KITOZER
KITOZER

KITOZER 1.25MW 2.4MWh Liquid-Cooled ESS Container KITOZER-LCS-2400 BESS Price






KITOZER 1.25MW 2.4MWh Liquid-Cooled ESS Container KITOZER-LCS-2400 BESS Price






KITOZER 1.25MW / 2.4MWh Liquid-Cooled ESS Container KITOZER-LCS-2400: Grid-Scale BESS Price & Configuration

1.25MW PCS
2.4MWh LFP
Liquid Cooling
Cluster BMS
FK-5-1-12 Fire
Grid-Tied/Off-Grid
Peak-Valley Arbitrage

1. Overview

The KITOZER-LCS-2400 is a 20ft outdoor liquid-cooled battery energy storage system (BESS) container designed for commercial & industrial (C&I), substation-side and renewable-storage applications. Rated at 1.25 MW / 2.4 MWh and sized for 0.5C charge/discharge, the whole cabin is pre-assembled and pre-commissioned in the factory, so on-site work is limited to lifting, grid connection and commissioning.

The battery system uses prismatic LFP cells for high energy density and long cycle life. Liquid cooling keeps the cell-to-cell temperature spread within 3C, reducing high-temperature degradation versus conventional air cooling. The system supports both grid-tied and off-grid operation, enabling peak-valley arbitrage, demand management and backup power for critical loads.

KITOZER-LCS-2400 1.25MW 2.4MWh liquid-cooled ESS container exterior, outdoor LFP BESS prefab cabin, Guangzhou Lain

2. System Architecture

The cabin integrates six subsystems plus installation and commissioning services:

Subsystem Main Components
Battery Cabin System LFP cells, modules, cluster racks, cluster/system BMS, DC busbar cabinet, HV connection kit
PCS System 1.25MW bidirectional PCS, 10kV AC outgoing cabinet, PCS auxiliary control kit
Liquid-Cooled Thermal 30kW integrated cooling unit, module cold plates, pipe network, glycol coolant, PT100 sensors, thermal control cabinet
EMS EMS controller, 10-inch HMI, communication gateway, environment unit, web monitoring software
Fire & Safety FK-5-1-12 clean-agent suppression, multi-zone detection, fire linkage controller, emergency lighting, E-stop buttons
Enclosure & Auxiliaries 20ft ESS cabin, internal distribution, lightning/grounding, access security, ventilation, cable trays, labels

3. Battery System: LFP + Cluster-Level BMS

The KITOZER-LCS-CL280 prismatic aluminum-shell LFP cell is rated 3.2V / 280Ah, compliant with GB/T 36276-2018, with cycle life ≥6000 cycles at 80% SOH and energy density ≥160 Wh/kg. The cabin holds 2720 cells arranged into 136 twenty-series liquid-cooled modules (KITOZER-LCS-MD20S, 17.92 kWh each), tiered across 8 KITOZER-LCS-BR8 cluster racks.

BMS uses a master-slave architecture: each cluster has a KITOZER-LCS-BMS-S slave for per-cluster voltage/current/temperature acquisition, passive balancing and fault diagnosis (SOC accuracy ≤3%); one KITOZER-LCS-BMS-M master manages whole-cabinet SOC/SOH, insulation monitoring and HV interlock, and links to EMS/PCS over Modbus-TCP. The DC side converges in the KITOZER-LCS-DCB busbar cabinet with a 1250A main breaker and fuses.

KITOZER-LCS-2400 battery cluster racks and liquid cooling piping layout, LFP storage rack row, Guangzhou Lain

4. PCS: 1.25MW Four-Quadrant Conversion

The KITOZER-LCS-PCS1250 is a 1.25MW bidirectional DC-AC converter with a DC range of 700-1500V and rated AC 10kV, operating in four quadrants at ≥97.5% efficiency, with low-voltage ride-through and anti-islanding protection. The AC side connects to the grid through the KITOZER-PDC-AC10 10kV outgoing switchgear (vacuum breaker, CT, metering, microcomputer protection). A 380V low-voltage output option is available.

KITOZER-LCS-PCS1250 1.25MW power conversion system and 10kV AC outgoing cabinet, C&I BESS power stage, Guangzhou Lain

5. Liquid-Cooled Thermal: 30kW Unit, ≤3C Cell Spread

One KITOZER-LCS-CLU30 integrated liquid cooling unit provides 30kW of cooling with low-ambient heating down to -30C, glycol coolant, outdoor IP55 rating, inverter compressor and RS485. Every module mounts a KITOZER-LCS-CP280 brazed aluminum cold plate (thermal resistance ≤0.02 K/W, flow resistance ≤15 kPa).

Coolant circulates through DN50 stainless mains and DN25 branches with shut-off valves, a filter, expansion tank and vent valves. Forty PT100 RTDs monitor cell and coolant temperature; the KITOZER-PDC-TCC thermal cabinet automatically adjusts cooling/heating per BMS commands to keep the cell spread within 3C and extend cycle life.

6. EMS: Peak-Valley Arbitrage + Demand Management

The KITOZER-LCS-EMS industrial controller handles power dispatch, peak-valley arbitrage, demand response and operating-strategy setup, programmable under IEC 61131-3. The gateway supports Modbus-RTU/TCP, IEC104 and MQTT for grid dispatch and cloud platforms. The KITOZER-LCS-EMSSW web platform offers ≥1-year data storage, reporting, alarm push and history query, with mobile access.

  • Peak-valley arbitrage: charge at low-price hours, discharge at peak hours.
  • Demand management: discharge at load peaks to lower the maximum demand and demand charge.
  • Demand response: follow grid dispatch signals for demand-side response revenue.
  • Backup power: islanded operation supplies critical loads continuously.

KITOZER-LCS-EMS energy management control screen and peak-valley arbitrage strategy, storage O&S platform, Guangzhou Lain

7. Fire & Safety: FK-5-1-12 Clean Agent + Multi-Stage Detection

Fire protection uses the KITOZER-FIRE-30 perfluorohexanone (FK-5-1-12) clean-agent system with ≥30kg fill — residue-free, non-conductive and non-corrosive to battery and electrical equipment. The KITOZER-FIRE-DET assembly includes 4 smoke detectors, 4 heat detectors, 2 hydrogen combustible-gas detectors and 2 flame detectors for multi-parameter early warning of thermal runaway.

On alarm, the KITOZER-FIRE-CTRL linkage controller trips power off, triggers suppression and starts exhaust. Emergency stop/start buttons are fitted inside and outside, with emergency lighting and exit signs (≥90 min backup). The cabin also has an explosion-proof exhaust fan interlocked with combustible-gas detection.

8. Enclosure & Applications

The 20ft custom cabin measures 6058×2438×2896mm with C5-M outdoor anti-corrosion, 50mm rock-wool insulation and IP54 rating. Inside are lighting, maintenance sockets, auxiliary distribution, Class-II SPD grounding, fingerprint/password access and 2 IR night-vision cameras; ventilation is interlocked with the fire system, and power/signal cable trays are fire-segregated.

Typical applications: C&I peak-valley arbitrage and demand management, substation peak shaving/frequency regulation, PV/wind paired storage, charging-station peak shaving, and backup for data centers and critical facilities.

9. Key Specifications

Item Parameter
System rating 1.25 MW / 2.4 MWh, 0.5C charge/discharge
Battery type Prismatic LFP, 280Ah (314Ah optional)
Cell count 2720 pcs (280Ah option)
Modules / clusters 136 modules / 8 cluster racks
PCS 1.25MW bidirectional DC-AC, DC 700-1500V, AC 10kV, ≥97.5% efficiency
Cooling Liquid, 30kW integrated unit, cell spread ≤3C
BMS Master-slave, cluster slave + system master, SOC accuracy ≤3%
Fire suppression FK-5-1-12 clean agent, ≥30kg, multi-zone detection + linkage
EMS Power dispatch / arbitrage / demand response, Modbus/IEC104/MQTT
Cabinet size 6058×2438×2896mm (20ft), C5-M, IP54
Coolant -35C ethylene-glycol
Warranty 5-year system warranty (cell cycle terms per commercial contract)

10. KITOZER Price List (USD, excl. tax)

No. Model Name Spec Summary Qty Unit Unit Price (USD) Amount (USD)
1. Battery Cabin System (incl. BMS)
1 KITOZER-LCS-CL280 LFP Battery Cell 3.2V 280Ah prismatic LFP cell per GB/T 36276-2018; cycle life >=6000 cycles at 80% SOH; energy density >=160 Wh/kg; 314Ah optional (qty becomes 2380) 2720 pc 153 416,160
2 KITOZER-LCS-MD20S Battery Module 20s280Ah liquid-cooled module with integrated aluminum cold plate, insulation and sensing harness; 17.92 kWh per module; about 64 V nominal 136 module 556 75,616
3 KITOZER-LCS-BR8 Battery Cluster Rack High-strength anti-corrosion steel rack, powder-coated, tiered layout to suit coolant piping; load capacity >=1500 kg per rack 8 rack 1,333 10,664
4 KITOZER-LCS-BMS-S Cluster BMS Slave Unit Per-cluster voltage/current/temperature acquisition, passive balancing, fault diagnosis, SOC accuracy <=3%, CAN communication 8 set 1,167 9,336
5 KITOZER-LCS-BMS-M System BMS Master Unit Whole-cabinet battery management, SOC/SOH estimation, insulation monitoring, HV interlock, Modbus-TCP link to EMS/PCS 1 set 6,875 6,875
6 KITOZER-LCS-DCB DC Busbar Cabinet DC-side main busbar; 1250A main breaker, fuses, insulation monitoring; IP54 1 cabinet 5,625 5,625
7 KITOZER-LCS-HVK HV Connection Kit Power busbar (TMY-4x40x4), power cable (YJV-1x95mm2), insulating boots and terminals 1 set 3,833 3,833
2. PCS Power Conversion System
8 KITOZER-LCS-PCS1250 Power Conversion System (PCS) 1.25MW bidirectional DC-AC; DC 700-1500 V; AC rated 10 kV; grid-tied four-quadrant; efficiency >=97.5%; LV ride-through and anti-islanding; 380V low-voltage output optional 1 unit 89,583 89,583
9 KITOZER-PDC-AC10 AC Outgoing Cabinet 10 kV switchgear with vacuum breaker, current transformer, metering unit and microcomputer protection relay 1 cabinet 11,667 11,667
10 KITOZER-LCS-PCSA PCS Auxiliary Control Kit Shielded twisted-pair comm cable, DC24V control circuit, grounding kit (busbar + ground wire) 1 set 1,458 1,458
3. Liquid-Cooled Thermal Management
11 KITOZER-LCS-CLU30 Integrated Liquid Cooling Unit 30 kW cooling capacity; low-ambient heating down to -30C; glycol coolant; outdoor IP55; inverter compressor; RS485 1 unit 17,500 17,500
12 KITOZER-LCS-CP280 Module Cold Plate Brazed aluminum cold plate for 280Ah modules; thermal resistance <=0.02 K/W; flow resistance <=15 kPa 136 plate 69 9,384
13 KITOZER-LCS-PIPE Cooling Pipe Network DN50 stainless main piping, DN25 branches, shut-off valves, filter, expansion tank, vent valves 1 set 5,625 5,625
14 KITOZER-LCS-CLG Antifreeze Coolant -35C ethylene-glycol coolant per GB/T 25146 200 kg 14 2,800
15 KITOZER-LCS-PT100 Temperature Sensor PT100 platinum RTD, Class A, for cell/coolant temperature, 3-wire 40 pc 42 1,680
16 KITOZER-PDC-TCC Thermal Control Cabinet Standalone thermal control logic, automatic cooling/heating, linked with BMS/EMS, 7-inch touchscreen 1 set 3,750 3,750
4. EMS Energy Management System
17 KITOZER-LCS-EMS EMS Energy Management Controller Industrial controller for power dispatch, peak-valley arbitrage, demand response and strategy setup; IEC 61131-3 programmable 1 set 14,583 14,583
18 KITOZER-LCS-HMI10 Local HMI Touchscreen 10-inch industrial touchscreen, 1280×800; local data display, parameter setup, alarm query 1 unit 1,458 1,458
19 KITOZER-LCS-COM Communication Gateway Modbus-RTU/TCP, IEC104, MQTT; links grid dispatch and cloud platform; 4x RS485 + 2x Ethernet 1 unit 1,875 1,875
20 KITOZER-LCS-ENV Environment Acquisition Unit Cabinet temperature/humidity, door status, water leak acquisition; DI/DO/AI interfaces 1 set 1,167 1,167
21 KITOZER-LCS-EMSSW Monitoring Software Web remote monitoring platform with >=1 year data storage, reports, alarm push, history query, mobile access; 1-year license included 1 set 7,500 7,500
5. Fire & Safety Protection
22 KITOZER-FIRE-30 FK-5-1-12 Clean-Agent Fire Suppression FK-5-1-12 (perfluorohexanone) pre-engineered clean-agent system, >=30 kg fill, matched to cabinet volume; includes cylinders, piping, nozzles 1 set 9,167 9,167
23 KITOZER-FIRE-DET Fire Detection Assembly 4 smoke detectors, 4 heat detectors, 2 hydrogen combustible-gas detectors, 2 flame detectors 1 set 2,292 2,292
24 KITOZER-FIRE-CTRL Fire Linkage Controller Receives fire signals, trips power off, triggers suppression and exhaust; dry-contact outputs 1 unit 1,875 1,875
25 KITOZER-FIRE-EML Emergency Lighting & Exit Signs Emergency lights and exit signs; >=90 min battery backup; LED 1 set 750 750
26 KITOZER-FIRE-EPB Emergency Stop/Start Button One set inside and one outside; manual suppression control with protective cover 2 set 111 222
6. Container Enclosure & Auxiliaries
27 KITOZER-LCS-2400 ESS Container Enclosure Custom 20ft enclosure, 6058x2438x2896 mm; C5-M outdoor anti-corrosion; 50mm rock-wool insulation; IP54 1 unit 21,667 21,667
28 KITOZER-PDC-DIST Internal Distribution System Lighting circuits, maintenance sockets, auxiliary power distribution with breakers and box 1 set 1,458 1,458
29 KITOZER-PDC-SPD Lightning & Grounding System Class II SPD, grounding busbar (30x3mm), ground lead (BVR-50mm2) 1 set 1,167 1,167
30 KITOZER-LCS-SEC Access & Security System Fingerprint/password access; 2x 2MP IR night-vision network cameras inside 1 set 1,875 1,875
31 KITOZER-LCS-VENT Ventilation & Exhaust System Explosion-proof exhaust fan (>=1200 m3/h), filtered intake louvers, linked to fire system 1 set 917 917
32 KITOZER-LCS-TRAY Cable Tray System Power and signal cable trays with fire separation; hot-dip galvanized 1 set 1,583 1,583
33 KITOZER-LCS-LABEL Equipment Labeling & Safety Signs Equipment tags and reflective safety warning signs 1 set 500 500
7. Installation, Commissioning & Service
34 KITOZER-SVC-LOG Freight & Logistics Road freight from factory to site, including loading/unloading and insurance; 20ft container truckload 1 lot 7,500 7,500
35 KITOZER-SVC-INST On-Site Installation Equipment positioning, electrical wiring, piping connection, grounding, labeling 1 lot 11,667 11,667
36 KITOZER-SVC-COMM System Commissioning Single-unit test, integrated commissioning, grid-connection test, functional verification 1 lot 9,167 9,167
37 KITOZER-SVC-TECH Technical Service Technical briefing, on-site training, acceptance support 1 lot 2,500 2,500
— — KITOZER Quote Total (excl. tax) 37 line items — — — USD 772,446

11. Notes

  • Prices are ex-works excluding tax; a 13% VAT special invoice applies domestically, or 6% ordinary invoice.
  • Quote includes road freight to site, on-site installation, system commissioning and technical service; it excludes civil foundations, grid-connection approval and external line works.
  • 314Ah cells are optional; cluster count and capacity adjust accordingly, with price recalculated.
  • Delivery: within 30 working days after contract signing, subject to commercial agreement.
  • 5-year system warranty; cell cycle-life warranty terms to be confirmed in the formal contract.
  • Adjustments to quantity, PCS voltage, cell capacity or site connection conditions will adjust the quote.


Shopping Cart