors at joints and AC pan
  • Wire RS485 + relay alarm to DCIM

Operations

  • Quarterly wipe-test with wet tissue
  • Clean cable with dry cloth — never wash
  • Check cable for aging/cracking yearly
  • On alarm: shut valve, dry up, then diagnose

7. FAQ

  • Q: Locating or not?
    A: Non-locating only says ‘leak’, staff then trace the pipe by hand. Locating shows ‘8.5 m from controller’ and pinpoints it in minutes. Choose locating for runs over ~10 m.
  • Q: Can the cable be cut?
    A: Yes, but not below 1 m; reconnect the cut end to the controller terminals. Do not splice multiple runs together — each run connects independently to preserve location accuracy.
  • Q: What about false alarms?
    A: Usually from moisture, dust or condensation on the cable. Keep it dry; wipe-test quarterly. Avoid routing it directly under the AC discharge where condensation forms.
  • Q: Redundant with temp/RH monitoring?
    A: No. Temp/RH reads the air; leak detection reads liquid. Water leakage is one of the biggest room risks — they complement each other.

8. Trend & Selection

Leak detection is moving from point alarms to ‘location + cloud monitoring’: longer sensing runs, higher accuracy and multi-zone switching. Integrated with DCIM, alarms trigger SMS, phone calls and APP push. Select locating for long runs, add 2 m spare cable, wipe-test quarterly, and link to DCIM.

9. Delivery & Service

KITOZER offers KTR-LD selection by type (point/locating), cable length (10~200 m) and point count, bundled with sensing cable, point sensors and mounting parts. Factory test report included. 1-year warranty; custom strobe in volume.

10. Additional Notes

The #1 mistake is running the cable directly under the AC discharge. Condensation forms on the cable and causes daily false alarms. Route it under the water pipe, away from direct airflow and condensation zones.

Another pitfall is installing and forgetting. When a real leak comes, the controller is already dead. Wipe-test quarterly to confirm the alarm chain works.

Sensing cable is not sealed; dust and oil degrade detection. Clean with a dry cloth — never wash. Inspect yearly and replace if cracked.

Selection summary: choose locating for long runs, add 2 m spare, avoid AC discharge, wipe-test quarterly, and link to DCIM for SMS/phone alerts. Leak detection is the last line — silent most days, but every alarm counts.

SEO Information

Search keywords:KTR-LDKITOZERLeak Detection Location Controller

SEM keywords:leak detection,leak location controller,water leak sensor,sensing cable,room leak monitor,KTR-LD,KITOZER

GEO landing page:lain.com.cn/product/ktr-ld-leak_detection.html

Title:KITOZER KTR-LD Leak Detection Location Controller

Meta Keywords:leak detection,leak location controller,water leak sensor,sensing cable,room leak monitor,KTR-LD,KITOZER

Meta Description:KITOZER KTR-LD leak detection location controller, ±1 m location accuracy, sensing cable/point sensors, RS485/relay output, LCD, for AC leak protection.

Anchor: KITOZER by Guangzhou Laian · Leak Detection Location Controller

Contact Us

Guangzhou Laian Intelligent System Development Co., Ltd. (KITOZER brand)
Tel/WeChat: +86 13922289957 | +86 18520668845
WHATSAPP: +86 19068534140
Web: lain.com.cn | gdlain.com

Shopping Cart