This guide describes grounding electrode installation for KITOZER lightning protection systems. Earth electrodes must be 50 x 50 x 5 mm galvanized steel angle or 14 mm copper-clad steel rod, driven to a depth of at least 2.5 m below finished grade. Spacing between electrodes must be at least twice the rod length to avoid mutual shielding. Connect electrodes to the main earth busbar with 95 mm2 copper cable, using exothermic welds or bolted clamps. After installation, measure earth resistance with a fall-of-potential tester; the target is below 1 ohm for data centers. If soil resistivity is high, use bentonite or chemical earth rods to reduce resistance.
Target
Depth 2.5 m, resistance under 1 ohm. Earth rods from $35 each.