The KITOZER LCC-40H is a 40-foot high-cube, single-phase immersion liquid-cooled computing shelter built for dense GPU and AI training workloads. IT hardware sits fully immersed in a high-boiling-point dielectric fluid, while a 200 kW coolant distribution unit (CDU) and an outdoor dry cooler reject heat directly to ambient air. The unit ships as one pre-integrated container: power, cooling, fire suppression, monitoring and network are factory-tested and ready to land on a prepared slab.
Table of Contents
ToggleAt a glance
- IT cooling capacity: 160 kW usable; CDU / dry-cooler rated 200 kW
- 4 x 42U immersion tanks (KITOZER LCC-T42), 304 stainless, ≥200 L each
- 10 x 2U immersed GPU servers (KITOZER LCC-GPU2U), 3.5 kW each, fanless
- Target power usage effectiveness: PUE ≤ 1.15
- Power: 200 kVA modular online UPS (N+X) + 512 V LFP battery bank
- Fire: FM200 gas suppression + CO2 hand units
- Enclosure: IP55, 50 mm rock-wool insulation, ≥1000 h salt-spray finish
- Monitoring: embedded DCIM host with 10-inch touchscreen, 4G uplink
How the cooling loop works
Servers drop straight into sealed stainless tanks filled with dielectric immersion fluid. Heat leaves the chips and transfers into the fluid, which is circulated by the secondary loop through plate heat exchangers inside the CDU. On the primary loop, water-glycol runs out to the dry cooler, where stepless EC fans hold the setpoint across seasons. Because the IT side is a closed dielectric circuit, there is no humidification, no raised floor, and no precision air-conditioner floorspace to engineer.
Dry-break quick couplings (KITOZER LCC-QC25) let a tank or server be swapped without draining the loop; Y-strainers, a refill tank, an expansion vessel and a water-softening feeder keep the primary side clean over years of operation.
Compute and network inside the tanks
Each 42U tank accepts up to ten 2U immersed nodes. The configured build carries 10 GPU servers — dual CPUs and 8 GPUs per node, each converted to a fanless immersion layout — giving roughly 35 kW of IT load distributed across four tanks. Top-of-rack 10G switches aggregate to a 40G/100G core, with OM3 fiber and Cat6a copper for out-of-band management.
Power chain and reliability
Utility enters a 400 A three-phase five-wire distribution panel (KITOZER PDC-400), feeds a 250 A busway, and lands on rack PDUs with per-outlet metering. The 200 kVA modular UPS runs online double conversion at ≥96% efficiency and supports N+X parallel expansion; the 512 V / 100 Ah LFP battery bank with BMS carries the bridge to generator. Three-stage surge protection and full equipotential bonding hold ground resistance at ≤4 ohm.
Fire suppression, security and DCIM
Two cabinet-type FM200 units protect the IT compartment, with rate-of-rise and fixed-temperature detectors, gas-release indicators, mechanical relief vents and manual abort switches. Video, door access and the environmental sensors — PT100 temperature, pressure, electromagnetic flow and tank-level probes — all report to the embedded monitoring host, which raises alarms locally and pushes them over the 4G gateway.
KITOZER Liquid-Cooled Computing Shelter Quotation
Complete single-container build as configured, priced in US dollars.
| # | Model | Specification | Qty | Unit | Unit Price (USD) | Amount (USD) |
|---|---|---|---|---|---|---|
| 1 | KITOZER-LCC-40H | Overall dims 12192x2438x2896 mm; weathering steel Q235B, outer panel 2.0 mm / inner panel 1.5 mm; protection IP55 | 1 | set | $15,833 | $15,833 |
| 2 | KITOZER-INS-50 | Rock wool, 50 mm thick, flame class B1, encapsulated with color steel plate inside and out | 1 | set | $5,000 | $5,000 |
| 3 | KITOZER-LCC-PW50 | 50 mm color-steel partition with sealed door frame; separates IT liquid-cooled zone from power/equipment zone | 1 | set | $3,542 | $3,542 |
| 4 | KITOZER-LCC-HD18 | Double-leaf 1800×2000 mm; sealing gasket, anti-theft lock | 1 | leaf | $2,833 | $2,833 |
| 5 | KITOZER-LCC-PD09 | Single-leaf 900×2100 mm; door closer, observation window | 1 | leaf | $1,333 | $1,333 |
| 6 | KITOZER-LCC-BASE | No.10 channel-steel welded frame, load >=1000 kg/m2, levelness <=2 mm/m | 1 | set | $3,958 | $3,958 |
| 7 | KITOZER-OUT-BASE | Channel-steel frame + precast concrete; matches dry-cooler footprint | 1 | set | $3,000 | $3,000 |
| 8 | KITOZER-LCC-AC1000 | Outdoor polyurethane finish, salt-spray resistance >=1000 h | 1 | set | $2,333 | $2,333 |
| 9 | KITOZER-LCC-T42 | 42U, single-tank volume >=200 L; 304 stainless steel; static load >=1500 kg; supports 19-inch immersed servers | 4 | unit | $21,667 | $86,668 |
| 10 | KITOZER-FLUID-75 | Dielectric strength >=10^14 ohm.cm, boiling point 47 C, working temp -40 C to 105 C, non-corrosive, no flash point | 800 | L | $283 | $226,400 |
| 11 | KITOZER-LCC-CDU200 | Heat rejection 200 kW; independent primary/secondary loops; 2 built-in pumps (1 duty, 1 standby); flow accuracy +/-2%; integrated temp/pressure/flow monitoring | 1 | unit | $77,083 | $77,083 |
| 12 | KITOZER-LCC-PIPE | 304 stainless steel DN50-DN80; welded, pressure-rated >=1.6 MPa | 1 | set | $11,667 | $11,667 |
| 13 | KITOZER-LCC-QC25 | Push-pull dry-break coupling DN25, 1.6 MPa | 8 | pair | $500 | $4,000 |
| 14 | KITOZER-LCC-T50 | 50 L, 304 stainless; level switch, refill port | 1 | pc | $1,583 | $1,583 |
| 15 | KITOZER-LCC-Y100 | 100 um strainer, 304 stainless | 2 | pc | $354 | $708 |
| 16 | KITOZER-LCC-DC200 | Total heat rejection 200 kW; full-load at 35 C dry-bulb; stepless EC fans; aluminum fins + copper-tube coil | 1 | unit | $68,750 | $68,750 |
| 17 | KITOZER-LCC-PUMP30 | Centrifugal 30 m3/h, head 28 m, 3 kW, IP55 | 2 | unit | $3,542 | $7,084 |
| 18 | KITOZER-LCC-HD80 | HDPE water pipe DN80, pressure >=1.0 MPa | 1 | set | $6,250 | $6,250 |
| 19 | KITOZER-LCC-EXP100 | 100 L carbon steel; automatic air vent, level gauge | 1 | pc | $917 | $917 |
| 20 | KITOZER-LCC-WS05 | Water softener 0.5 m3/h, outlet hardness <=0.03 mmol/L | 1 | set | $2,833 | $2,833 |
| 21 | KITOZER-LCC-GPU2U | Dual CPU + 8-GPU configuration, 3.5 kW per unit; fully immersed, fanless conversion | 10 | unit | $118,750 | $1,187,500 |
| 22 | KITOZER-NET-A10 | 24x10G SFP+ + 4x40G uplink; forwarding performance >=660 Mpps | 2 | unit | $7,000 | $14,000 |
| 23 | KITOZER-NET-C40 | 32x40G + 8x100G uplink; supports VRRP stacking | 1 | unit | $35,417 | $35,417 |
| 24 | KITOZER-LCC-RAIL | 19-inch standard, 304 stainless steel | 40 | pair | $133 | $5,320 |
| 25 | KITOZER-LCC-FJOM3 | OM3 multimode, LC-LC | 48 | pc | $19 | $912 |
| 26 | KITOZER-LCC-C6A | Cat6a, oxygen-free copper conductor | 20 | pc | $33 | $660 |
| 27 | KITOZER-LCC-CM1U | 19-inch cable-management unit, metal | 8 | pc | $50 | $400 |
| 28 | KITOZER-PDC-400 | 380 V 3-phase 5-wire input, 400 A; main breaker, branch MCBs, energy metering, Type-2 surge protection | 1 | unit | $11,667 | $11,667 |
| 29 | KITOZER-UPS-200 | 200 kVA online double-conversion; efficiency >=96%; N+X parallel expansion | 1 | unit | $32,500 | $32,500 |
| 30 | KITOZER-LFP-512 | 512 V DC system, 100 Ah; battery cabinet + BMS | 1 | bank | $35,417 | $35,417 |
| 31 | KITOZER-PDU-32A | 3-phase 32 A input; 12x C13 + 4x C19 outlets; per-outlet V/A/kW metering | 4 | unit | $1,333 | $5,332 |
| 32 | KITOZER-BUS-250 | 250 A busway, 3-phase 5-wire | 1 | set | $9,167 | $9,167 |
| 33 | KITOZER-LP-10 | 10-circuit lighting distribution; lighting + maintenance-socket branch protection | 1 | unit | $500 | $500 |
| 34 | KITOZER-LED-40 | 40 W white LED, IP44 | 6 | lamp | $75 | $450 |
| 35 | KITOZER-SOCK-10 | 10 A shuttered duplex socket | 4 | pc | $27 | $108 |
| 36 | KITOZER-GND-3 | 3-stage surge protection; equipotential bonding; ground resistance <=4 ohm | 1 | set | $5,000 | $5,000 |
| 37 | KITOZER-ENV-DH10 | Embedded Linux; integrates power, environment, liquid-cooling and fire systems; 10-inch touchscreen | 1 | unit | $3,542 | $3,542 |
| 38 | KITOZER-PT100 | PT100 RTD, -20 C to 100 C, accuracy +/-0.2 C | 12 | pc | $117 | $1,404 |
| 39 | KITOZER-PT16 | Pressure 0-1.6 MPa, accuracy 0.5% | 4 | pc | $188 | $752 |
| 40 | KITOZER-FL50 | Electromagnetic flowmeter 0-50 m3/h, accuracy +/-0.5% | 2 | pc | $1,333 | $2,666 |
| 41 | KITOZER-LV1M | Submersible level 0-1 m, accuracy +/-5 mm | 4 | pc | $200 | $800 |
| 42 | KITOZER-FIRE-SMOKE | Photoelectric smoke detector, adjustable sensitivity | 6 | pc | $92 | $552 |
| 43 | KITOZER-CCTV-AC | Fingerprint + password + card authentication; paired electromagnetic lock and exit button | 1 | set | $750 | $750 |
| 44 | KITOZER-CCTV-CAM | 4 MP, IR night vision, PoE | 4 | unit | $283 | $1,132 |
| 45 | KITOZER-ALARM-110 | Red strobe, sound pressure >=110 dB | 2 | pc | $242 | $484 |
| 46 | KITOZER-ENV-4G | 4G remote-platform uplink, store-and-forward on interruption | 1 | unit | $1,167 | $1,167 |
| 47 | KITOZER-FIRE-FM70 | 70 L cabinet FM200 unit, 42 kg charge, 8% extinguishing concentration, electric actuation | 2 | unit | $2,833 | $5,666 |
| 48 | KITOZER-FIRE-T70 | Fixed-temperature 70 C alarm | 6 | pc | $75 | $450 |
| 49 | KITOZER-FIRE-GASL | Steady red indicator with Gas Release – Do Not Enter sign | 2 | pc | $146 | $292 |
| 50 | KITOZER-FIRE-ES | Manual start/stop with protective cover | 2 | pc | $175 | $350 |
| 51 | KITOZER-FIRE-VT | 300×300 mm gravity relief vent | 2 | pc | $283 | $566 |
| 52 | KITOZER-FIRE-CO2 | 5 kg clean-agent hand-held extinguisher | 2 | extinguisher | $158 | $316 |
| 53 | KITOZER-LCC-FAN500 | Axial fan 500 m3/h, 100 Pa static pressure, IP55 | 2 | unit | $750 | $1,500 |
| 54 | KITOZER-LCC-LV30 | 300×300 mm rain louver with insect screen | 4 | pc | $35 | $140 |
| 55 | KITOZER-LCC-LABEL | Acrylic equipment labels showing name, tag number and parameters | 1 | set | $1,042 | $1,042 |
| 56 | KITOZER-LCC-DOC | Full drawing set, manuals, test reports, certificates and O&M handbook | 1 | set | $1,250 | $1,250 |
| Grand Total (KITOZER LCC-40H complete shelter) | $1,900,946 | |||||
Why choose immersion liquid cooling
- Higher density per footprint. Fanless immersed nodes remove the airflow ceiling, so a 40HQ container houses GPU loads that would otherwise need a much larger conventional hall.
- Lower overhead. Removing CRAH units, raised floors and humidification supports a PUE around 1.15 in the right climate.
- Quieter and cleaner. No rack fans means lower acoustic noise and no airborne dust load on sensitive electronics.
- Faster deployment. A factory-integrated shelter can be commissioned on a prepared slab in days rather than a multi-month build.
Related KITOZER products
Explore the wider family: containerized data centers (KITOZER CDC series), liquid-cooled energy storage (KITOZER LCS series), and precision air conditioning (KITOZER PAC series). For density planning, the LCC-40H pairs naturally with our outdoor integrated cabinets and environmental monitoring systems.
Keyword matrix
- Core keyword: immersion liquid-cooled data center container
- High-conversion long-tail: 160kW immersion liquid cooling GPU shelter price, 40HQ containerized liquid cooled data center cost, single-phase immersion cooling container for AI training
- Industry-traffic: liquid cooled data center, CDU coolant distribution unit, dry cooler PUE, immersion cooling GPU server, container data center
- Brand keyword: KITOZER LCC-40H, KITOZER liquid cooled computing shelter, Guangzhou Lain immersion cooling
- Suggested / related search: how does immersion cooling work, PUE of liquid cooled container, dielectric coolant data center, FM200 gas suppression for immersion tank
- SEM keyword: buy immersion cooling container, liquid cooled GPU container supplier China, containerized CDU 200kW
- GEO (AI-search) questions: “What PUE can an immersion liquid-cooled data center shelter achieve?” / “How much IT load can a 40HQ immersion-cooled container hold?” / “What is the difference between single-phase and two-phase immersion cooling?” / “How long does it take to deploy a containerized liquid-cooled data center?”
KITOZER by Guangzhou Lain Intelligent System Development Co., Ltd. | Tel/WeChat: +86 13922289957 / +86 18520668845 | WhatsApp: +86 19068534140 | Web: lain.com.cn, gdlain.com | Add: Zhongrun Industrial Park Chaotian Zone, No.5 Huashan Road, Shilou, Panyu, Guangzhou, China.