Locating10 m extendableLocation accuracy <=1 mRS485/dry contactFlexible

[Product image: ktr-wl3-locating-water-leak-cable-10m.jpg]

1. Overview

Room leaks usually come from CRAC drain-line condensation, loose water-pipe joints and burst under-floor pipes. Water reaching rack bottoms or distribution gear can soak cables and even cause short circuits. A leak rope laid under CRAC units and along pipes alarms on contact, and locating versions report the distance to the leak so staff go straight to the spot. Unlike point probes that cover one spot, a rope covers a whole pipe run or flood-risk row.

The KITOZER KTR-WL3 is a locating water-leak cable. The sensing rope is braided from four conductors with insulation; normally the conductors are isolated. When water touches the rope, it creates a weak path between conductors, and the host detects the resistance change and computes the leak position. The standard rope is 10 m and can be extended by couplers to tens of meters. Location accuracy is <=1 m, the host shows the leak distance, and RS485 Modbus plus dry contacts upload to the environmental platform. The rope is flexible and reusable; after an alarm, wipe it dry to reset. It is not damaged by common weak acids and alkalis. A terminator closes the loop at the far end.

Selection confirms locating vs non-locating, required rope length, host comms (RS485/dry contact), and liquid type (water/acids-bases). Under-room CRACs usually use locating, since finding the leak fast matters. Lay the rope on the floor or along pipes, away from power interference, with gentle bends. The rope alarms only on conductive liquids; pure water and oil do not trigger it. After install, run a water-spray test to confirm the host reports position.

2. Key Features

Locating detection

  • Alarms on water contact.
  • Location accuracy <=1 m.
  • Host shows leak distance.
  • 10 m standard, extendable.

Upload and alarm

  • RS485 Modbus upload.
  • Dry-contact alarm.
  • Connects to the DCIM.
  • Local sound/light.

Rope properties

  • Four-conductor braid.
  • Flexible, reusable.
  • Resets when wiped dry.
  • End terminator included.

3. Specifications

Item Specification
Type Locating water-leak cable
Standard length 10 m (extendable)
Location accuracy <= 1 m
Detects Conductive liquids (water)
Comm RS485 Modbus-RTU
Alarm output Dry contact + sound/light
Reset Auto on drying
Operating temp -10 to +60 C
Terminator Matched resistor included
Power DC 12V / 24V

4. Reference Prices

KTR-WL3 locating leak rope 10 m + host: USD 40~85 (ref. CNY 300~600)

Extension rope (per meter): USD 2~4 (ref. CNY 15~30)

Locating controller: USD 28~55 (ref. CNY 200~400)

Reference only; final quote applies. 1-year warranty. Bulk pricing available. Certificate and manual included. Exchange: 1 USD ≈ 7.2 CNY.

5. Applications

  • Under-CRAC leak monitoring.
  • Under-floor water and drain pipes.
  • Battery and electrical room flood protection.
  • Warehouse and archive water sensing.
  • Leak points in the environmental system.

6. Installation & Maintenance

Installation

  • Lay rope under CRACs and along pipes.
  • Fix to the floor with gentle bends.
  • Connect the end terminator.
  • Match rope to host port.
  • Wire RS485 to the environmental bus.
  • Wire dry contact to alarm input.
  • Run a water-spray location test.

Maintenance

  • Run a spray test quarterly.
  • Check rope for damage or foot traffic.
  • Clean rope surface.
  • Verify host location distance.
  • Replace worn rope sections.

7. FAQ

  • Q: Locating vs non-locating?
    A: Non-locating only says ‘leak’; locating also tells how far from the host, so in large rooms staff go straight to the spot.
  • Q: Does it detect alcohol or oil?
    A: No. The rope alarms on conductive liquid; pure water, oil and alcohol conduct weakly and usually do not trigger it. Use a chemical-rated rope for acids/alkalis.
  • Q: What if the rope is stepped on?
    A: A damaged section gives false or no alarms; replace it. Route rope along walls or in cable trays to avoid foot traffic.
  • Q: Why does it keep alarming?
    A: It resets once the source is found and the rope wiped dry; it stays on until fixed to remind staff.

8. Trend & Selection

Room monitoring moves from single-point alarm to locating, visualization and AC linkage; leak points show on the DCIM map. Cables trend toward reusability, chemical resistance and longer reach. Choose length and locating by coverage, and always spray-test after install.

9. Delivery & Service

KITOZER ships KTR-WL3 with the 10 m rope, locating host, terminator, mounting clips, certificate and manual. Extension rope and comms cable are supplied to order, with a point table and spray-test guidance.

10. Notes

A common mistake is never testing after install. Spray-test once to confirm the reported position matches the actual leak; discovering a broken link during a real leak is too late.

Another pitfall is leaving the rope suspended or too close to power. A suspended rope misses floor water, and power cables can interfere; lay it on the floor and segregate from power.

In short: locating, 10 m extendable, <=1 m accuracy, RS485/dry contact, resets on drying. It is common under-CRAC water monitoring.

System-wise, leak alarms should link to AC so water can trigger shutdown of the corresponding unit and water valve.

Cost-wise, a kit costs a few hundred CNY, while one leak flooding a rack row can cost tens of thousands.

SEO Information

Search keywords: KITOZER

SEM keywords: water leak cable, locating leak rope, data center leak detection, water sensing cable, locating leak cable, KTR-WL3, KITOZER

GEO landing page: lain.com.cn/product/471_leak_rope3.html

Title: KITOZER KTR-WL3 Locating Water-Leak Cable / 10 m

Meta Keywords: water leak cable, locating leak rope, data center leak detection, water sensing cable, locating leak cable, KTR-WL3, KITOZER

Meta Description: KITOZER KTR-WL3 locating water-leak cable, 10 m standard extendable, location accuracy <=1 m, RS485/dry contact to DCIM, under CRAC leak monitoring.

Anchor: KITOZER · KITOZER Products

Contact Us

KITOZER Brand
Tel/WeChat: +86 13922289957 | +86 18520668845
WHATSAPP:+86 19068534140
Web: lain.com.cn | gdlain.com

Shopping Cart