Table of Contents
ToggleKITOZER 1.25MW / 2.4MWh Liquid-Cooled ESS Container KITOZER-LCS-2400: Grid-Scale BESS Price & Configuration
1.25MW PCS
2.4MWh LFP
Liquid Cooling
Cluster BMS
FK-5-1-12 Fire
Grid-Tied/Off-Grid
Peak-Valley Arbitrage
1. Overview
The KITOZER-LCS-2400 is a 20ft outdoor liquid-cooled battery energy storage system (BESS) container designed for commercial & industrial (C&I), substation-side and renewable-storage applications. Rated at 1.25 MW / 2.4 MWh and sized for 0.5C charge/discharge, the whole cabin is pre-assembled and pre-commissioned in the factory, so on-site work is limited to lifting, grid connection and commissioning.
The battery system uses prismatic LFP cells for high energy density and long cycle life. Liquid cooling keeps the cell-to-cell temperature spread within 3C, reducing high-temperature degradation versus conventional air cooling. The system supports both grid-tied and off-grid operation, enabling peak-valley arbitrage, demand management and backup power for critical loads.

2. System Architecture
The cabin integrates six subsystems plus installation and commissioning services:
| Subsystem | Main Components |
|---|---|
| Battery Cabin System | LFP cells, modules, cluster racks, cluster/system BMS, DC busbar cabinet, HV connection kit |
| PCS System | 1.25MW bidirectional PCS, 10kV AC outgoing cabinet, PCS auxiliary control kit |
| Liquid-Cooled Thermal | 30kW integrated cooling unit, module cold plates, pipe network, glycol coolant, PT100 sensors, thermal control cabinet |
| EMS | EMS controller, 10-inch HMI, communication gateway, environment unit, web monitoring software |
| Fire & Safety | FK-5-1-12 clean-agent suppression, multi-zone detection, fire linkage controller, emergency lighting, E-stop buttons |
| Enclosure & Auxiliaries | 20ft ESS cabin, internal distribution, lightning/grounding, access security, ventilation, cable trays, labels |
3. Battery System: LFP + Cluster-Level BMS
The KITOZER-LCS-CL280 prismatic aluminum-shell LFP cell is rated 3.2V / 280Ah, compliant with GB/T 36276-2018, with cycle life ≥6000 cycles at 80% SOH and energy density ≥160 Wh/kg. The cabin holds 2720 cells arranged into 136 twenty-series liquid-cooled modules (KITOZER-LCS-MD20S, 17.92 kWh each), tiered across 8 KITOZER-LCS-BR8 cluster racks.
BMS uses a master-slave architecture: each cluster has a KITOZER-LCS-BMS-S slave for per-cluster voltage/current/temperature acquisition, passive balancing and fault diagnosis (SOC accuracy ≤3%); one KITOZER-LCS-BMS-M master manages whole-cabinet SOC/SOH, insulation monitoring and HV interlock, and links to EMS/PCS over Modbus-TCP. The DC side converges in the KITOZER-LCS-DCB busbar cabinet with a 1250A main breaker and fuses.

4. PCS: 1.25MW Four-Quadrant Conversion
The KITOZER-LCS-PCS1250 is a 1.25MW bidirectional DC-AC converter with a DC range of 700-1500V and rated AC 10kV, operating in four quadrants at ≥97.5% efficiency, with low-voltage ride-through and anti-islanding protection. The AC side connects to the grid through the KITOZER-PDC-AC10 10kV outgoing switchgear (vacuum breaker, CT, metering, microcomputer protection). A 380V low-voltage output option is available.

5. Liquid-Cooled Thermal: 30kW Unit, ≤3C Cell Spread
One KITOZER-LCS-CLU30 integrated liquid cooling unit provides 30kW of cooling with low-ambient heating down to -30C, glycol coolant, outdoor IP55 rating, inverter compressor and RS485. Every module mounts a KITOZER-LCS-CP280 brazed aluminum cold plate (thermal resistance ≤0.02 K/W, flow resistance ≤15 kPa).
Coolant circulates through DN50 stainless mains and DN25 branches with shut-off valves, a filter, expansion tank and vent valves. Forty PT100 RTDs monitor cell and coolant temperature; the KITOZER-PDC-TCC thermal cabinet automatically adjusts cooling/heating per BMS commands to keep the cell spread within 3C and extend cycle life.
6. EMS: Peak-Valley Arbitrage + Demand Management
The KITOZER-LCS-EMS industrial controller handles power dispatch, peak-valley arbitrage, demand response and operating-strategy setup, programmable under IEC 61131-3. The gateway supports Modbus-RTU/TCP, IEC104 and MQTT for grid dispatch and cloud platforms. The KITOZER-LCS-EMSSW web platform offers ≥1-year data storage, reporting, alarm push and history query, with mobile access.
- Peak-valley arbitrage: charge at low-price hours, discharge at peak hours.
- Demand management: discharge at load peaks to lower the maximum demand and demand charge.
- Demand response: follow grid dispatch signals for demand-side response revenue.
- Backup power: islanded operation supplies critical loads continuously.

7. Fire & Safety: FK-5-1-12 Clean Agent + Multi-Stage Detection
Fire protection uses the KITOZER-FIRE-30 perfluorohexanone (FK-5-1-12) clean-agent system with ≥30kg fill — residue-free, non-conductive and non-corrosive to battery and electrical equipment. The KITOZER-FIRE-DET assembly includes 4 smoke detectors, 4 heat detectors, 2 hydrogen combustible-gas detectors and 2 flame detectors for multi-parameter early warning of thermal runaway.
On alarm, the KITOZER-FIRE-CTRL linkage controller trips power off, triggers suppression and starts exhaust. Emergency stop/start buttons are fitted inside and outside, with emergency lighting and exit signs (≥90 min backup). The cabin also has an explosion-proof exhaust fan interlocked with combustible-gas detection.
8. Enclosure & Applications
The 20ft custom cabin measures 6058×2438×2896mm with C5-M outdoor anti-corrosion, 50mm rock-wool insulation and IP54 rating. Inside are lighting, maintenance sockets, auxiliary distribution, Class-II SPD grounding, fingerprint/password access and 2 IR night-vision cameras; ventilation is interlocked with the fire system, and power/signal cable trays are fire-segregated.
Typical applications: C&I peak-valley arbitrage and demand management, substation peak shaving/frequency regulation, PV/wind paired storage, charging-station peak shaving, and backup for data centers and critical facilities.
9. Key Specifications
| Item | Parameter |
|---|---|
| System rating | 1.25 MW / 2.4 MWh, 0.5C charge/discharge |
| Battery type | Prismatic LFP, 280Ah (314Ah optional) |
| Cell count | 2720 pcs (280Ah option) |
| Modules / clusters | 136 modules / 8 cluster racks |
| PCS | 1.25MW bidirectional DC-AC, DC 700-1500V, AC 10kV, ≥97.5% efficiency |
| Cooling | Liquid, 30kW integrated unit, cell spread ≤3C |
| BMS | Master-slave, cluster slave + system master, SOC accuracy ≤3% |
| Fire suppression | FK-5-1-12 clean agent, ≥30kg, multi-zone detection + linkage |
| EMS | Power dispatch / arbitrage / demand response, Modbus/IEC104/MQTT |
| Cabinet size | 6058×2438×2896mm (20ft), C5-M, IP54 |
| Coolant | -35C ethylene-glycol |
| Warranty | 5-year system warranty (cell cycle terms per commercial contract) |
10. KITOZER Price List (USD, excl. tax)
| No. | Model | Name | Spec Summary | Qty | Unit | Unit Price (USD) | Amount (USD) |
|---|---|---|---|---|---|---|---|
| 1. Battery Cabin System (incl. BMS) | |||||||
| 1 | KITOZER-LCS-CL280 | LFP Battery Cell | 3.2V 280Ah prismatic LFP cell per GB/T 36276-2018; cycle life >=6000 cycles at 80% SOH; energy density >=160 Wh/kg; 314Ah optional (qty becomes 2380) | 2720 | pc | 153 | 416,160 |
| 2 | KITOZER-LCS-MD20S | Battery Module | 20s280Ah liquid-cooled module with integrated aluminum cold plate, insulation and sensing harness; 17.92 kWh per module; about 64 V nominal | 136 | module | 556 | 75,616 |
| 3 | KITOZER-LCS-BR8 | Battery Cluster Rack | High-strength anti-corrosion steel rack, powder-coated, tiered layout to suit coolant piping; load capacity >=1500 kg per rack | 8 | rack | 1,333 | 10,664 |
| 4 | KITOZER-LCS-BMS-S | Cluster BMS Slave Unit | Per-cluster voltage/current/temperature acquisition, passive balancing, fault diagnosis, SOC accuracy <=3%, CAN communication | 8 | set | 1,167 | 9,336 |
| 5 | KITOZER-LCS-BMS-M | System BMS Master Unit | Whole-cabinet battery management, SOC/SOH estimation, insulation monitoring, HV interlock, Modbus-TCP link to EMS/PCS | 1 | set | 6,875 | 6,875 |
| 6 | KITOZER-LCS-DCB | DC Busbar Cabinet | DC-side main busbar; 1250A main breaker, fuses, insulation monitoring; IP54 | 1 | cabinet | 5,625 | 5,625 |
| 7 | KITOZER-LCS-HVK | HV Connection Kit | Power busbar (TMY-4x40x4), power cable (YJV-1x95mm2), insulating boots and terminals | 1 | set | 3,833 | 3,833 |
| 2. PCS Power Conversion System | |||||||
| 8 | KITOZER-LCS-PCS1250 | Power Conversion System (PCS) | 1.25MW bidirectional DC-AC; DC 700-1500 V; AC rated 10 kV; grid-tied four-quadrant; efficiency >=97.5%; LV ride-through and anti-islanding; 380V low-voltage output optional | 1 | unit | 89,583 | 89,583 |
| 9 | KITOZER-PDC-AC10 | AC Outgoing Cabinet | 10 kV switchgear with vacuum breaker, current transformer, metering unit and microcomputer protection relay | 1 | cabinet | 11,667 | 11,667 |
| 10 | KITOZER-LCS-PCSA | PCS Auxiliary Control Kit | Shielded twisted-pair comm cable, DC24V control circuit, grounding kit (busbar + ground wire) | 1 | set | 1,458 | 1,458 |
| 3. Liquid-Cooled Thermal Management | |||||||
| 11 | KITOZER-LCS-CLU30 | Integrated Liquid Cooling Unit | 30 kW cooling capacity; low-ambient heating down to -30C; glycol coolant; outdoor IP55; inverter compressor; RS485 | 1 | unit | 17,500 | 17,500 |
| 12 | KITOZER-LCS-CP280 | Module Cold Plate | Brazed aluminum cold plate for 280Ah modules; thermal resistance <=0.02 K/W; flow resistance <=15 kPa | 136 | plate | 69 | 9,384 |
| 13 | KITOZER-LCS-PIPE | Cooling Pipe Network | DN50 stainless main piping, DN25 branches, shut-off valves, filter, expansion tank, vent valves | 1 | set | 5,625 | 5,625 |
| 14 | KITOZER-LCS-CLG | Antifreeze Coolant | -35C ethylene-glycol coolant per GB/T 25146 | 200 | kg | 14 | 2,800 |
| 15 | KITOZER-LCS-PT100 | Temperature Sensor | PT100 platinum RTD, Class A, for cell/coolant temperature, 3-wire | 40 | pc | 42 | 1,680 |
| 16 | KITOZER-PDC-TCC | Thermal Control Cabinet | Standalone thermal control logic, automatic cooling/heating, linked with BMS/EMS, 7-inch touchscreen | 1 | set | 3,750 | 3,750 |
| 4. EMS Energy Management System | |||||||
| 17 | KITOZER-LCS-EMS | EMS Energy Management Controller | Industrial controller for power dispatch, peak-valley arbitrage, demand response and strategy setup; IEC 61131-3 programmable | 1 | set | 14,583 | 14,583 |
| 18 | KITOZER-LCS-HMI10 | Local HMI Touchscreen | 10-inch industrial touchscreen, 1280×800; local data display, parameter setup, alarm query | 1 | unit | 1,458 | 1,458 |
| 19 | KITOZER-LCS-COM | Communication Gateway | Modbus-RTU/TCP, IEC104, MQTT; links grid dispatch and cloud platform; 4x RS485 + 2x Ethernet | 1 | unit | 1,875 | 1,875 |
| 20 | KITOZER-LCS-ENV | Environment Acquisition Unit | Cabinet temperature/humidity, door status, water leak acquisition; DI/DO/AI interfaces | 1 | set | 1,167 | 1,167 |
| 21 | KITOZER-LCS-EMSSW | Monitoring Software | Web remote monitoring platform with >=1 year data storage, reports, alarm push, history query, mobile access; 1-year license included | 1 | set | 7,500 | 7,500 |
| 5. Fire & Safety Protection | |||||||
| 22 | KITOZER-FIRE-30 | FK-5-1-12 Clean-Agent Fire Suppression | FK-5-1-12 (perfluorohexanone) pre-engineered clean-agent system, >=30 kg fill, matched to cabinet volume; includes cylinders, piping, nozzles | 1 | set | 9,167 | 9,167 |
| 23 | KITOZER-FIRE-DET | Fire Detection Assembly | 4 smoke detectors, 4 heat detectors, 2 hydrogen combustible-gas detectors, 2 flame detectors | 1 | set | 2,292 | 2,292 |
| 24 | KITOZER-FIRE-CTRL | Fire Linkage Controller | Receives fire signals, trips power off, triggers suppression and exhaust; dry-contact outputs | 1 | unit | 1,875 | 1,875 |
| 25 | KITOZER-FIRE-EML | Emergency Lighting & Exit Signs | Emergency lights and exit signs; >=90 min battery backup; LED | 1 | set | 750 | 750 |
| 26 | KITOZER-FIRE-EPB | Emergency Stop/Start Button | One set inside and one outside; manual suppression control with protective cover | 2 | set | 111 | 222 |
| 6. Container Enclosure & Auxiliaries | |||||||
| 27 | KITOZER-LCS-2400 | ESS Container Enclosure | Custom 20ft enclosure, 6058x2438x2896 mm; C5-M outdoor anti-corrosion; 50mm rock-wool insulation; IP54 | 1 | unit | 21,667 | 21,667 |
| 28 | KITOZER-PDC-DIST | Internal Distribution System | Lighting circuits, maintenance sockets, auxiliary power distribution with breakers and box | 1 | set | 1,458 | 1,458 |
| 29 | KITOZER-PDC-SPD | Lightning & Grounding System | Class II SPD, grounding busbar (30x3mm), ground lead (BVR-50mm2) | 1 | set | 1,167 | 1,167 |
| 30 | KITOZER-LCS-SEC | Access & Security System | Fingerprint/password access; 2x 2MP IR night-vision network cameras inside | 1 | set | 1,875 | 1,875 |
| 31 | KITOZER-LCS-VENT | Ventilation & Exhaust System | Explosion-proof exhaust fan (>=1200 m3/h), filtered intake louvers, linked to fire system | 1 | set | 917 | 917 |
| 32 | KITOZER-LCS-TRAY | Cable Tray System | Power and signal cable trays with fire separation; hot-dip galvanized | 1 | set | 1,583 | 1,583 |
| 33 | KITOZER-LCS-LABEL | Equipment Labeling & Safety Signs | Equipment tags and reflective safety warning signs | 1 | set | 500 | 500 |
| 7. Installation, Commissioning & Service | |||||||
| 34 | KITOZER-SVC-LOG | Freight & Logistics | Road freight from factory to site, including loading/unloading and insurance; 20ft container truckload | 1 | lot | 7,500 | 7,500 |
| 35 | KITOZER-SVC-INST | On-Site Installation | Equipment positioning, electrical wiring, piping connection, grounding, labeling | 1 | lot | 11,667 | 11,667 |
| 36 | KITOZER-SVC-COMM | System Commissioning | Single-unit test, integrated commissioning, grid-connection test, functional verification | 1 | lot | 9,167 | 9,167 |
| 37 | KITOZER-SVC-TECH | Technical Service | Technical briefing, on-site training, acceptance support | 1 | lot | 2,500 | 2,500 |
| — | — | KITOZER Quote Total (excl. tax) | 37 line items | — | — | — | USD 772,446 |
11. Notes
- Prices are ex-works excluding tax; a 13% VAT special invoice applies domestically, or 6% ordinary invoice.
- Quote includes road freight to site, on-site installation, system commissioning and technical service; it excludes civil foundations, grid-connection approval and external line works.
- 314Ah cells are optional; cluster count and capacity adjust accordingly, with price recalculated.
- Delivery: within 30 working days after contract signing, subject to commercial agreement.
- 5-year system warranty; cell cycle-life warranty terms to be confirmed in the formal contract.
- Adjustments to quantity, PCS voltage, cell capacity or site connection conditions will adjust the quote.
KITOZER by Guangzhou Lain Intelligent System Development Co., Ltd. | Tel/WeChat: +86 13922289957 / +86 18520668845 | WhatsApp: +86 19068534140 | Web: lain.com.cn, gdlain.com | Add: Zhongrun Industrial Park Chaotian Zone, No.5 Huashan Road, Shilou, Panyu, Guangzhou, China.