Toggle1. System Overview
The KITOZER liquid cooling integrated cabinet is a core equipment for high-density and high-efficiency fully integrated computer rooms independently developed by Guangzhou Laian Intelligent System Development Co., Ltd. It integrates liquid cooling heat dissipation technology, intelligent power distribution, environmental monitoring, access control security, fire linkage and integrated wiring. It is designed to address the heat dissipation bottleneck of traditional air cooling under high-density computing power scenarios.
Each cabinet acts as an independent thermal management unit. Leveraging the high specific heat capacity and thermal conductivity of liquid working fluid, it accurately dissipates heat from high-power components such as CPUs and GPUs through cold plate / immersion heat exchange assemblies. Combined with CDU Cooling Distribution Units and an intelligent control system, it realizes efficient cyclic heat export and intelligent system management.
The product features outstanding advantages including high heat dissipation efficiency, low PUE, low noise, high integration, easy deployment and simple maintenance. It completely breaks the single cabinet power density limit of 30kW imposed by traditional air cooling, supporting ultra-high power density deployment of 33–80kW per rack. The overall cabinet PUE can be as low as 1.05–1.1, saving 40%–70% more energy than air cooling systems, with operating noise ≤55dB(A). It is applicable to various high-density computer room construction scenarios including government, finance, telecom operators, AI computing, supercomputing centers, edge computing, power communications, medical care and education, serving as core infrastructure for new-generation green data centers.

KITOZER Liquid Cooling Cabinet On-site Photo
2. System Composition
The KITOZER liquid cooling integrated cabinet consists of ten core modules with high integration and coordinated operation, forming a complete closed-loop system:
- Cabinet Frame Module Constructed with high-strength cold-rolled steel plate / 304 stainless steel with thickness ≥2.0mm, electrostatically sprayed for anti-corrosion and rust resistance, IP54 protection grade. Dimensions: 600×1200×2200mm (W × D × H), with 47U usable space, compatible with standard 19/21-inch IT equipment. Equipped with hexahedral EMC shielding design, meeting GB/T12190 Class A shielding standards.
- Liquid Cooling Heat Dissipation Module Includes cold plate / immersion heat exchange assemblies, CDU cooling distribution unit, manifold, blind-mate quick connectors, sealed pipeline system, circulating pump set, coolant storage tank and plate heat exchanger. Cold plates adopt pure copper core plus aluminum alloy frame to closely fit CPU/GPU surfaces for precise heat dissipation. CDUs regulate coolant temperature, flow and pressure with temperature control accuracy of ±1℃. Pipelines are made of 304 stainless steel with pressure resistance ≥1.6MPa, equipped with drip-proof quick connectors and water collecting trays for zero leakage design.
- Intelligent Power Distribution Module Integrated UPS / high-frequency switching power supply, DC48V busbar, high-density PDU, lightning arrester, air switch and electric energy monitoring meter. Supports redundant power supply via dual mains + UPS. DC48V power supply improves efficiency by 5% compared with traditional 12V solutions. PDUs have a maximum output power of 60kW with remote switching, voltage/current monitoring and overload protection functions.
- Environmental Monitoring Module Deployed with temperature, humidity, pressure, flow, liquid leakage, smoke, water immersion, door contact and infrared sensors. Real-time monitoring of cabinet internal temperature (18–28℃), humidity (40%–60%RH), liquid cooling system pressure (0–1MPa) and flow rate. Liquid leakage detection accuracy ≤5ml/s, linked solenoid valves cut off pipelines within 80ms. Supports remote monitoring, data storage, abnormal alarms and log query.
- Access Control Security Module Supports four identification methods: card swiping, password, fingerprint and remote authorization. Equipped with electromagnetic locks, door timeout alarms, illegal intrusion alarms and access log recording. The access controller links with the monitoring system, uploading real-time alerts for abnormal events to the platform.

Liquid Cooling Cabinet Row Installation View
- Fire Linkage Module Integrated heptafluoropropane / aerosol fire extinguishing device, smoke & temperature detectors, gas release indicator lights and emergency start/stop buttons. Linked with the building fire system; power supply is automatically cut off and fire suppression activated in case of fire to protect equipment.
- Integrated Wiring Module Cable trays and trunking are installed on the top and bottom of the cabinet, supporting separate strong & weak current wiring as well as vertical/horizontal cable management. Wiring capacity ≥24 optical fibers + 48 network cables, delivering neat layout and convenient maintenance.
- Intelligent Management Platform Developed on B/S architecture, supporting local touch screen + remote Web/APP management. Real-time monitoring of cabinet temperature, humidity, voltage, current, power, liquid cooling parameters and equipment operating status. Features remote control, parameter configuration, fault early warning, report generation and data export, supporting cluster management of multiple cabinets and hierarchical permission settings.
- Lighting Module Adopts low-power LED lighting (≤10W) with dual control modes: human body induction and manual operation. Automatically turns on when the cabinet door opens and shuts down with delay, energy-saving and certified for low power consumption.
- Auxiliary Heat Dissipation Module (Optional) Equipped with low-noise axial fans and air cooling heat exchangers, supporting hybrid heat dissipation with liquid cooling as primary and air cooling as auxiliary. Ensures full-load stable operation under 50℃ high-temperature environments.
3. System Classification
KITOZER liquid cooling integrated cabinets are divided into three major categories by heat dissipation mode, power density and deployment form, covering all scenario demands:
3.1 Classification by Heat Dissipation Mode

Cabinet Production Workshop
- Cold Plate Liquid Cooling Cabinet (Mainstream) Cold plates are directly attached to high-power components such as CPUs and GPUs for precise heat dissipation, with low-power components assisted by air cooling. Compatible with existing air-cooled servers, low transformation difficulty, easy maintenance and moderate cost. Suitable for power density of 15–30kW per rack with PUE 1.1–1.2, widely applied in enterprise private clouds, high-density computer rooms and edge computing scenarios.
- Immersion Liquid Cooling Cabinet (High Density) The cabinet forms a sealed pressure-bearing cavity where servers are fully immersed in insulating coolant (fluorinated liquid / deionized water) for full-contact heat exchange. Delivers the highest heat dissipation efficiency with PUE as low as 1.05, zero noise, supporting ultra-high power density above 80kW per rack. Ideal for AI computing, supercomputing centers and GPU cluster high-density scenarios, divided into single-phase immersion (natural convection) and two-phase immersion (phase-change heat transfer).
- Spray Liquid Cooling Cabinet (Convenient Type) Coolant is evenly sprayed onto server components from the top spray plate, absorbing heat and flowing back to the liquid collecting tray for circulation. No server modification required, supports hot swapping and simple maintenance, suitable for legacy computer room renovation. Fits power density of 10–20kW per rack, applied in edge computing and small & medium-sized data centers.
3.2 Classification by Power Density
- Standard Density Type: Single cabinet power density 15–30kW, cold plate heat dissipation, suitable for conventional high-density computer rooms, enterprise private clouds and telecom operator edge computer rooms with high cost performance.
- High Density Type: Single cabinet power density 30–60kW, cold plate / immersion heat dissipation, applicable to AI training clusters, GPU servers and small & medium supercomputing centers.
- Ultra-high Density Type: Single cabinet power density 60–80kW, immersion heat dissipation, designed for supercomputing centers, large AI model training and High Performance Computing (HPC) scenarios.
3.3 Classification by Deployment Form

On-site Installation of Cabinet Cluster
- Indoor Standalone Type: Single cabinet independent deployment with complete built-in liquid cooling, power distribution and monitoring systems, no supporting computer room required. Suitable for small computer rooms, command centers, offices and edge sites.
- Cluster Type (Micro Module): Multiple cabinets (4–20 units) deployed in rows, matched with centralized CDU, closed cooling tower, UPS and monitoring platform to form a micro-module data center. Factory prefabricated for rapid on-site deployment and unified management with optimal energy efficiency, for medium & large data centers and computing centers.
- Container Type: Fully integrated inside a 40/45-foot container, including liquid cooling cabinets, CDU, cooling tower, UPS, fire protection and monitoring systems. Fully prefabricated and deployable within 7 days, wind resistance Grade 12, adaptable to harsh environments (high temperature / extreme cold / high altitude). Used for field data centers, emergency computer rooms and mining/park computer rooms.
4. System Schematic Working Principle
4.1 Cold Plate Liquid Cooling System Working Flow
- Coolant (deionized water / ethylene glycol solution) is cooled to 22–25℃ by CDU and pressurized via circulating pumps for delivery to the manifold.
- The manifold distributes coolant to cold plates of each cabinet through blind-mate quick connectors.
- Cold plates attach to CPUs/GPUs to absorb heat, raising coolant temperature to 32–35℃.
- High-temperature coolant flows back to CDU, exchanging heat with outdoor cooling tower cold water via plate heat exchangers for cooling.
- Cooled coolant is circulated again to form a closed loop.
- The monitoring system tracks temperature, pressure and flow in real time, implementing automatic adjustment or alarms for abnormal conditions.
4.2 Immersion Liquid Cooling System Working Flow
- The sealed cavity is filled with insulating fluorinated liquid whose liquid level submerges servers.
- Heat generated by running servers warms the fluorinated liquid.
- Hot fluorinated liquid rises via natural convection to the condensing coil at the top of the cavity.
- Cooling water flows inside the condensing coil to cool the fluorinated liquid, which flows back to the bottom of the cavity.
- Circulating pumps assist coolant circulation, and CDU regulates cooling water temperature.
- Liquid leakage sensors monitor cavity tightness in real time to ensure safe operation.
5. Full System Configuration List (3 Grades: Basic / Standard / Premium, Brand: KITOZER)
5.1 Basic Version (Cold Plate, 15kW/Rack, Basic Configuration)
è¡¨æ ¼
| No. | Product Name | Model | Technical Parameters | Qty | Unit | Brand | Remarks |
|---|---|---|---|---|---|---|---|
| 1 | Liquid Cooling Integrated Cabinet Frame | KITOZER-LC601222-S | 600×1200×2200mm, 47U, 2.0mm cold-rolled steel, IP54, EMC shielding | 1 | Set | KITOZER | Includes door lock, side panels, base, top cover |
| 2 | Cold Plate Heat Exchange Assembly | KITOZER-CB-1500 | Pure copper core + aluminum frame, 1500W heat dissipation per unit, compatible with CPU/GPU | 4 | Pcs | KITOZER | With thermal grease and fixing brackets |
| 3 | CDU Cooling Distribution Unit | KITOZER-CDU-15 | 15kW cooling capacity, ±1℃ temperature control accuracy, pressure 0–1MPa, flow 0–5m³/h, single pump | 1 | Set | KITOZER | Equipped with controller, display, alarm module |
| 4 | Manifold | KITOZER-MF-8 | 8-way output, 304 stainless steel, 1.6MPa pressure resistance, blind-mate quick connectors | 1 | Set | KITOZER | With valves, pressure gauges and connectors |
| 5 | Sealed Pipeline System | KITOZER-PIPE-S | DN20 304 stainless steel pipes, 1.6MPa pressure resistance, drip-proof connectors, thermal insulation cotton | 1 | Set | KITOZER | Includes main pipes, branch pipes and fixings |
| 6 | Circulating Water Pump | KITOZER-PUMP-0.75 | 0.75kW power, 30m head, 5m³/h flow, F-class insulation | 1 | Set | KITOZER | With shock absorption base and inlet/outlet valves |
| 7 | Coolant Storage Tank | KITOZER-TANK-50 | Stainless steel, 50L volume, liquid level gauge, drain valve, liquid filling port | 1 | Pcs | KITOZER | Compatible with deionized water / ethylene glycol solution |
| 8 | Plate Heat Exchanger | KITOZER-BHE-15 | 5㎡ heat exchange area, 15kW heat exchange capacity, 304 stainless steel plates | 1 | Set | KITOZER | With inlet/outlet valves and pressure gauges |
| 9 | Intelligent Power Distribution Unit (PDU) | KITOZER-PDU-30 | 380V input, 220V output, 30kW, 12 sockets, remote switching, current monitoring | 1 | Set | KITOZER | Includes lightning arrester and air switches |
| 10 | UPS Power Supply | KITOZER-UPS-10 | Online type, 10kVA, 30-minute backup, dual input mains | 1 | Set | KITOZER | With battery pack and battery cabinet |
| 11 | Environmental Monitoring Sensors | KITOZER-SEN-BASIC | Temperature (0–50℃), humidity (0–100%RH), door contact, smoke, water immersion sensors | 1 | Set | KITOZER | With connecting cables and fixing brackets |
| 12 | Monitoring Host (Touch Screen) | KITOZER-MON-7 | 7-inch touch screen, B/S architecture, local monitoring, data storage, alarm function | 1 | Set | KITOZER | With power supply and mounting bracket |
| 13 | LED Lighting Module | KITOZER-LIGHT-10 | 10W power, human body induction control, AC220V | 1 | Set | KITOZER | With lamps, switches and connecting wires |
| 14 | Cable Tray / Trunking | KITOZER-CAB-BASIC | Standard 19-inch, metal material, separate strong & weak current routing | 1 | Set | KITOZER | With cable organizers, cable ties and fixings |
5.2 Standard Version (Cold Plate, 30kW/Rack, Standard Configuration)
è¡¨æ ¼
| No. | Product Name | Model | Technical Parameters | Qty | Unit | Brand | Remarks |
|---|---|---|---|---|---|---|---|
| 1 | Liquid Cooling Integrated Cabinet Frame | KITOZER-LC601222-M | 600×1200×2200mm, 47U, 2.5mm cold-rolled steel, IP55, Class A EMC shielding | 1 | Set | KITOZER | Reinforced ribs, door lock, side panels, base, top cover included |
| 2 | Cold Plate Heat Exchange Assembly | KITOZER-CB-3000 | Pure copper core + aluminum frame, 3000W heat dissipation per unit, compatible with CPU/GPU/memory | 6 | Pcs | KITOZER | With thermal grease and quick fixing brackets |
| 3 | CDU Cooling Distribution Unit | KITOZER-CDU-30 | 30kW cooling capacity, ±0.5℃ temperature control accuracy, pressure 0–1.6MPa, flow 0–10m³/h, dual redundant pumps | 1 | Set | KITOZER | Intelligent controller, 7-inch touch screen, audible & visual alarm |
| 4 | Manifold | KITOZER-MF-12 | 12-way output, 304 stainless steel, 2.0MPa pressure resistance, anti-spray blind-mate quick connectors | 1 | Set | KITOZER | With electric valves, digital pressure gauges and connectors |
| 5 | Sealed Pipeline System | KITOZER-PIPE-M | DN25 304 stainless steel pipes, 2.0MPa pressure resistance, drip-proof quick connectors, thickened thermal insulation cotton | 1 | Set | KITOZER | Main pipes, branch pipes, fixings and leak detection ports included |
| 6 | Circulating Water Pump | KITOZER-PUMP-1.5 | 1.5kW power, 40m head, 10m³/h flow, N+1 redundancy, variable frequency control | 2 | Set | KITOZER | Shock absorption base, inlet/outlet valves, standby pump |
| 7 | Coolant Storage Tank | KITOZER-TANK-100 | Stainless steel, 100L volume, liquid level gauge, drain valve, filling port, pressure sensor | 1 | Pcs | KITOZER | Compatible with deionized water / ethylene glycol, built-in filtration |
| 8 | Plate Heat Exchanger | KITOZER-BHE-30 | 10㎡ heat exchange area, 30kW capacity, 316L stainless steel plates, anti-corrosion | 1 | Set | KITOZER | Inlet/outlet valves, digital pressure & temperature sensors included |
| 9 | Intelligent Power Distribution Unit (PDU) | KITOZER-PDU-60 | 380V input, 220V output, 60kW, 24 sockets, remote switching/monitoring/alarm, lightning protection | 1 | Set | KITOZER | Lightning arrester, air switches and electric energy meter included |
| 10 | High-frequency DC48V Switching Power Supply | KITOZER-PS-60 | DC48V output, 60kW, ≥95% efficiency, N+1 redundancy | 1 | Set | KITOZER | With busbar and insulation monitoring |
| 11 | UPS Power Supply | KITOZER-UPS-20 | Online type, 20kVA, 60-minute backup, dual input mains, intelligent management | 1 | Set | KITOZER | Lithium battery pack, battery cabinet and monitoring module included |
| 12 | Environmental Monitoring Sensors | KITOZER-SEN-STD | Temperature (-20–60℃), humidity (0–100%RH), pressure, flow, liquid leakage, door contact, smoke, water immersion, infrared sensors | 1 | Set | KITOZER | High-precision probes, connecting cables and fixings |
| 13 | Intelligent Management Platform | KITOZER-PLAT-STD | B/S architecture, local 10-inch touch screen + remote Web/APP, multi-cabinet cluster management, data storage/analysis/alarm/reports | 1 | Set | KITOZER | Server, software license, installation & commissioning included |
| 14 | LED Lighting Module | KITOZER-LIGHT-10 | 10W power, dual control (human induction + manual), AC220V, energy efficiency certified | 1 | Set | KITOZER | Lamps, switches, cables and emergency lighting |
| 15 | Access Control Security Module | KITOZER-ACC-STD | Card + password + fingerprint recognition, electromagnetic lock, door timeout / illegal intrusion alarm, access logs | 1 | Set | KITOZER | Access controller, card reader, fingerprint scanner and power supply |
| 16 | Fire Linkage Module | KITOZER-FIRE-STD | Heptafluoropropane fire suppression device, smoke & temperature detectors, gas indicator lights, emergency start/stop buttons | 1 | Set | KITOZER | Fire extinguishing agent, pipelines, nozzles and linkage controller |
| 17 | Cable Tray / Trunking | KITOZER-CAB-STD | Standard 19-inch thickened metal, separate strong & weak current, vertical/horizontal cable management | 1 | Set | KITOZER | Cable organizers, ties, fixings and label paper |
5.3 Premium Version (Immersion, 60kW/Rack, High-end Configuration)
è¡¨æ ¼
| No. | Product Name | Model | Technical Parameters | Qty | Unit | Brand | Remarks |
|---|---|---|---|---|---|---|---|
| 1 | Liquid Cooling Integrated Cabinet Frame | KITOZER-LC601222-H | 600×1200×2200mm, 47U, 3.0mm 304 stainless steel, IP65, sealed pressure-bearing cavity, Class A EMC shielding | 1 | Set | KITOZER | High-strength sealing rings, pressure-bearing door, observation window, pressure relief valve |
| 2 | Immersion Heat Exchange Assembly | KITOZER-IMC-60 | Sealed cavity, non-flammable insulating fluorinated liquid, 60kW heat exchange capacity, full server immersion support | 1 | Set | KITOZER | Server fixing rack, liquid distribution & collection manifold |
| 3 | CDU Cooling Distribution Unit | KITOZER-CDU-60 | 60kW cooling capacity, ±0.3℃ temperature control accuracy, pressure 0–2.0MPa, flow 0–20m³/h, dual redundant variable frequency pumps | 1 | Set | KITOZER | Intelligent controller, 10-inch touch screen, remote monitoring, audible & visual alarm |
| 4 | Condensing Coil Assembly | KITOZER-CC-60 | 316L stainless steel coil, 60kW heat exchange capacity, compatible with two-phase immersion phase-change heat transfer | 1 | Set | KITOZER | Fixing brackets, inlet/outlet connectors and thermal insulation layer |
| 5 | Sealed Pipeline System | KITOZER-PIPE-H | DN32 316L stainless steel pipes, 2.5MPa pressure resistance, anti-spray blind-mate quick connectors, double-layer thermal insulation cotton | 1 | Set | KITOZER | Main pipes, branch pipes, fixings and helium mass spectrometer leak detection |
| 6 | Circulating Water Pump | KITOZER-PUMP-3.0 | 3.0kW power, 50m head, 20m³/h flow, N+1 redundant variable frequency control, low noise | 2 | Set | KITOZER | Shock absorption base, inlet/outlet valves, standby pump and sound insulation cover |
| 7 | Coolant Storage Tank | KITOZER-TANK-200 | 304 stainless steel, 200L volume, liquid level gauge, drain valve, filling port, pressure/temperature/conductivity sensors | 1 | Pcs | KITOZER | For fluorinated liquid, built-in filtration/deaeration/regeneration functions |
| 8 | Plate Heat Exchanger | KITOZER-BHE-60 | 20㎡ heat exchange area, 60kW capacity, 316L stainless steel plates, temperature & corrosion resistant | 1 | Set | KITOZER | Inlet/outlet valves, digital pressure/temperature gauges and flow sensors |
| 9 | Intelligent Power Distribution Unit (PDU) | KITOZER-PDU-80 | 380V input, 220V output, 80kW, 32 sockets, remote switching/monitoring/alarm/energy metering, lightning & surge protection | 1 | Set | KITOZER | Lightning arrester, air switches, energy meter and harmonic suppression |
| 10 | High-frequency DC48V Switching Power Supply | KITOZER-PS-80 | DC48V output, 80kW, ≥96% efficiency, N+1 redundancy, intelligent current sharing | 1 | Set | KITOZER | Busbar, insulation monitoring and fault early warning |
| 11 | Modular UPS Power Supply | KITOZER-UPS-40 | Online modular type, 40kVA, 120-minute backup, dual input mains, hot-swappable modules, intelligent management | 1 | Set | KITOZER | Lithium battery pack, battery cabinet, monitoring module and remote diagnosis |
| 12 | Environmental Monitoring Sensors | KITOZER-SEN-HIGH | Temperature (-40–80℃), humidity (0–100%RH), pressure, flow, liquid leakage, liquid level, conductivity, PH, door contact, smoke, water immersion, infrared, vibration sensors | 1 | Set | KITOZER | High-precision explosion-proof probes, connecting cables and fixings |
| 13 | Cluster Version Intelligent Management Platform | KITOZER-PLAT-HIGH | B/S architecture, local 15-inch touch screen + remote Web/APP/API, cluster management up to 100 cabinets, AI early warning, big data analysis, report generation, energy consumption statistics, remote O&M | 1 | Set | KITOZER | Server, software license, installation & commissioning, 3-year warranty |
| 14 | LED Lighting Module | KITOZER-LIGHT-10 | 10W power, triple control (human induction + manual + emergency), AC220V, energy efficiency certified, explosion-proof | 1 | Set | KITOZER | Lamps, switches, cables, emergency lighting and backup power supply |
| 15 | High-end Access Control Security Module | KITOZER-ACC-HIGH | Card + password + fingerprint + facial recognition, electromagnetic + mechanical lock, door timeout / illegal intrusion / violent damage alarm, access log + video linkage | 1 | Set | KITOZER | Access controller, card reader, fingerprint scanner, facial recognition camera and power supply |
| 16 | High-end Fire Linkage Module | KITOZER-FIRE-HIGH | Aerosol fire suppression device, smoke/temperature/combustible gas detectors, gas indicator lights, emergency start/stop buttons, fire linkage interface | 1 | Set | KITOZER | Fire extinguishing agent, pipelines, nozzles, linkage controller and emergency broadcast |
| 17 | High-end Cable Tray / Trunking | KITOZER-CAB-HIGH | Standard 19-inch thickened stainless steel, separate strong & weak current, vertical/horizontal cable management, cable organizers, ties, fixings, label paper and dust covers | 1 | Set | KITOZER | Cable organizers, ties, fixings, label paper, dust covers and anti-static design |
| 18 | Auxiliary Air Cooling Module | KITOZER-AUX-FAN | Low-noise axial fans (≤55dB(A)), air cooling heat exchanger, hybrid heat dissipation with liquid cooling as primary | 1 | Set | KITOZER | Fans, heat exchanger, fixing brackets and control switches |
6. Full Product Technical Parameters
6.1 Liquid Cooling Integrated Cabinet Frame Parameters
- Model: KITOZER-LC601222-S/M/H
- Overall Dimensions (W × D × H): 600×1200×2200mm
- Internal Usable Space: 47U (1U=44.45mm)
- Material: Basic version: 2.0mm cold-rolled steel; Standard version: 2.5mm cold-rolled steel; Premium version: 3.0mm 304 stainless steel
- Protection Grade: Basic IP54; Standard IP55; Premium IP65
- Shielding Performance: Comply with GB/T12190 Class A shielding standard (30MHz–1GHz, ≥80dB shielding attenuation)
- Load-bearing Capacity: ≥1500kg
- Color: RAL7035 (light gray) / Customizable
- Installation Methods: Indoor standalone / cluster / container deployment
- Operating Environment: -20–50℃, 40%–60%RH (non-condensing)
6.2 Cold Plate Heat Exchange Assembly Parameters
- Model: KITOZER-CB-1500/3000
- Heat Dissipation Power: 1500W per unit (Basic); 3000W per unit (Standard)
- Material: Pure copper core + aluminum alloy frame
- Size: Compatible with mainstream CPU/GPU (100×100×10mm)
- Operating Pressure: ≤1.6MPa
- Operating Temperature: Inlet 22–25℃, Outlet 32–35℃
- Thermal Conductivity: ≥400W/(m·K)
- Installation: Attached to CPU/GPU surface via screw fixing
- Compatible Equipment: Intel/AMD CPU, NVIDIA GPU (RTX/A100/H100)
6.3 Immersion Heat Exchange Assembly Parameters
- Model: KITOZER-IMC-60
- Heat Dissipation Power: 60kW
- Cavity Material: 3.0mm 304 stainless steel, sealed pressure-bearing
- Coolant Type: Insulating fluorinated liquid (non-flammable, non-conductive, non-corrosive)
- Coolant Boiling Point: 56℃
- Operating Temperature: Cavity internal temperature 25–45℃
- Operating Pressure: ≤2.0MPa
- Liquid Level: Submerges server motherboard (≥500mm)
- Compatible Equipment: Standard 19-inch fanless servers
6.4 CDU Cooling Distribution Unit Parameters
- Model: KITOZER-CDU-15/30/60
- Cooling Capacity: 15kW (Basic), 30kW (Standard), 60kW (Premium)
- Temperature Control Accuracy: ±1℃ (Basic), ±0.5℃ (Standard), ±0.3℃ (Premium)
- Operating Pressure: 0–1MPa (Basic), 0–1.6MPa (Standard), 0–2.0MPa (Premium)
- Flow Range: 0–5m³/h (Basic), 0–10m³/h (Standard), 0–20m³/h (Premium)
- Pump Configuration: Single pump (Basic), dual redundant pumps (Standard/Premium), variable frequency control (Premium)
- Display Interface: 7-inch touch screen (Standard), 10-inch touch screen (Premium)
- Communication Interfaces: RS485, Ethernet, SNMP, Modbus TCP
- Power Supply: AC380V±10%, 50Hz
- Noise Level: ≤60dB(A)
6.5 Circulating Water Pump Parameters
- Model: KITOZER-PUMP-0.75/1.5/3.0
- Power: 0.75kW (Basic), 1.5kW (Standard), 3.0kW (Premium)
- Head: 30m (Basic), 40m (Standard), 50m (Premium)
- Flow Rate: 5m³/h (Basic), 10m³/h (Standard), 20m³/h (Premium)
- Voltage: AC380V, 50Hz
- Insulation Class: F
- Protection Grade: IP54
- Control Mode: Power frequency (Basic), variable frequency (Standard/Premium)
- Noise Level: ≤55dB(A)
6.6 Intelligent Power Distribution Unit (PDU) Parameters
- Model: KITOZER-PDU-30/60/80
- Input Voltage: AC380V±10%, 50Hz
- Output Voltage: AC220V±5%
- Rated Power: 30kW (Basic), 60kW (Standard), 80kW (Premium)
- Socket Quantity: 12 outlets (Basic), 24 outlets (Standard), 32 outlets (Premium)
- Protection Functions: Overload, short circuit, overvoltage, undervoltage, lightning and surge protection
- Monitoring Functions: Real-time current, voltage, power and energy monitoring (Standard/Premium)
- Control Functions: Remote switching, timing control, fault alarm (Standard/Premium)
- Communication Interfaces: RS485, Ethernet, SNMP
- Installation: Vertical cabinet mounting
6.7 High-frequency DC48V Switching Power Supply Parameters
- Model: KITOZER-PS-60/80
- Input Voltage: AC380V±10%, 50Hz
- Output Voltage: DC48V±1%
- Rated Power: 60kW (Standard), 80kW (Premium)
- Conversion Efficiency: ≥95% (Standard), ≥96% (Premium)
- Redundancy Mode: N+1 redundant
- Current Sharing Accuracy: ≤±2%
- Protection Functions: Overvoltage, undervoltage, overcurrent, short circuit, overheating and lightning protection
- Communication Interfaces: RS485, Ethernet, Modbus TCP
- Operating Temperature: -10–50℃
6.8 Environmental Monitoring Sensor Parameters
- Temperature Sensor: Range -40–80℃, Accuracy ±0.5℃, Response Time ≤10s
- Humidity Sensor: Range 0–100%RH, Accuracy ±3%RH, Response Time ≤15s
- Pressure Sensor: Range 0–2.5MPa, Accuracy ±0.5%FS, Response Time ≤5s
- Flow Sensor: Range 0–20m³/h, Accuracy ±1%FS, Response Time ≤3s
- Liquid Leakage Sensor: Detection accuracy ≤5ml/s, Response Time ≤80ms, Positioning accuracy ≤1m
- Liquid Level Sensor: Range 0–500mm, Accuracy ±1mm
- Conductivity Sensor: Range 0–100μS/cm, Accuracy ±2%FS
- Door Contact Sensor: Response Time ≤1s, Contact capacity AC220V/5A
- Smoke Sensor: Response Time ≤3s, Compliant with GB4715
- Water Immersion Sensor: Detection height ≤1mm, Response Time ≤2s
6.9 Intelligent Management Platform Parameters
- Architecture: B/S architecture, compatible with Windows/Linux systems
- Display Interface: 7-inch touch screen (Basic), 10-inch touch screen (Standard), 15-inch touch screen (Premium)
- Remote Access: Web browser, mobile APP, WeChat Mini Program
- Management Capacity: Single cabinet (Basic), ≤20 cabinets (Standard), ≤100 cabinets (Premium)
- Data Storage: Local storage ≥1 year, remote backup supported
- Alarm Functions: Audible & visual alarm, SMS push, APP notification, email alert
- Communication Protocols: RS485, Ethernet, SNMP, Modbus TCP, MQTT
- Security Mechanism: Hierarchical permission management, encrypted account passwords, operation log recording
- Functional Modules: Real-time monitoring, parameter configuration, fault early warning, report generation, energy consumption statistics, remote operation & maintenance
7. Product Application Scope
With advantages of high heat dissipation efficiency, low PUE, high integration, easy deployment and convenient maintenance, KITOZER liquid cooling integrated cabinets are widely applied in the following scenarios:
- AI Computing Centers: AI training clusters, GPU server clusters and large AI model training platforms, supporting single cabinet power density of 30–80kW to resolve heat dissipation bottlenecks of high-power hardware.
- Supercomputing Centers (HPC): High-performance computing, scientific computing, weather forecasting, aerospace engineering, gene sequencing and drug research, supporting ultra-high power density deployment with PUE as low as 1.05.
- High-density Enterprise Private Clouds: Large enterprises, financial institutions and internet companies’ private cloud platforms with high-density server deployment (15–30kW per rack), realizing energy saving and improved computing density.
- Telecom Operator Data Centers: Backbone / edge data centers of China Mobile, China Unicom and China Telecom, 5G base station supporting computer rooms for high-density server and storage equipment deployment (15–30kW per rack).
- Edge Computing / Micro Data Centers: Small computer rooms in industrial parks, office buildings, factories, hospitals, schools and branch offices, featuring independent deployment and fast launch without dedicated supporting computer rooms.
- Command & Monitoring Centers: Government emergency command, public security dispatch, traffic control, power dispatching and security monitoring centers, with integrated design for stable performance and low noise.
- Power & Communication Computer Rooms: Substations, power plants, communication base stations and optical cable relay stations, adaptable to high-temperature/humidity harsh environments with IP54–IP65 protection grade.
- Medical & Educational Computer Rooms: Hospital information centers, university data centers and research laboratories for high-density servers, medical imaging equipment and scientific computing hardware.
- Containerized Data Centers: Mining sites, oil & gas fields, border outposts, disaster emergency response and temporary offices, fully prefabricated with 7-day fast deployment, wind resistance Grade 12 and adaptability to -40–50℃ extreme temperatures.
- Legacy Computer Room Renovation: Upgrade of traditional air-cooled computer rooms with heat dissipation shortages, high energy consumption and loud noise. Supports hybrid liquid-air cooling deployment with low transformation difficulty and short construction cycle.
8. Product Advantages
8.1 Core Technical Advantages
- Ultra-high Heat Dissipation Efficiency: Liquid cooling delivers 3–5 times higher heat dissipation efficiency than traditional air cooling. Cold plate type supports 15–30kW per rack, immersion type supports 30–80kW per rack, completely breaking air cooling heat dissipation limits.
- Extreme Energy Saving: Overall cabinet PUE as low as 1.05–1.1, saving 40%–70% energy compared with air cooling systems, drastically cutting data center electricity costs and supporting national dual-carbon goals.
- Ultra-low Operating Noise: Eliminates massive server fans and precision air conditioners, operating noise ≤55dB(A), 20–30dB lower than air-cooled computer rooms (70–85dB(A)) to improve working environments.
- Full-link Zero Leakage Protection: Four layers of protection including anti-spray blind-mate quick connectors, 304/316L stainless steel pipelines, diversion water collecting trays and real-time liquid leakage monitoring. Liquid leakage response time ≤80ms to guarantee equipment safety.
- Highly Integrated All-in-one Design: Integrates liquid cooling, power distribution, monitoring, security, fire protection and wiring in one unit, factory prefabrication rate ≥90%. Only water and electricity connection required on-site, cutting deployment cycle by 70%.
- Intelligent Monitoring & Early Warning: Over 500 sensors real-time track temperature, pressure, flow and liquid leakage parameters. AI algorithms predict faults 48–72 hours in advance, supporting remote monitoring and operation & maintenance to reduce labor costs.
- Wide Temperature Adaptation: Operating range -20–50℃; immersion version adapts to -40–80℃ extreme environments, maintaining full load without frequency reduction under high temperatures and stable startup under low temperatures.
- Flexible Expansion & Compatibility: Supports standalone single cabinet, multi-cabinet cluster and containerized deployment; compatible with standard 19/21-inch IT equipment, mainstream CPUs/GPUs and Windows/Linux systems, enabling mixed deployment of new and legacy hardware.
8.2 Customization & Service Advantages
- Full-dimensional Customization Capability: Customizable dimensions (600–800mm width, 1000–1500mm depth, 2000–2400mm height), power density (15–80kW per rack), heat dissipation mode (cold plate / immersion / spray), configuration (Basic/Standard/Premium), color and additional functions (energy storage, photovoltaic interfaces) to meet personalized client demands.
- OEM/ODM Processing Service: Supports private label production, customized design, core component OEM and full cabinet OEM, providing complete technical solutions and production support for clients to build independent brands rapidly.
- Strict Confidentiality Mechanism: Confidentiality agreements signed to protect client customized solutions, technical parameters and project information; full production process control to prevent technical leakage and safeguard client intellectual property rights.
- Fast Delivery of Stock Products: Standard configurations in stock for delivery within 3–7 days; customized products delivered in 15–30 days, factory prefabricated and shipped as whole cabinets for fast on-site deployment.
- One-stop Service System: Full lifecycle service including pre-project planning, site survey, product customization, manufacturing, delivery, on-site installation & commissioning, operation training, 7×24-hour technical support and lifetime maintenance, with dedicated project managers for full-process tracking.
- Comprehensive After-sales Warranty: Core components (CDU, circulating pump, UPS, monitoring host) covered by 3-year free warranty, full cabinet 1-year free warranty; free installation & commissioning, free technical training and free software upgrades provided; 7×24-hour technical hotline with 2-hour response and 24-hour on-site service nationwide.
8.3 Functional & Parameter Advantages
- Stable & Safe Power Distribution: Redundant power supply via dual mains + UPS, high-efficiency DC48V power delivery supporting 60–80kW high-power output. Equipped with overload, short circuit, overvoltage, undervoltage, lightning and surge protection to guarantee power supply safety for IT equipment.
- Comprehensive & Precise Monitoring: Full-parameter monitoring covering temperature, humidity, pressure, flow, liquid leakage, liquid level, conductivity, PH value, door contact, smoke, water immersion, infrared and vibration with high precision and fast response to track equipment operation status in real time.
- Intelligent & Reliable Security: Multi-factor access control (card, password, fingerprint, facial recognition), real-time alarms for abnormal events, log recording and video linkage to ensure physical security of computer rooms.
- Efficient Fire Linkage: Integrated heptafluoropropane / aerosol fire suppression devices linked with smoke & temperature detectors, completing fire suppression within 30 seconds upon fire detection to minimize equipment loss.
- Neat & Convenient Wiring: Separate strong & weak current routing with vertical/horizontal cable management, large wiring capacity for tidy layout, easy maintenance, reduced cable interference and improved network stability.
9. Bid Tender Control Parameters (★ Marked as Mandatory Items)
- ★ Cabinet Material & Protection: Cabinet frame constructed with ≥2.0mm high-strength cold-rolled steel / 304 stainless steel, electrostatically sprayed anti-corrosion coating, protection grade ≥IP54, hexahedral EMC shielding design meeting GB/T12190 Class A shielding standard.
- ★ Heat Dissipation Efficiency & Power Density: Liquid cooling heat dissipation efficiency ≥3 times air cooling, cold plate single cabinet power density ≥15kW, immersion type ≥30kW, overall cabinet PUE ≤1.1.
- ★ CDU Temperature Control Accuracy: CDU cooling distribution unit temperature control accuracy ≤±1℃, with real-time monitoring and automatic adjustment of temperature, pressure and flow.
- ★ Liquid Leakage Protection & Response: Triple protection including anti-spray blind-mate quick connectors, diversion water collecting trays and liquid leakage sensors, liquid leakage detection accuracy ≤5ml/s, response time ≤80ms with automatic pipeline cut-off function.
- ★ Power Distribution Efficiency & Redundancy: Supports high-efficiency DC48V power supply with conversion efficiency ≥95% and N+1 redundant design; PDU rated power ≥30kW with remote switching, voltage/current monitoring and overload protection functions.
- ★ Monitoring System Precision: Temperature sensor accuracy ≤±0.5℃, humidity sensor accuracy ≤±3%RH, pressure sensor accuracy ≤±0.5%FS, liquid leakage sensor response time ≤80ms.
- ★ Intelligent Management Platform Functions: B/S architecture, supporting local touch screen + remote Web/APP management, equipped with real-time monitoring, parameter configuration, fault early warning, report generation and energy consumption statistics, supporting multi-cabinet cluster management.
- ★ Operating Environment Adaptability: Operating temperature range -20℃–50℃, full-load stable operation under 50℃ high temperature, humidity 40%–60%RH (non-condensing).
- ★ Noise Index: Overall operating noise ≤55dB(A), compliant with GB/T19889.3 standard.
- ★ Integration & Deployment Cycle: Factory prefabrication rate ≥90%, on-site deployment cycle ≤7 days, supporting standalone single cabinet / multi-cabinet cluster / containerized deployment modes.
- ★ Customization Capability: Full-dimensional customization support for dimensions, power density, heat dissipation mode, configuration, color and additional functions to meet personalized client demands.
- ★ After-sales Service Warranty: Core components ≥3-year warranty, full cabinet ≥1-year warranty; 7×24-hour technical support, 2-hour response and 24-hour on-site service guarantee.
10. Full Product Solutions
10.1 Liquid Cooling Solution for AI Computing Centers
- Pain Points: AI training clusters require single cabinet power density of 30–80kW; traditional air cooling suffers insufficient heat dissipation, high energy consumption, loud noise and high PUE.
- Solution: Adopt KITOZER premium immersion liquid cooling integrated cabinets (60–80kW per rack), full-contact heat exchange via fluorinated liquid with PUE as low as 1.05. Matched with centralized CDU, closed cooling tower, DC48V bus power supply and intelligent management platform for cluster deployment of 10–20 cabinets, factory prefabricated for on-site launch within 7 days.
- Outcomes: Heat dissipation efficiency improved by 5 times, PUE reduced to 1.08 with 60% annual energy saving; noise ≤55dB(A) for improved working environment; intelligent fault early warning boosts operation & maintenance efficiency by 50%.
10.2 High-density Enterprise Private Cloud Solution
- Pain Points: High-density server deployment (15–30kW per rack) in enterprise computer rooms faces air cooling bottlenecks, high energy consumption, low space utilization and complex maintenance.
- Solution: Deploy KITOZER standard cold plate liquid cooling integrated cabinets (30kW per rack), cold plates closely attached to CPUs/GPUs for precise heat dissipation. Integrated UPS+PDU, environmental monitoring, access control security and fire linkage, supporting standalone single cabinet or cluster deployment of 4–8 units with no major computer room renovation required for fast launch.
- Outcomes: Heat dissipation efficiency tripled, PUE reduced to 1.12 with 40% annual energy saving; space utilization increased by 30%, integrated design simplifies operation & maintenance, ensuring 24/7 stable business operation.
10.3 Edge Computing / Micro Data Center Solution
- Pain Points: Edge sites feature limited space, complex high-temperature/humidity environments, limited budgets, fast deployment requirements and unattended operation.
- Solution: Adopt KITOZER basic cold plate liquid cooling integrated cabinets with compact 600×1200×2200mm dimensions, occupying only 0.72㎡ floor space for standalone deployment. IP54 protection grade adapts to -20–50℃ environments, integrated UPS, monitoring, security and fire protection for plug-and-play deployment with remote unattended operation & maintenance.
- Outcomes: Single site deployment completed within 3 days with no dedicated computer room required; 45% energy saving cuts operational costs; remote monitoring & early warning eliminates on-site labor, stable operation under high temperatures without frequency reduction or downtime.
10.4 Containerized Data Center Solution
- Pain Points: Field/harsh environment data centers require rapid deployment, wind/earthquake resistance, high/low temperature adaptability and flexible relocation capability.
- Solution: KITOZER containerized liquid cooling integrated cabinets, integrating 10–20 liquid cooling cabinets, centralized CDU, closed cooling tower, UPS, fire protection and monitoring inside a 45-foot container. Fully factory prefabricated, on-site deployment within 7 days, wind resistance Grade 12, seismic resistance Grade 8, adaptable to -40–50℃ extreme temperatures, supporting multi-energy access including mains, diesel generators and photovoltaic power.
- Outcomes: Deployment cycle shortened by 80% to respond to business demands rapidly; fully sealed dustproof design delivers stable operation in harsh field environments; integrated management simplifies maintenance; whole-container relocation capability adapts to shifting business demands of mining sites.
10.5 Legacy Computer Room Liquid Cooling Renovation Solution
- Pain Points: Traditional air-cooled computer rooms suffer insufficient heat dissipation, high energy consumption, loud noise, high PUE, aging equipment, long renovation cycles and high costs.
- Solution: KITOZER cold plate / spray liquid cooling integrated cabinets, compatible with existing servers without hardware modification. Hybrid liquid-air cooling deployment via cold plate attachment or top spray heat dissipation, integrated intelligent monitoring and remote operation & maintenance. Renovation cycle ≤15 days with 50% lower costs compared with new computer room construction.
- Outcomes: Heat dissipation efficiency tripled to resolve heat shortages; 40%–60% energy saving reduces electricity expenditure; noise reduced by 20dB for improved working environments; short renovation cycle and low cost enable fast computer room upgrade.
11. Product Application Cases
11.1 AI Technology Company Training Cluster Project
- Project Background: Construction of a 10-cabinet AI training cluster with single cabinet power density of 40kW to resolve heat dissipation issues of GPU servers and reduce PUE.
- Solution Deployed: KITOZER premium immersion liquid cooling integrated cabinets (60kW per rack), fluorinated liquid full-contact heat exchange, matched with centralized CDU, closed cooling tower, DC48V bus power supply and intelligent management platform for 10-cabinet cluster deployment.
- Project Results: Heat dissipation efficiency improved by 5 times, PUE reduced to 1.08, annual electricity cost savings of RMB 800,000; operating noise ≤55dB(A); intelligent fault early warning boosts O&M efficiency by 50%; zero major faults over 2 years of continuous stable operation.
11.2 Large Financial Enterprise Private Cloud Project
- Project Background: Construction of an 8-cabinet high-density private cloud computer room with single cabinet power density of 25kW, requiring energy saving, stable performance and simplified maintenance.
- Solution Deployed: KITOZER standard cold plate liquid cooling integrated cabinets (30kW per rack) with precise cold plate heat dissipation, integrated UPS+PDU, environmental monitoring, access control security and fire linkage for 8-cabinet cluster deployment.
- Project Results: Heat dissipation efficiency tripled, PUE reduced to 1.12, annual electricity cost savings of RMB 500,000; integrated design cuts O&M workload by 40%; zero major faults over 3 years of stable operation to guarantee secure financial business.
11.3 Telecom Operator Edge Data Center Project
- Project Background: Edge data center construction across 5 prefecture-level cities with 2 cabinets per site, limited space, high ambient temperature (45℃), fast deployment and unattended operation requirements.
- Solution Deployed: KITOZER basic cold plate liquid cooling integrated cabinets with standalone 600×1200×2200mm layout, IP54 protection grade adapting to 45℃ high temperatures, integrated UPS, monitoring, security and fire protection for plug-and-play remote unattended operation.
- Project Results: Each site fully deployed within 3 days; 45% energy saving delivers annual electricity savings of RMB 300,000; remote monitoring & early warning enables 2 years of stable unattended operation without frequency reduction or downtime under high temperatures.
11.4 Mining Site Containerized Data Center Project
- Project Background: Field data center deployment in mining areas with high temperature (50℃), heavy sand dust, no dedicated computer rooms, fast launch and relocatable requirements.
- Solution Deployed: KITOZER 45-foot containerized liquid cooling integrated system, integrating 12 cold plate liquid cooling cabinets, centralized CDU, closed cooling tower, UPS, fire protection and monitoring. Factory prefabricated for on-site deployment within 7 days, wind resistance Grade 12, dustproof and adaptable to 50℃ high temperatures.
- Project Results: Full deployment completed within 7 days to rapidly support mining business; fully sealed dustproof design delivers 1 year of fault-free stable operation; 50% energy saving cuts field operational costs; whole-container relocation capability adapts to shifting mining business demands.
12. Common Product Faults & Maintenance Guide
12.1 Common Faults & Troubleshooting Methods
- Excessively High Coolant Temperature
- Root Causes: CDU failure, circulating pump shutdown, pipeline blockage, poor cooling tower heat dissipation, insufficient coolant volume
- Solutions: ①Inspect CDU operation, restart or repair faulty CDU; ② Check pump power and running status, activate standby pump; ③ Clean pipeline filters and remove blockages; ④ Clear cooling tower heat sink dust to improve ventilation; ⑤ Top up coolant to standard liquid level.
- Liquid Leakage Alarm Triggered
- Root Causes: Loose connectors, aging sealing rings, damaged pipelines, cold plate leakage
- Solutions: ①Shut down equipment and release pipeline pressure, cut off power supply immediately; ② Tighten loose pipe connectors; ③ Replace aged sealing rings; ④ Repair or replace damaged pipelines; ⑤ Inspect cold plate tightness, replace cold plate if leakage occurs; ⑥ Reset alarm and conduct trial operation to monitor status.
- Abnormal Noise / Vibration of Circulating Pump
- Root Causes: Worn pump bearings, pump internal cavitation, loose base fixing bolts, excessive pipeline stress
- Solutions: ①Shut down pump to inspect bearings, replace severely worn bearings; ② Open exhaust valves to release air bubbles inside pump; ③ Tighten base fixing bolts; ④ Adjust pipeline supports to eliminate pipeline stress; ⑤ Restart pump and monitor operating status.
- PDU Overload Alarm
- Root Causes: Excessive load power, short circuit, PDU hardware failure
- Solutions: â‘ Cut off PDU power supply immediately and inspect connected load equipment; â‘¡ Remove non-essential loads to control power within rated range; â‘¢ Troubleshoot and eliminate short circuit faults; â‘£ Restart PDU, repair or replace if alarm persists.
- No Data / Malfunctioning Alarms on Monitoring System
- Root Causes: Faulty sensors, loose connecting cables, monitoring host failure, communication interruption
- Solutions: ①Inspect sensor status, replace faulty sensors; ② Tighten sensor connecting cables; ③ Restart monitoring host and resolve software faults; ④ Inspect communication lines to restore data transmission; ⑤ Calibrate sensors to ensure data accuracy.
12.2 Routine Maintenance Schedule (Daily / Monthly / Quarterly / Annual)
12.2.1 Daily Inspection (Manual + Automatic)
- Manual Inspection: â‘ Check cabinet exterior for deformation, damage or liquid leakage traces; â‘¡ Inspect CDU, circulating pump and UPS operation for abnormal noise or odor; â‘¢ Review touch screen monitoring data to confirm normal temperature, pressure, flow and liquid level parameters; â‘£ Check indicator and alarm light status for abnormal alerts.
- Automatic Inspection: Monitoring system tracks all parameters in real time and triggers automatic alarms for anomalies, completing preliminary diagnosis within 15 minutes.
12.2.2 Monthly Maintenance
- Coolant Testing: Sample coolant to test conductivity, PH value, turbidity and color; add insulating additives for excessive conductivity, adjust PH value or fully replace emulsified coolant.
- Filter Cleaning: Disassemble Y-type filters in circulation system, blow clean filter screens with compressed air to remove impurities and prevent pipeline blockage.
- Connector & Pipeline Inspection: Check all pipe connectors, pipelines and sealing rings for looseness, aging, damage or leakage traces; tighten or replace defective components promptly.
- Fan & Heat Sink Cleaning: Clear dust from auxiliary cooling fans and cooling tower heat sinks to guarantee heat dissipation performance.
- Sensor Calibration: Calibrate temperature, pressure, flow and liquid leakage sensors to ensure monitoring precision.
12.2.3 Quarterly Maintenance
- Pipeline Pressure Test: Conduct pressure test on liquid cooling pipelines at 1.2 times rated pressure, hold pressure for 30 minutes with zero leakage and pressure drop as qualified standard.
- Pump Set Maintenance: Inspect pump bearings, sealing components and motor insulation, replace lubricating oil and tighten connecting bolts.
- Power Distribution System Inspection: Check UPS, PDU, air switches and lightning arrester operation, test protection functions and tighten wiring terminals.
- Monitoring System Test: Verify alarm, communication and remote control functions; back up monitoring data.
- Cabinet Cleaning: Remove dust and stains inside & outside cabinets, inspect cabinet grounding integrity.
12.2.4 Annual Maintenance
- Coolant Replacement: Fully replace water-based coolant; partially replace fluorinated liquid and replenish additives; thoroughly clean storage tanks, pipelines and cold plates.
- Replacement of Seals & Consumables: Replace all pipe connector sealing rings, pump sealing components, filter cartridges and sensor probes.
- Cold Plate / Heat Exchange Assembly Inspection: Test tightness and heat exchange efficiency of cold plates / immersion heat exchange assemblies, clean or replace if performance degradation occurs.
- Full Machine Performance Test: Complete functional testing of liquid cooling, power distribution, monitoring, security and fire protection systems to verify all indicators meet standards.
- Firmware & Software Upgrade: Upgrade CDU, monitoring host and UPS firmware & software to fix vulnerabilities and optimize performance.
- Operation & Maintenance Training: Annual training for O&M staff to update maintenance knowledge and troubleshooting skills.
13. Factory Strength & After-sales Service System
13.1 Factory Strength
- Production Scale: Guangzhou Laian Intelligent System Development Co., Ltd. operates a 20,000㎡ modern production base with 10 specialized production lines, annual output capacity of over 5,000 liquid cooling integrated cabinets to fulfill large-batch orders.
- R&D Team: Over 50 professional R&D staff including liquid cooling technical experts, structural engineers, electrical engineers and software developers with 10+ years of computer room equipment R&D experience, mastering core technologies of liquid cooling heat dissipation, intelligent monitoring and high-efficiency power distribution, holding more than 20 patented technologies.
- Production Craftsmanship: Adopts advanced manufacturing processes including laser cutting, CNC bending, robotic welding, electrostatic spraying and dust-free assembly. 100% inspection of core components, products compliant with ISO9001, ISO14001, ISO45001 international standards, certified by CE, FCC and RoHS.
- Supply Chain: Long-term strategic cooperation with high-quality raw material and core component suppliers; key parts sourced from domestic top-tier or imported brands to guarantee product stability; stock inventory maintained for fast delivery of standard products within 3–7 days.
- Testing Capacity: Equipped with high-low temperature test chamber, rain test chamber, vibration test chamber, EMC shielding test chamber and liquid cooling performance test platform to simulate full operating conditions and verify stable performance under extreme environments.
13.2 After-sales Service System
- One-stop Full Lifecycle Service: Pre-project planning → site survey → product customization → manufacturing → delivery → on-site installation & commissioning → O&M training → 7×24-hour technical support → lifetime maintenance, with dedicated project managers tracking full project delivery to ensure smooth project launch.
- Warranty Commitment: Core components (CDU, circulating pump, UPS, monitoring host) covered by 3-year free warranty, full cabinet 1-year free warranty; free repair, component replacement and on-site service within warranty period.
- Fast Response Mechanism: 7×24-hour technical hotline, 2-hour response to client inquiries, solution provided within 4 hours, 24-hour on-site service nationwide and 48-hour overseas on-site service.
- Installation & Commissioning: Professional engineers provide free on-site installation & commissioning in strict compliance with construction standards to ensure normal equipment operation; free training for client O&M staff covering daily operation, maintenance and fault handling post-installation.
- Lifetime Maintenance Service: Lifetime maintenance available after warranty expiration, only charging component cost fees; regular client follow-ups to evaluate equipment operation and provide maintenance recommendations; free software upgrades, technical consultation and solution optimization services permanently.
- Spare Parts Support: National spare parts warehouse network with permanent stock of core components for rapid spare parts supply; preferential pricing for replacement components post-warranty to cut client maintenance costs.
14. Conclusion
As the flagship product of Guangzhou Laian Intelligent System Development Co., Ltd., the KITOZER liquid cooling integrated cabinet integrates cutting-edge liquid cooling technology, highly integrated design and intelligent control concepts, thoroughly resolving pain points of traditional air-cooled computer rooms including insufficient heat dissipation, high energy consumption, loud noise, low integration and complex maintenance. It delivers high-efficiency, energy-saving, stable, reliable and easy-to-maintain all-in-one solutions for AI computing, supercomputing centers, high-density private clouds, edge computing, containerized data centers and legacy computer room renovation scenarios.
With core strengths of ultra-high heat dissipation efficiency, extreme energy saving, ultra-low noise operation, full-link zero leakage, flexible expansion, full-dimensional customization and comprehensive after-sales service, the product has been successfully deployed in over 100 projects across more than 30 provinces and municipalities nationwide, winning consistent client recognition.
Adhering to core values of technological innovation, quality priority, customer-centricity and win-win cooperation, Guangzhou Laian Intelligent System Development Co., Ltd. continuously invests in R&D to optimize product performance and upgrade service quality, supporting green, intelligent and high-efficiency transformation of data centers and contributing to national dual-carbon goals.
In the future, the company will deepen its layout in liquid cooling technology, launching new liquid cooling integrated cabinet products with higher power density, lower PUE and enhanced intelligence & integration, expanding applicable scenarios to create greater value for clients and strive to become a world-leading provider of liquid cooling integrated cabinet solutions.
15. Search Keywords & SEO Tags
15.1 Core Search Keywords
Liquid cooling integrated cabinet, KITOZER liquid cooling cabinet, Laian Intelligent liquid cooling integrated cabinet, indoor liquid cooling integrated cabinet, high-density liquid cooling cabinet, AI liquid cooling cabinet, supercomputing liquid cooling cabinet, cold plate liquid cooling cabinet, immersion liquid cooling cabinet
15.2 Long-tail Search Keywords
Liquid cooling integrated cabinet manufacturer, customized liquid cooling integrated cabinet, Guangzhou liquid cooling integrated cabinet, liquid cooling cabinet solution, liquid cooling cabinet configuration list, liquid cooling cabinet technical parameters, liquid cooling cabinet application cases, liquid cooling cabinet maintenance guide, data center liquid cooling cabinet, micro-module liquid cooling cabinet, containerized liquid cooling cabinet, legacy computer room liquid cooling renovation, DC48V liquid cooling cabinet, low PUE liquid cooling cabinet, energy-saving liquid cooling cabinet
15.3 SEO Hashtags
#LiquidCoolingIntegratedCabinet #KITOZER #LaianIntelligent #HighDensityCabinet #AICabinet #SupercomputingCabinet #ColdPlateLiquidCooling #ImmersionLiquidCooling #DataCenter #MicroModule #ComputerRoomConstruction #EnergySavingCabinet
Company Profile Supplementary Text
KITOZER (Kaituozhe) is a brand owned by Guangzhou Laian Intelligent System Development Co., Ltd., a high-tech enterprise focusing on R&D, production, sales and service of liquid cooling integrated cabinets, indoor integrated cabinets, micro-module data centers and supporting computer room equipment. Headquartered in Guangzhou, Guangdong Province, the company operates a 20,000㎡ modern production base and over 50 professional R&D staff with annual output capacity exceeding 5,000 units. Products are sold nationwide across more than 30 provinces and exported to Southeast Asia, the Middle East, Europe and America.
The flagship KITOZER liquid cooling integrated cabinet integrates advanced liquid cooling technology, high integration design and intelligent management systems, divided into three series: cold plate, immersion and spray types, supporting single cabinet power density of 15–80kW with overall cabinet PUE as low as 1.05–1.1, saving 40%–70% more energy than traditional air cooling systems and operating noise ≤55dB(A). It completely breaks heat dissipation bottlenecks of air cooling and is applicable to AI computing, supercomputing centers, high-density private clouds, edge computing, containerized data centers and legacy computer room renovation scenarios.
Constructed with high-strength cold-rolled steel / 304 stainless steel with IP54–IP65 protection grade and hexahedral EMC shielding design, the KITOZER cabinet integrates liquid cooling heat dissipation, intelligent power distribution, environmental monitoring, access control security, fire linkage and integrated wiring with factory prefabrication rate ≥90%. Only water and electricity connection required on-site for deployment within 3–7 days, with no dedicated supporting computer room needed for plug-and-play operation.
Product core strengths include full-link zero leakage, intelligent fault early warning, wide temperature environment adaptation, flexible expansion compatibility and full-dimensional customization. OEM/ODM processing, strict confidentiality agreements and fast stock delivery services are available. The company provides one-stop full lifecycle service including pre-project planning, site survey, product customization, installation & commissioning, O&M training, 7×24-hour technical support and lifetime maintenance.
All products pass ISO9001, ISO14001, ISO45001 international quality system certifications, CE, FCC and RoHS certifications with over 20 patented technologies. Core components carry a 3-year warranty and full cabinets a 1-year warranty with reliable quality and stable performance.
Sales & Consultation Hotline: +86 +86 13538869979 (WeChat available), +86 +86 13538869979 (WeChat available). Direct supply from factory with complete qualification documents, tender materials, product manuals, technical parameter solutions, engineering cases and configuration lists provided. New and existing clients are welcome to contact us for consultation, factory inspection and cooperation negotiations.