Table of Contents
ToggleI. Introduction to KITOZER Modular Cold Aisle Cooling System
1.1 System Definition & Industry Background
With the rapid development of the digital economy, data centers serve as the core computing infrastructure supporting cloud computing, artificial intelligence, big data, 5G communications and other critical businesses. Servers, switches and other IT equipment operate 24/7 and generate massive heat, which becomes a core pain point threatening the safe, stable and efficient operation of data centers. Industry statistics show that cooling systems account for 40%–60% of the total energy consumption of traditional data centers. More than 30% of cooling capacity is wasted due to disordered mixing of cold and hot airflows, short-circuit circulation and bypass leakage. This not only drives up electricity costs for computer room operation, but also easily creates local hotspots, triggering server outages and shortening hardware service life.
The KITOZER Modular Cold Aisle Cooling System is a new-generation core airflow management and precision cooling solution independently developed by our company, complying with authoritative domestic and international standards including GB 50174-2017 Code for Design of Data Centers, GB/T 41783-2022 Technical Requirements for Cold Aisle Containment Assemblies of Data Centers, and TIA-942 Telecommunications Infrastructure Standard for Data Centers. The core technical logic relies on physical isolation of cold and hot airflows, directional circulation and on-demand cooling. A fully enclosed cold air static pressure plenum is built on the air intake side of face-to-face arranged cabinets, restraining low-temperature cold air of 16–22°C output by air conditioning systems within the cold aisle. Cold air is forced to flow only through preset paths—front cabinet grille openings to vertically enter IT equipment for heat exchange. Heated hot air is exhausted from the rear of cabinets into hot aisles and circulated back to air conditioning return air outlets, forming a complete closed-loop airflow cycle. This thoroughly eliminates cooling capacity waste caused by cold-hot airflow mixing, fundamentally boosts cooling efficiency and reduces data center PUE.
1.2 Core System Value & Industry Significance
1.2.1 Extreme Energy Saving & Cost Reduction to Support Dual Carbon Goals
Compared with traditional open computer room layouts, the KITOZER enclosed cold aisle system improves cooling efficiency by over 40% and cuts cooling energy consumption by 20%–40%. A provincial data center of a joint-stock bank achieved an annual electricity saving of RMB 5.8 million after renovation, with PUE dropping from 1.58 to 1.32. By combining natural cold sources with the KITOZER cold aisle solution, China Telecom Wenzhou Binhai Data Center attained over 40% annual natural cooling runtime and a PUE of 1.19 with a 35% energy saving rate. It fully meets the mandatory requirement of PUE ≤1.3 for newly built large data centers specified in the National Three-Year Action Plan for New Data Center Development, supporting enterprises’ green and low-carbon transformation.
1.2.2 Eliminate Local Hotspots to Guarantee Stable Equipment Operation
Disordered airflow in traditional computer rooms easily creates overheating hotspots on upper cabinet sections and high-density server zones, resulting in CPU throttling and elevated hard disk failure rates. Adopting a static pressure plenum design, the KITOZER cold aisle system delivers uniform temperature distribution inside the cold aisle, with vertical temperature difference ≤2°C and horizontal temperature difference ≤1°C, completely eliminating local hotspots. IT equipment consistently operates within the ASHRAE-recommended optimal temperature range of 18–27°C. Server hard disk failure rates drop by 40%, and the Mean Time Between Failures (MTBF) of equipment rises by over 60%.
1.2.3 Improve Computer Room Space Utilization to Support High-Density Deployment
Traditional air-cooled computer rooms are limited to a single cabinet power density of 3–5 kW, beyond which heat dissipation becomes insufficient. With precision cooling, the KITOZER cold aisle system supports medium-density deployment of 8–15 kW per cabinet, 20–30 kW high-density deployment paired with in-row precision air conditioners, and ultra-high-density AI computing clusters exceeding 50 kW when assisted by liquid cooling. The number of deployable cabinets per unit computer room area increases by 25%, significantly boosting space utilization and computing power density of data centers.
1.2.4 Modular Elastic Architecture Adaptable to Full Lifecycle Demands
The entire system adopts a fully modular design with all components prefabricated in factories for rapid on-site assembly, cutting construction cycles by over 40% versus traditional solutions. It supports phased construction and smooth capacity expansion without downtime or disruption to existing services, perfectly matching the full lifecycle demands of data centers from initial construction to later expansion. The system is compatible with all standard 19-inch cabinets of mainstream brands, as well as under-floor air supply, overhead air supply and in-row air conditioning layouts. It enables seamless adaptation for both new computer room construction and legacy computer room retrofits.
1.2.5 Comprehensive Safety Protection Complying with Compliance Audit Requirements
The system integrates multi-layer safety mechanisms including fire linkage, access control, environmental monitoring and emergency escape, satisfying high-level security compliance requirements for finance, government and military industries. The fire linkage system automatically opens aisle skylights within 0.5 seconds upon receiving fire alarm signals to ensure rapid penetration of fire suppression agents into the aisle, fully complying with GB 50116-2013 Code for Design of Automatic Fire Alarm System. The access control system supports multi-authentication methods including facial recognition, card swiping and passwords to realize authority management and full traceability of personnel access. The environmental monitoring system conducts 24/7 real-time full-parameter monitoring with second-level alerts for abnormal conditions, meeting Class 2 Cybersecurity Classified Protection, Tier III/Tier IV and other data center grading certification standards.
1.3 System Design Principles
The R&D and design of the KITOZER Modular Cold Aisle Cooling System strictly adheres to the following core principles to guarantee advanced performance, reliability, safety and applicability:
- Safety First Principle: All designs prioritize safe operation of computer room IT equipment. Fire protection, electrical and structural designs comply with national mandatory standards, equipped with redundant and emergency safeguard mechanisms to eliminate all potential safety hazards.
- Energy Efficiency Core Principle: Centered on reducing data center PUE, the system optimizes airflow organization, enhances sealing performance and adapts intelligent regulation to maximize cooling efficiency and cut cooling energy consumption.
- Modular Standardization Principle: Full-system standardized modular design delivers universal and interchangeable components, supporting rapid installation and flexible expansion while lowering construction and maintenance costs.
- Full-Scenario Adaptation Principle: Customized solutions are provided for distinct scenarios including new computer rooms, legacy retrofits, edge computer rooms, high-density AI computing computer rooms, financial and government computer rooms to meet personalized customer demands.
- Intelligent O&M Principle: An integrated intelligent environmental monitoring system enables real-time data collection, intelligent analysis, abnormal early warning and remote control to reduce O&M difficulty and improve efficiency.
- Compliance Principle: All product design, production and testing strictly follow national and industrial standards, satisfying bidding, grading certification and compliance audit requirements.
- Humanized Design Principle: The aisle clear height, door opening mode, emergency operation and lighting systems conform to human engineering considering operation habits and safety of O&M staff to elevate maintenance experience.
II. Composition of KITOZER Modular Cold Aisle Cooling System
The KITOZER Modular Cold Aisle Cooling System is a complete closed-loop computer room thermal management system composed of five core subsystems: Cold Aisle Containment Main System, Intelligent Control System, Cooling Adaptation System, Environmental Monitoring System and Safety Protection System. All subsystems coordinate to deliver full functions of airflow isolation, precision cooling, intelligent management and safety protection.
2.1 Cold Aisle Containment Main System
The Cold Aisle Containment Main System acts as the core carrier for physical isolation of cold and hot airflows, consisting of four key parts: aisle frame structural components, aisle door assemblies, overhead skylight assemblies and sealing components. All parts adopt factory prefabrication and on-site assembly modular design for easy installation and stable structure.
2.1.1 Aisle Frame Structural Components
The aisle frame forms the load-bearing and supporting backbone of the entire cold aisle system, connecting cabinets on both sides and securing aisle doors and overhead skylights to construct a fully enclosed cold aisle space.
- Core Materials: The main body adopts high-strength SPCC cold-rolled steel plate; support plates and cross beams have a thickness ≥1.5 mm, while other steel sections are ≥1.2 mm thick. High-end customized versions use 6061-T5 high-strength aluminum alloy for lighter weight and superior corrosion resistance.
- Surface Treatment: All steel components undergo full anti-corrosion treatment including degreasing, pickling, phosphating, pure water cleaning and electrostatic powder coating, with coating thickness ≥60 μm. Adhesion reaches Grade 1 per GB/T 9286-1998, delivering acid/alkali resistance, corrosion resistance and fingerprint resistance with uniform color free of sagging, substrate exposure or bubbling defects.
- Structural Design:
- Dual longitudinal keel + transverse support beam frame structure rigidly connected to cabinet tops via special connectors. 25mm grid universal connection holes accommodate standard cabinets of varying widths and depths for flexible, stable installation.
- The overall structure meets Grade 8 and 9 seismic resistance requirements specified in YD5083-2005 Specification for Seismic Performance Testing of Telecommunication Equipment, with static load capacity ≥1,500 kg to support overhead cable trays, lighting and monitoring equipment without permanent deformation.
- Available aisle widths: 1,200 mm, 1,500 mm, 1,800 mm, complying with GB/T 41783-2022 standards. Aisle clear height ≥2,000 mm allows personnel passage and equipment handling; threshold-free design enables unobstructed movement of trolleys and equipment.
- Pre-reserved mounting positions for strong/weak current cable trays, sensors and lighting systems deliver high integration and a neat appearance with all wiring concealed without exposed cables.
2.1.2 Aisle Door Assemblies
Installed at both ends of the cold aisle, aisle doors realize aisle enclosure, personnel access and emergency escape. KITOZER offers three series: manual swing doors, manual sliding doors and automatic sliding doors for diverse scenarios.
(1) Manual Swing Door
- Applicable Scenarios: Small computer rooms, aisles ≤10 m in length with low personnel traffic; cost-effective with simple installation and maintenance.
- Core Structure: Steel door frame embedded with ≥5 mm thick tempered glass (light transmittance ≥85%), opening angle ≥160°, fitted with industrial-grade stainless steel hinges passing 100,000 opening/closing cycle durability testing without damage. EPDM flame-retardant sealing strips line all door edges, with air leakage rate ≤3% when fully closed.
- Safety Configuration: Standard mechanical lock with internal emergency release knob for keyless exit during emergencies. A door closer automatically shuts the door to maintain sealing performance.
(2) Manual Sliding Door
- Applicable Scenarios: Medium-sized computer rooms, aisles 10–20 m long with moderate personnel traffic; space-saving at aisle ends and easy operation.
- Core Structure: Steel/aluminum alloy frame embedded with monolithic ≥8 mm thick tempered glass (frameless design for maximum visibility). Reinforced aluminum guide rails and industrial-grade upper/lower sliding wheels deliver smooth, silent operation without jamming. Buffer guides are installed at closing positions with dual-side sealing strips, air leakage rate ≤2%.
- Safety Configuration: Standard anti-theft mechanical lock with emergency release; optional access control and infrared anti-pinch sensors.
(3) Automatic Sliding Door
- Applicable Scenarios: Large data centers, aisles ≥20 m long with high personnel traffic and high-grade computer room scenarios, featuring high intelligence and superior user experience.
- Core Structure: High-strength aluminum alloy frame embedded with ≥10 mm thick tempered glass complying with impact resistance and fragment state testing standards of GB 15763.2-2005. Driven by brushless DC motors and intelligent microcomputer controllers with adjustable opening/closing speed and hold time, operating noise ≤55 dB.
- Safety Configuration: Standard infrared safety light curtains with anti-pinch rebound function to avoid personnel pinching hazards. Multi-authentication access control (facial recognition + card swiping for entry, push button for exit) and manual emergency release for power outages. Removable door panels with reserved mounting slots for O&M display screens deliver high integration.
- Intelligent Linkage: Links with fire systems to fully open during fire alarms for personnel escape and fire agent penetration; links with lighting systems to activate aisle lights upon door opening with delayed automatic shutoff for energy conservation.
2.1.3 Overhead Skylight Assemblies
Mounted on top of the cold aisle, overhead skylights deliver overhead sealing, fire linkage and lighting. Two categories are available: fixed skylights and flip-type active skylights, with active flip skylights serving as core fire linkage execution components.
(1) Fixed Skylight Assembly
- Core Function: Seals fixed overhead cold aisle areas while maintaining high light transmittance without interfering with original computer room lighting.
- Structure & Materials: Steel frame embedded with ≥4 mm flame-retardant acrylic glass or 5 mm tempered glass (light transmittance ≥85%). Flame-retardant sealant between frame and glass plus EPDM edge sealing strips achieve air leakage rate ≤1%.
- Specifications: Standard width matches cabinet widths (600 mm / 800 mm) with 600 mm length. Modular design enables arbitrary combination with active skylights for flexible adaptation to varying aisle lengths and easy disassembly for maintenance and expansion.
- Customization Option: Integrated LED lighting, cable trays and sensor mounting slots for streamlined installation and higher integration.
(2) Flip-Type Active Fire Linkage Skylight
- Core Function: Remains closed under normal operation to maintain aisle sealing; automatically opens upon receiving fire alarm signals to enable rapid penetration of fire suppression agents and emergency personnel evacuation.
- Structure & Materials: ≥1.5 mm thick SPCC cold-rolled steel frame embedded with ≥5 mm tempered glass with explosion-proof film, flame retardancy UL94 V-0 grade. Industrial-grade stainless steel rotating shafts pass 100,000 flip cycle testing without jamming.
- Drive & Control: DC24V safety voltage electromagnetic lock with adsorption force ≥500 N to hold skylights closed under normal power supply. Upon receiving passive dry contact fire signals, power is cut within 0.5 seconds, allowing skylights to flip open by gravity at an angle ≥90°. Single skylight opening area ≥0.36 m², with total overhead opening area no less than 30% of the ceiling surface to fully satisfy fire code requirements.
- Safety Configuration: Each skylight is fitted with an on-site manual emergency release button for tool-free opening during crises. Skylights can be manually reset after opening, and real-time open/closed status feedback is transmitted to the environmental monitoring system.
- Control Modes: Supports active/passive fire signal input and three control modes (fire linkage, local manual control, remote control) with priority ranking: Fire Signal > Manual Control > Remote Control to guarantee fire instructions are executed first during emergencies.
2.1.4 Sealing Components
Sealing components form the critical auxiliary materials preventing cooling capacity leakage by realizing full-circuit sealing of the cold aisle, delivering overall static air leakage rate ≤3% (≤1% for flagship premium models).
- Sealing Strips: EPDM flame-retardant sponge sealing strips (UL94 V-0 flame retardancy) installed at all door, skylight and frame joints, operating stably from -40°C to +120°C with anti-aging performance and ≥10-year service life. Self-adhesive design ensures tight fitting and superior sealing.
- Cabinet Gap Sealing Kits: Customized sealing accessories including brush strips, sponge seal strips and L-shaped baffles block gaps between cabinets, cabinets and floors, and cabinets and overhead frames to eliminate cooling leakage.
- Cabinet Blanking Panels: Standard 1U/2U/4U 19-inch ABS flame-retardant blanking panels with snap-fit tool-free installation to block empty cabinet U-slots and avoid cold air bypass leakage from vacant equipment positions, boosting internal cabinet cold air utilization efficiency.
- Cable Penetration Sealing Assemblies: Brush-equipped cable penetration plates minimize air gaps while allowing routing of strong/weak current cables through the cold aisle barrier.
2.2 Intelligent Control System
Acting as the “brain” of the entire system, the KITOZER Cold Aisle Intelligent Control System manages fire linkage, aisle door operation, lighting control and status monitoring/feedback. It adopts standardized modular design with stable performance and strong expandability.
- Integrated Aisle Control Unit (Main Controller)
- Installation: Standard 19-inch 3U rack-mountable for direct cabinet installation with standardized plug-and-play ports for easy expansion and maintenance.
- Power Supply: Wide-range AC220V input (150–245 V) with dual redundant power supply and standard UPS backup power interface, sustaining core control functions for ≥2 hours during power outages.
- Core Interfaces: Standard AC220V power output, DC24V safety voltage output, dual fire control ports, passive/active fire signal input, skylight control, lighting control, door control, dry contact status feedback, RS485/RS232 communication ports for seamless integration with environmental monitoring and BMS systems.
- Core Functions: Centralized control of all skylights, fire signal reception and execution, aisle door and lighting management, real-time equipment status monitoring, abnormal alarms and data upload. Supports simultaneous control of up to 128 skylight units with cascading expansion capability.
- Human-Machine Interaction Unit
- Standard 7-inch / 10-inch / 21.5-inch industrial touch screens with 1920*1080 resolution, ARM Cortex-A17 1.8 GHz processors and embedded Android/Linux operating systems delivering smooth, responsive operation.
- Real-time display of full parameters including aisle temperature/humidity, skylight status, door status, lighting state and fire signal conditions. Supports local manual control of skylight opening/reset, lighting switching and door operation, plus parameter configuration, permission management and alarm record query functions.
- Fire Linkage Control Module
- Hardware-level fire linkage independent of software intervention. Upon receiving dry contact fire alarm signals, power to all skylight electromagnetic locks is cut via hardware circuits within 0.5 seconds to eliminate failure risks caused by software malfunctions.
- Supports fire signal circuit detection, automatically triggering alarms for open/short-circuited fire wiring to ensure fire circuits remain functional at all times.
- Transmits real-time fire linkage execution status feedback to fire control rooms and environmental monitoring systems.
- Lighting & Access Control Module
- Lighting Control: Multiple modes including human body infrared induction, door linkage, timing switching and manual control to realize “lights on when personnel enter, lights off after personnel leave” energy-saving operation with customizable delay-off durations.
- Access Control: Multi-authentication support for facial recognition, card swiping, passwords and fingerprints, capable of managing ≥10,000 user profiles and storing ≥100,000 access records with query functionality. Links with environmental monitoring systems to trigger automatic alarms and video capture for unauthorized entry.
2.3 Cooling Adaptation System
The KITOZER cold aisle system seamlessly adapts to diverse cooling methods, delivering customized cooling matching solutions for distinct computer room scenarios and power densities to maximize cooling efficiency.
- Under-Floor Air Supply Adaptation Solution
- Applicable Scenarios: Medium/low-density computer rooms with single cabinet power ≤8 kW, newly built standardized computer rooms with sufficient raised floor height.
- Adaptation Design: Adjustable air supply louvers are installed at raised floor positions corresponding to the cold aisle, with adjustable opening sizes and quantities calibrated to cabinet power density for uniform cold air distribution. The floor static pressure plenum is fully sealed to block floor gaps and cable penetrations, maintaining stable plenum static pressure and precise cold air delivery into the cold aisle.
- Compatible Equipment: Room-level precision air conditioners, air-cooled chillers and water-cooled chillers.
- In-Row Air Conditioner Horizontal Air Supply Adaptation Solution
- Applicable Scenarios: Medium/high-density computer rooms with single cabinet power 8–30 kW, AI computing computer rooms, computer rooms without raised floors or insufficient floor height, legacy computer room renovation projects.
- Adaptation Design: In-row air conditioners are installed side-by-side with cabinets within the cold aisle, supplying air forward into the cold aisle and returning hot air backward to air conditioner intake ports. Supply distance is limited to 2–6 m with low air resistance for high cooling efficiency, independent of air ducts and flexible deployment.
- Compatible Equipment: KITOZER series in-row precision air conditioners (air-cooled, chilled water, fluorine pump natural cooling variants optional), supporting N+1/N+X redundancy and group control management for on-demand cooling and further energy consumption reduction.
- Overhead Duct Air Supply Adaptation Solution
- Applicable Scenarios: Legacy computer room renovations without raised floors, computer rooms with sufficient ceiling height and small-scale computer rooms.
- Adaptation Design: Air supply ducts deliver cold air directly into overhead cold aisle static plenums with variable air volume louvers dynamically adjusting airflow according to cabinet loads to realize precision air supply and avoid cooling waste.
- Rear Door Heat Exchanger Air Conditioner Adaptation Solution
- Applicable Scenarios: Ultra-high-density AI computing computer rooms with single cabinet power 20–50 kW and GPU server clusters.
- Adaptation Design: Rear door heat exchangers are mounted on cabinet rear panels. Cold air enters cabinet fronts, absorbs heat from servers and is immediately cooled by rear door heat exchangers to realize cabinet-level precision heat dissipation, completely eliminating hotspots and maximizing cooling efficiency when paired with cold aisle containment.
- Natural Cold Source Adaptation Solution
- Applicable Scenarios: Northern regions with extended annual natural cooling runtime and large data centers pursuing ultra-low PUE.
- Adaptation Design: Fully compatible with indirect evaporative cooling, fluorine pump natural cooling and water-side natural cooling systems. Cold aisle containment extends natural cooling utilization hours, minimizing compressor operation time to achieve extreme energy savings.
2.4 Environmental Monitoring System
The KITOZER cold aisle supporting environmental monitoring system delivers 24/7 comprehensive real-time monitoring, intelligent analysis, abnormal early warning and remote control for cold aisles and computer room environments, providing full safeguards for stable operation. Adopting B/S architecture, it supports remote access via PC and mobile terminals for centralized full-view management.
- Core Monitoring Units
- Temperature & Humidity Monitoring: Multi-point temperature/humidity sensors deployed inside cold aisles, cabinet air intake/outlet vents and hot aisles with measurement accuracy ±0.3°C (temperature) / ±2%RH (humidity). Sampling frequency configurable from 1 s to 300 s for real-time temperature field distribution monitoring and second-level abnormal hotspot alerts.
- Air Quality Monitoring (Optional): PM2.5, COâ‚‚ and VOC sensors track indoor air quality to protect O&M staff health.
- Water Leakage Monitoring: Positioned/non-positioned water leak detection cables deployed around cold aisles and under air conditioners paired with leak alarm controllers for real-time monitoring and location identification of water leakage events with response time ≤2 s to eliminate flooding risks.
- Smoke Monitoring: Photoelectric smoke sensors mounted on cold aisle ceilings and inside cabinets paired with temperature sensors for early fire warning and fire system linkage.
- Access & Security Monitoring: Real-time tracking of door open/closed status and personnel access records; optional video surveillance cameras and infrared intrusion detectors trigger automatic alarms and video capture for unauthorized entry.
- Equipment Status Monitoring: Real-time tracking of skylight open/closed status, electromagnetic lock operation, air conditioner runtime and power distribution parameters to fully grasp equipment operating conditions.
- Core System Functions
- Real-Time Data Collection & Display: 3D visualization interfaces render real-time data and equipment status with customizable dashboards for intuitive data presentation.
- Multi-Tier Alarm Function: Four configurable alarm severity levels with customizable thresholds and delivery methods including pop-up window alerts, audible/visual alarms, SMS, phone calls, email and APP push notifications to ensure timely alert delivery.
- Data Storage & Traceability: Historical data stored for ≥1 year, alarm records stored for ≥3 years with full historical data query, report generation and export functionality to meet compliance audit requirements.
- Intelligent Linkage Control: Temperature/humidity linkage with air conditioning systems to dynamically adjust air volume and set temperatures based on internal aisle temperature; access control linkage with lighting and video surveillance; full-chain linkage between fire signals and skylights, doors, air conditioners and power distribution systems.
- Remote Management & Permission Control: Multi-user hierarchical permission management assigning distinct operation authorities to different users, supporting remote access, control and firmware upgrades without on-site visits for routine maintenance.
- Fault Early Warning & Diagnosis: AI algorithms analyze equipment operation trends to identify potential failure risks in advance and enable predictive maintenance to reduce equipment failure rates.
- System Compatibility
- Supports standard communication protocols including Modbus-RTU, Modbus-TCP, SNMP and BACnet for seamless integration with all mainstream precision air conditioners, UPS, power distribution cabinets, fire systems and BMS building management systems.
- Compatible with upper-level centralized environmental monitoring platforms to satisfy centralized management demands of large-scale data centers.
2.5 Safety Protection System
The KITOZER cold aisle system constructs an all-dimensional safety protection framework covering fire safety, electrical safety, personnel safety and equipment safety to meet high-grade computer room compliance requirements.
- Fire Safety Protection System
- Hardware-level fire linkage: Independent hardware fire linkage circuits unaffected by system software or power failures, automatically opening all active skylights within 0.5 seconds upon fire alarms to enable fire suppression agent penetration.
- Fire status monitoring: Real-time tracking of fire signal circuits and skylight actuators with immediate alarms for abnormal conditions to guarantee continuous fire system availability.
- Flame-retardant materials: All non-metallic components adopt UL94 V-0 flame-retardant materials to eliminate ignition risks, complying with GB 50174-2017 fire protection requirements.
- Emergency escape design: All aisle end doors support keyless internal emergency release; active skylights feature on-site manual emergency opening to enable rapid personnel evacuation during crises.
- Electrical Safety Protection System
- Safe voltage design: All actuators and sensors operate on DC24V safe voltage to eliminate electric shock hazards.
- Redundant power supply design: Control systems support dual power input with standard UPS backup power interfaces to sustain core functions during power outages.
- Electrical protection: Short-circuit, overload and leakage protection fitted on all electrical circuits; all metal components reliably grounded with grounding resistance ≤4 Ω complying with GB 50054-2011 Code for Design of Low-Voltage Electrical Installations.
- Electromagnetic compatibility: The system passes full EMC testing with strong anti-interference performance, eliminating electromagnetic interference with computer room IT equipment and complying with the GB/T 17626 series standards.
- Personnel Safety Protection System
- Anti-pinch design: Automatic sliding doors are equipped with infrared anti-pinch devices that rebound upon obstacle contact to avoid personnel pinching injuries.
- Emergency release: All doors and skylights feature emergency release mechanisms for tool-free opening during crises to guarantee evacuation.
- Threshold-free design: No thresholds at aisle ends eliminate tripping hazards and simplify trolley and equipment transit.
- Emergency lighting: Standard emergency lighting systems sustain ≥90 minutes of illumination during power outages to ensure safe personnel passage during emergencies.
- Equipment Safety Protection System
- Structural safety: The overall frame meets Grade 8 and 9 seismic resistance standards with static load capacity ≥1,500 kg to eliminate collapse risks.
- Tempered glass protection: All glass components are tempered; active skylight glass is fitted with explosion-proof film to prevent flying fragments if broken, protecting equipment and personnel.
- Access control management: Access control systems enforce personnel access authority management to block unauthorized entry and avoid equipment failures caused by human operational errors.
- Video surveillance (Optional): 24/7 video recording of aisle interior with full traceability.
III. Classification of KITOZER Modular Cold Aisle Cooling Systems
KITOZER provides a full range of cold aisle products customized for distinct computer room scenarios, power densities and construction demands, categorized by containment form, application scenario, structural material and intelligence level to fully cover small edge computer rooms up to ultra-large cloud data centers.
3.1 Classification by Containment Form (Core Classification Standard)
Based on containment completeness and airflow isolation methods, systems are divided into fully enclosed cold aisles, semi-enclosed cold aisles and open cold aisles—the mainstream industry classification framework.
3.1.1 Fully Enclosed Cold Aisle System (Flagship Model)
The flagship core product of KITOZER and the most widely adopted solution for newly built data centers (72% adoption rate for 2025 new data centers). A fully sealed cold air static pressure plenum is formed via fully enclosed overhead skylights, fully sealed end doors and adjacent cabinets to achieve complete physical isolation of cold and hot airflows.
- Core Features
- Optimal sealing performance: Overall static air leakage rate ≤3% (≤1% for premium flagship variants) for maximum cold air utilization efficiency, capable of reducing data center PUE below 1.3 (as low as 1.15 when paired with natural cold sources).
- Highest temperature control precision: Uniform temperature distribution inside cold aisles with vertical/horizontal temperature difference ≤2°C, precisely regulating cold aisle temperature at 18–22°C to completely eliminate local hotspots and support ultra-high-density deployment up to 50 kW per cabinet.
- Most comprehensive safety protection: Integrated complete fire linkage, access control, environmental monitoring and emergency escape safety systems, satisfying high security grade compliance requirements for finance, government and military industries.
- Highest intelligence level: Full intelligent linkage with air conditioning, power distribution and fire systems to realize on-demand cooling and refined management reducing O&M difficulty.
- Applicable Scenarios
- New large/ultra-large data centers and cloud service provider IDC computer rooms
- AI computing centers, GPU server clusters and medium/high-density computer rooms with single cabinet power ≥8 kW
- Financial, securities, insurance and provincial-level government cloud computer rooms with strict stability and compliance requirements
- Green data centers pursuing extreme energy efficiency and low PUE
- Limitations
- Slightly higher upfront investment versus semi-enclosed variants
- Certain requirements for computer room ceiling height and consistent cabinet layout
3.1.2 Semi-Enclosed Cold Aisle System (Cost-Effective Model)
A high-value retrofit solution designed for legacy computer rooms with irregular cabinet layouts and limited budgets. Partial overhead cold aisle sealing plus fully enclosed end doors deliver partial cold-hot airflow isolation balancing energy-saving performance, renovation costs and construction flexibility.
- Core Features
- Low renovation cost: No large-scale rework of original computer room layouts or cabinets; phased non-stop construction without disrupting existing business operations.
- Strong flexibility: Adapts to irregular cabinet layouts and mixed brands/specifications of cabinets with high customization; partial sealing schemes designed per actual computer room conditions.
- Significant energy-saving performance: Improves cooling efficiency by 20%–30% versus traditional open computer rooms, reducing PUE below 1.4 with high return on investment (ROI), typically recovering renovation costs within 1.5–2 years.
- Easy installation & maintenance: Modular design supports zone-by-zone phased renovation and seamless future upgrade to fully enclosed cold aisle configuration.
- Applicable Scenarios
- Legacy computer room energy-saving renovation projects operating over 5 years
- Computer rooms with irregular layouts and mixed cabinet specifications
- Small/medium enterprise computer rooms with limited budgets prioritizing cost performance
- Medium/low-density computer rooms with single cabinet power 3–8 kW
- Online business computer rooms requiring non-stop renovation
- Limitations
- Inferior sealing and energy-saving performance compared to fully enclosed solutions
- Limited adaptability for ultra-high-density scenarios; not recommended for single cabinet power exceeding 10 kW
3.1.3 Open Cold Aisle System (Entry-Level Basic Model)
No physical containment structures; cold/hot aisle zones are merely defined by rearranging cabinet face-to-face/back-to-back layouts to optimize airflow organization—the most fundamental cold aisle solution for low-density, ultra-low budget small computer rooms.
- Core Features
- Minimum cost: No additional containment structure investment, only cabinet position adjustment required for basic airflow optimization.
- Simplest construction: No complex installation work; airflow optimization realized solely by rearranging cabinet placement.
- No space restrictions: No special ceiling height or cabinet specification requirements, compatible with all small computer room scenarios.
- Applicable Scenarios
- Low-density small computer rooms with single cabinet power ≤3 kW
- Branch office and edge node micro computer rooms
- Entry-level initial construction computer rooms with ultra-limited budgets
- Limitations
- Severe residual cold-hot airflow mixing with limited energy efficiency improvement of only 10%–15%
- Unable to eliminate local hotspots or support medium/high-density deployment
- No safety protection or intelligent control functions with weak compliance performance
3.2 Classification by Application Scenario
Scene-customized product series are developed to match unique demands across distinct industries and deployment environments:
3.2.1 Standard Data Center Dedicated Cold Aisle System
- Core Positioning: Standardized products for operators, third-party IDCs and large enterprise data centers with full modular design supporting rapid large-scale deployment, compatible with standard 19-inch cabinets and mainstream cooling methods.
- Core Features: High standardization and component interchangeability supporting phased construction and smooth expansion, equipped with complete fire linkage and environmental monitoring systems complying with national/industrial standards to satisfy bidding and grading certification requirements.
- Compatible Specifications: Supports ultra-long aisles of 10–100 cabinets with optional aisle widths of 1,200/1,500/1,800 mm, fitting 600/800 mm wide standard cabinets.
3.2.2 AI Computing Center High-Density Dedicated Cold Aisle System
- Core Positioning: For AI training clusters, GPU servers and High-Performance Computing (HPC) ultra-high-density scenarios with single cabinet power support of 20–50 kW to resolve heat dissipation challenges from extreme heat flux density.
- Core Features: Reinforced sealing structure with air leakage rate ≤1%, optimized static pressure plenum design for uniform cold air distribution, compatible with in-row air conditioners, rear door heat exchangers and cold plate liquid cooling hybrid cooling solutions. Built-in multi-point high-precision temperature/humidity monitoring to identify hotspots in real time and intelligently link cooling systems for dynamic adjustment.
- Customization Options: Custom widened aisles, reinforced load-bearing frames, air-liquid hybrid cooling adaptation structures and high-density cabinet linkage schemes available.
3.2.3 Edge Computing Integrated Cold Aisle System
- Core Positioning: Distributed edge scenarios including 5G base station edge nodes, industrial internet edge computer rooms, financial branches, medical clinics and retail outlets with constrained space and absence of dedicated O&M personnel.
- Core Features: High integration integrating cabinets, cold aisle containment, power distribution, cooling and environmental monitoring into a single plug-and-play unit with small footprint suitable for office environment deployment, supporting unattended O&M and low noise stable operation.
- Optional Specifications: Compact sizes for 3/6/10 cabinets with floor-mounted and wall-mounted deployment options.
3.2.4 Legacy Computer Room Renovation Dedicated Cold Aisle System
- Core Positioning: Customized renovation solutions for aging legacy computer rooms featuring inconsistent cabinet specifications, irregular layouts, absent raised floors and mandatory non-stop renovation without business disruption.
- Core Features: Flexible modular design compatible with mixed brands, specifications and vintages of cabinets, eliminating large-scale rework of original computer room structures and equipment. Zone-by-zone non-stop construction delivers low renovation costs and short cycles with seamless future upgrade capability.
- Supporting Services: Full-process services including on-site surveys, thermal imaging scanning, airflow organization simulation, scheme design, installation and commissioning validation to guarantee renovation performance targets.
3.2.5 Financial & Government High-Security Dedicated Cold Aisle System
- Core Positioning: Bank, securities, insurance, government and military scenarios with stringent security grading, compliance and confidentiality requirements.
- Core Features: Compliant with Classified Protection of Cybersecurity, Classified Protection of Secret Information Systems and Tier IV highest-grade standards. Adopts national cryptographic algorithm access control, encrypted environmental monitoring, anti-intrusion security and enhanced electromagnetic shielding design. All products pass authoritative domestic testing certification with complete compliance audit documentation.
- Customization Services: Optional shielded cold aisles, partitioned authority management, multi-factor authentication and fully traceable audit logs for advanced security functions.
3.2.6 Containerized/Modular Prefabricated Data Center Dedicated Cold Aisle System
- Core Positioning: Containerized and prefabricated modular data center scenarios with deep integration with cabin structures, factory pre-assembled and commissioned for plug-and-play on-site deployment.
- Core Features: Precisely matched to container/prefabricated cabin dimensions with rigid structural connection to cabin bodies, resistant to vibration and impact during transportation and hoisting, with anti-seismic, moisture-proof and dust-proof properties suitable for harsh outdoor environments. Factory pre-assembly enables rapid commissioning post on-site water/electricity connection.
3.3 Classification by Structural Material
3.3.1 Steel Cold Aisle System
- Core Materials: Entire main structure fabricated from premium SPCC cold-rolled steel plate (1.2–2.0 mm thickness) with high structural strength and load-bearing capacity at moderate cost, the mainstream material solution currently deployed.
- Core Features: Stable seismic performance, high customizability and diverse surface treatment options with superior cost performance suitable for nearly all indoor computer room scenarios.
- Surface Treatment: Degreasing, pickling, phosphating and electrostatic powder coating with customizable colors (default black matte matching standard cabinet finishes).
3.3.2 Aluminum Alloy Cold Aisle System
- Core Materials: 6061-T5 high-strength aluminum alloy extrusions for main frame lightweight construction (1/3 the weight of steel variants) with exceptional anti-corrosion and rust-proof performance.
- Core Features: Light weight minimizing cabinet load pressure, easy installation, premium visual aesthetics and superior corrosion resistance suitable for humid environments, high-grade computer rooms and premium customized projects.
- Surface Treatment: Anodizing, sandblasting and electrophoresis options delivering wear and corrosion resistance with ≥15-year service life.
3.3.3 Steel-Aluminum Hybrid Cold Aisle System
- Core Materials: Load-bearing frames adopt steel construction while door and skylight frames use aluminum alloy, balancing structural strength, lightweight design and visual aesthetics.
- Core Features: Optimized balance of cost, structural strength and appearance with superior cost performance, combining steel structural stability with aluminum alloy aesthetics and corrosion resistance as the preferred solution for mid-to-high-end projects.
3.4 Classification by Intelligence Level
3.4.1 Basic Cold Aisle System
- Core Configuration: Cold aisle containment main structure, manual doors, fixed skylights + basic fire linkage skylights; no intelligent control or environmental monitoring systems.
- Core Features: Lowest cost with fundamental airflow isolation and fire linkage functionality for small computer rooms and ultra-limited budget projects.
- Expandability: Intelligent control and environmental monitoring modules can be retrofitted later for smooth upgrade to intelligent variants.
3.4.2 Standard Intelligent Cold Aisle System
- Core Configuration: Cold aisle containment main structure, automatic sliding doors, fire linkage skylights, integrated control unit, 10-inch touch screen HMI, basic temperature/humidity/water leak/smoke monitoring and access control systems.
- Core Features: Complete intelligent control and environmental monitoring functionality delivering fire linkage, intelligent access control, environmental monitoring, abnormal alerts and remote management, the mainstream selection for medium/large-scale projects.
3.4.3 Flagship AI Intelligent Cold Aisle System
- Core Configuration: Upgraded AI intelligent management platform, 3D visualization O&M, multi-point high-precision thermal distribution monitoring, AI predictive maintenance, deep intelligent linkage with air conditioning and power distribution systems, and digital twin functionality built upon standard intelligent configurations.
- Core Features: Full-process intelligent O&M leveraging AI algorithms to realize on-demand cooling, fault early warning and energy consumption optimization, minimizing energy use and O&M labor costs for ultra-large data centers and premium AI computing centers.
IV. Working Principle & Schematic Diagrams of KITOZER Modular Cold Aisle Cooling System
4.1 Core System Operating Principle
Built upon the Second Law of Thermodynamics and Bernoulli’s Equation, the core operating principle of the KITOZER Modular Cold Aisle Cooling System relies on physical isolation to construct independent cold and hot airflow circulation channels, eliminating disordered cold-hot mixing in traditional computer rooms to realize “on-demand cooling, precision heat exchange and closed-loop circulation” and maximize cooling system energy efficiency. The complete closed-loop airflow cycle operates through four core stages:
- Cold Air Static Pressure Plenum Construction: A fully sealed cold air static pressure plenum is built on the air intake side of face-to-face arranged cabinets. Low-temperature cold air of 16–22°C output by air conditioning systems is confined within this sealed plenum to form a stable positive pressure environment, preventing cold air diffusion into other computer room zones.
- Directional Cold Air Delivery: Driven by pressure differential, positive-pressure cold air within the static plenum flows exclusively through front cabinet grille openings vertically into cabinet interiors, forced to pass through heat-generating components of servers and switches for heat exchange. Cold air short-circuiting and bypass leakage are completely blocked to realize 100% effective cold air utilization.
- Centralized Hot Air Exhaust: After absorbing heat from IT equipment, cold air warms to 30–35°C and becomes high-temperature hot air exhausted from cabinet rear outlets into back-to-back hot aisles (open or enclosed structures). Driven by buoyancy and air conditioner return negative pressure, hot air flows centrally and directionally back to air conditioner return air outlets without diffusing into cold aisles or other computer room areas.
- Circulating Cooling & Intelligent Regulation: Hot air returning to air conditioners is cooled by evaporators to regenerate low-temperature cold air re-delivered into cold aisles, forming a complete closed-loop airflow cycle. Simultaneously, the environmental monitoring system tracks real-time parameters including cold aisle temperature/humidity, hot aisle temperature and cabinet air intake/exhaust temperature differential, intelligently linking air conditioning systems to dynamically adjust air volume and supply temperature based on actual IT equipment heat load to realize “cold air volume follows load” on-demand cooling and further reduce cooling energy consumption.
4.2 In-Depth Explanation of Core Technical Principles
4.2.1 Static Pressure Plenum Equalization Technology
In traditional computer rooms, cold air diffuses across the entire room space with uneven pressure distribution, leading to drastically varying air intake volumes between different cabinets and vertical cabinet positions, creating insufficient upper cabinet airflow and hotspots. The KITOZER cold aisle sealed static pressure plenum design delivers uniform static pressure distribution inside aisles with vertical static pressure differential ≤5 Pa and horizontal static pressure differential ≤3 Pa, guaranteeing consistent air intake volume across every cabinet and vertical position to resolve vertical cabinet temperature differentials and achieve uniform full-aisle temperature distribution.
4.2.2 Airflow Short-Circuit Blocking Technology
Over 30% of cold air in traditional computer rooms bypasses IT equipment entirely, flowing directly back to air conditioner return air outlets through cabinet gaps and ceiling spaces to form airflow short-circuiting and severe cooling waste. The KITOZER cold aisle full-circuit sealing design achieves complete physical separation of cold and hot airflows, mandating cold air pass through IT equipment heat exchange before returning to air conditioner intake ports to fully block airflow short-circuiting and raise air conditioner sensible heat ratio above 0.95 for maximum cooling efficiency.
4.2.3 Return Air Temperature Elevation Technology
Cold-hot mixing in traditional computer rooms limits air conditioner return air temperature to only 22–24°C, resulting in low air conditioner evaporation temperatures and poor Energy Efficiency Ratio (EER). The KITOZER cold aisle system concentrates hot air return to raise air conditioner return air temperature to 30–35°C. Per refrigeration principles, each 1°C rise in return air temperature boosts air conditioner EER by 3%–4%, drastically improving air conditioner operating efficiency and reducing compressor power consumption for significant energy savings.
4.2.4 Fire Linkage Safety Principle
Cold aisle containment necessitates a solution enabling fire suppression agent penetration into enclosed aisles. KITOZER adopts a “normally closed electromagnetic lock + gravity flip skylight” fire linkage mechanism: under normal operation, DC24V electromagnetic locks remain powered to secure skylights closed and maintain aisle sealing. During fires, fire alarm signals trigger hardware-level power cut-off to electromagnetic locks, allowing skylights to flip open automatically by gravity with total overhead opening area ≥30% to enable rapid, uniform penetration of FM200, IG541 or water mist fire suppression agents for fire suppression, fully complying with fire code requirements. This passive trigger design functions normally even during complete computer room power outages to guarantee fire safety.
4.3 System Schematic Diagrams
- Cold Aisle Airflow Circulation Principle Schematic
- Cold Aisle System Structural Schematic
- Under-Floor Air Supply Cold Aisle Operating Principle Schematic
- In-Row Air Conditioner Cold Aisle Operating Principle Schematic
- Fire Linkage System Control Schematic
- Normal Operating State: No alarm signal from fire control host → Fire linkage module maintains electromagnetic lock power supply → Skylights closed, cold aisle sealed for standard cooling operation.
- Fire Alarm State: Fire control host outputs dry contact alarm signal → Fire linkage module hardware cuts power to all electromagnetic locks → Skylights flip open automatically by gravity → Fire suppression agents penetrate cold aisle for fire suppression → Status signals fed back to fire host and environmental monitoring systems.
- Emergency Operation State: On-site personnel press manual emergency release button → Electromagnetic lock power cut → Skylights open for local emergency control.
- Remote Control State: O&M staff send open commands remotely via environmental monitoring systems → Control unit cuts electromagnetic lock power → Skylights open for remote emergency operation. Note: Fire signals carry highest priority; skylights immediately open upon fire signal reception regardless of active manual or remote control commands.
V. Full-Series Configuration Lists of KITOZER Modular Cold Aisle Cooling System
KITOZER provides three tiered complete configuration packages for distinct customer budgets, scenarios and power density demands: Economy (Entry-Level), Standard (Mid-Range Mainstream) and Flagship (High-End Customized). All products are genuine KITOZER brand, adjustable flexibly per actual cabinet quantities, aisle lengths and customization requirements. Below are standard configuration lists for a 10-cabinet double-row cold aisle, directly applicable to bidding projects.
5.1 Economy (Entry-Level) Cold Aisle System Configuration List (10-Cabinet Double-Row)
Applicable Scenarios: Small/medium enterprise computer rooms, branch office computer rooms, low-density environments with single cabinet power ≤5 kW, new construction/renovation projects with limited budgets; core functionality delivers basic airflow isolation and fire linkage with superior cost performance.
è¡¨æ ¼
| No. | Product Name | Model Specification | Qty | Unit | Brand | Technical Parameters & Remarks |
|---|---|---|---|---|---|---|
| 1 | Cold Aisle Longitudinal Load-Bearing Keel | KTZ-LD-LG-600 | 20 | pc | KITOZER | Premium SPCC cold-rolled steel plate ≥1.5 mm thick, length 600 mm, rigidly connected to cabinet tops, electrostatic powder coated black matte finish for 600 mm wide standard cabinets |
| 2 | Cold Aisle Transverse Support Beam | KTZ-LD-HL-1200 | 11 | pc | KITOZER | Premium SPCC cold-rolled steel plate ≥1.5 mm thick, length 1,200 mm for 1,200 mm aisle width, rigidly connected to longitudinal keels, electrostatic powder coated black matte finish |
| 3 | Fixed Sealing Skylight | KTZ-LD-TC-GD-600 | 6 | set | KITOZER | Steel frame ≥1.2 mm thick embedded with 4 mm flame-retardant acrylic glass, light transmittance ≥85%, 600*600 mm dimensions with EPDM flame-retardant sealing strips, air leakage rate ≤1%, snap-fit frame mounting |
| 4 | Fire Linkage Flip Skylight | KTZ-LD-TC-XF-600 | 5 | set | KITOZER | Steel frame ≥1.5 mm thick embedded with 5 mm tempered glass, DC24V electromagnetic lock with adsorption force ≥500 N, auto-open within 0.5 s upon fire signals, opening angle ≥90°, manual emergency release button, 600*600 mm dimensions |
| 5 | Cold Aisle Manual Swing Door | KTZ-LD-M-PK-1200 | 2 | leaf | KITOZER | Steel door frame embedded with 5 mm tempered glass, single door size 1,200*2,000 mm, opening angle ≥160°, stainless steel hinges, door closer, mechanical lock with internal emergency release, full-perimeter EPDM sealing strips, air leakage rate ≤3% |
| 6 | Integrated Aisle Control Unit | KTZ-LD-KZ-3U | 1 | unit | KITOZER | Standard 19-inch 3U rack-mountable, AC220V input, DC24V output, passive fire signal input support, controls up to 32 skylights, fire linkage and manual control functionality, standard RS485 communication port |
| 7 | Aisle LED Lighting System | KTZ-LD-ZM-12W | 2 | set | KITOZER | 12 W DC24V cool white LED strip lights, illuminance ≥300 lux, manual switches mounted on overhead frames with concealed wiring |
| 8 | Temperature & Humidity Sensor | KTZ-LD-WS-01 | 2 | pc | KITOZER | Measurement range -20~+80°C, 0–100%RH, accuracy ±0.5°C / ±3%RH, RS485 communication, 2 units installed at both aisle ends |
| 9 | Full-Circuit Sealing Kit | KTZ-LD-MF-10G | 1 | set | KITOZER | Includes cabinet gap sealing strips, EPDM sealing strips, 20 pcs of 1U cabinet blanking panels, cable penetration sealing plates to block all aisle gaps |
| 10 | Standard Connectors & Fasteners | KTZ-LD-LJ-10G | 1 | set | KITOZER | Complete installation auxiliary materials including cabinet connection bolts, frame connectors, grounding bolts, flat/spring washers, all 304 stainless steel anti-corrosion hardware |
5.2 Standard (Mid-Range Mainstream) Cold Aisle System Configuration List (10-Cabinet Double-Row)
Applicable Scenarios: Medium/large enterprise computer rooms, provincial government computer rooms, operator edge computer rooms, medium-density environments with single cabinet power 5–15 kW; mainstream bidding configuration delivering complete intelligent control, environmental monitoring and safety protection complying with industrial standards and compliance requirements.
è¡¨æ ¼
| No. | Product Name | Model Specification | Qty | Unit | Brand | Technical Parameters & Remarks |
|---|---|---|---|---|---|---|
| 1 | Cold Aisle Longitudinal Load-Bearing Keel (PRO) | KTZ-LD-LG-600-PRO | 20 | pc | KITOZER | Premium SPCC cold-rolled steel plate ≥1.5 mm thick, length 600 mm, rigid cabinet top connection with pre-reserved concealed strong/weak current cable trays and sensor mounting slots, electrostatic black matte powder coating for 600 mm wide standard cabinets |
| 2 | Cold Aisle Transverse Support Beam (PRO) | KTZ-LD-HL-1200-PRO | 11 | pc | KITOZER | Premium SPCC cold-rolled steel plate ≥1.5 mm thick, length 1,200 mm for 1,200 mm aisle width, reinforced structure with static load capacity ≥1,500 kg, rigid longitudinal keel connection, electrostatic black matte powder coating |
| 3 | Fixed Sealing Skylight (Integrated Lighting) | KTZ-LD-TC-GD-600-ZM | 6 | set | KITOZER | Steel frame ≥1.2 mm thick embedded with 5 mm tempered glass, light transmittance ≥85%, 600*600 mm dimensions with integrated 8 W LED lighting modules, EPDM flame-retardant sealing strips, air leakage rate ≤1%, bolted frame mounting |
| 4 | Fire Linkage Flip Skylight (PRO) | KTZ-LD-TC-XF-600-PRO | 5 | set | KITOZER | Steel frame ≥1.5 mm thick embedded with 5 mm explosion-proof tempered glass, UL94 V-0 flame retardancy, DC24V electromagnetic lock with adsorption force ≥500 N, auto-open within 0.5 s upon fire signals, opening angle ≥90°, manual emergency release + open/closed status feedback, 600*600 mm dimensions |
| 5 | Cold Aisle Automatic Sliding Door | KTZ-LD-M-ZD-1200 | 2 | leaf | KITOZER | Steel door frame embedded with 8 mm tempered glass, double sliding door size 1,200*2,200 mm, brushless DC motor drive with microcomputer controller, adjustable opening/closing speed and hold time, standard infrared anti-pinch and mechanical emergency lock with access control mounting slots, full-perimeter EPDM sealing strips, air leakage rate ≤2% |
| 6 | Integrated Aisle Control Mainframe (PRO) | KTZ-LD-KZ-6U-PRO | 1 | unit | KITOZER | Standard 19-inch 6U rack-mountable, dual redundant AC220V input, DC24V safety voltage output, active/passive fire signal input support, hardware-level fire linkage, controls up to 128 skylights, integrated door and lighting control modules, standard RS485/RS232/SNMP communication ports for seamless integration with environmental monitoring/BMS systems |
| 7 | Industrial Touch Screen HMI Unit | KTZ-LD-CP-10 | 1 | unit | KITOZER | 10-inch industrial touch screen, 1280*800 resolution, ARM architecture processor, embedded system, real-time display of aisle conditions, equipment parameters, local manual control, parameter configuration, alarm record query and hierarchical permission management |
| 8 | Intelligent Access Control System | KTZ-LD-MJ-01 | 2 | set | KITOZER | Facial recognition + card swiping + password triple authentication, supports ≥10,000 user profiles and ≥100,000 access record storage, tamper and unauthorized entry alarms, linkage with aisle doors and lighting systems, paired exit push buttons |
| 9 | Environmental Monitoring System (10-Cabinet Package) | KTZ-LD-DH-10G | 1 | set | KITOZER | Includes 1 environmental monitoring host, 4 high-precision temperature/humidity sensors (2 inside cold aisle, 2 inside hot aisle, accuracy ±0.3°C / ±2%RH), 1 non-positioned water leak alarm controller + 3 m leak detection cable, 2 photoelectric smoke sensors, 4 door magnetic sensors for full real-time parameter monitoring, multi-tier alarms and remote access |
| 10 | Emergency Lighting System | KTZ-LD-ZM-YJ | 1 | set | KITOZER | 2 emergency lighting fixtures DC24V powered, auto-activate during power outages with ≥90 min runtime, illuminance ≥200 lux to satisfy emergency evacuation requirements |
| 11 | Full-Circuit Sealing Kit (PRO) | KTZ-LD-MF-10G-PRO | 1 | set | KITOZER | Includes cabinet gap brush sealing strips, EPDM flame-retardant sealing strips, 40 pcs of 1U/2U cabinet blanking panels, cable penetration sealing plates and cabinet side gap baffles for full gap blocking with overall aisle air leakage rate ≤3% |
| 12 | Standard Connectors & Fasteners (PRO) | KTZ-LD-LJ-10G-PRO | 1 | set | KITOZER | Complete installation auxiliary materials including cabinet connection bolts, frame connectors, grounding bolts, flat/spring washers, all 304 stainless steel anti-corrosion hardware paired with grounding copper bars and wires for full-system reliable grounding |
5.3 Flagship (High-End Customized) Cold Aisle System Configuration List (10-Cabinet Double-Row)
Applicable Scenarios: Large data centers, AI computing centers, head office financial computer rooms, provincial government clouds, military classified computer rooms, high-density environments with single cabinet power 15–50 kW requiring top-tier security grading, intelligence, energy efficiency and compliance.
è¡¨æ ¼
| No. | Product Name | Model Specification | Qty | Unit | Brand | Technical Parameters & Remarks |
|---|---|---|---|---|---|---|
| 1 | Cold Aisle Longitudinal Load-Bearing Keel (Flagship) | KTZ-LD-LG-600-FLAG | 20 | pc | KITOZER | 6061-T5 high-strength aluminum alloy extrusion, anodized surface, thickness ≥2.0 mm, length 600 mm, rigid cabinet top connection with integrated concealed strong/weak current cable trays, sensor and lighting mounting slots, reinforced load-bearing design with static load capacity ≥2,000 kg for 600/800 mm wide cabinets |
| 2 | Cold Aisle Transverse Support Beam (Flagship) | KTZ-LD-HL-1200-FLAG | 11 | pc | KITOZER | 6061-T5 high-strength aluminum alloy extrusion, anodized surface, thickness ≥2.0 mm, length 1,200 mm (1,500 mm optional) for aisle width selection, rigid longitudinal keel connection, Grade 9 seismic resistance, black/silver anodized finishes optional |
| 3 | Integrated Fixed Skylight (Lighting + Cabling + Sensing) | KTZ-LD-TC-GD-600-YT | 6 | set | KITOZER | Aluminum alloy frame embedded with 8 mm tempered glass, light transmittance ≥90%, 600*600 mm dimensions with integrated 12 W intelligent LED lighting, cable trays and sensor mounting bases, dual-layer EPDM flame-retardant sealing strips, air leakage rate ≤0.5% |
| 4 | Intelligent Fire Linkage Flip Skylight (Flagship) | KTZ-LD-TC-XF-600-FLAG | 5 | set | KITOZER | Aluminum alloy frame embedded with 6 mm explosion-proof tempered glass, UL94 V-0 flame retardancy, dual redundant DC24V electromagnetic locks with adsorption force ≥800 N, auto-open within 0.3 s upon fire signals, opening angle ≥95°, manual emergency release + real-time open/closed state + fault feedback, 600*600 mm dimensions supporting independent single-skylight control |
| 5 | Premium Intelligent Automatic Sliding Door (Flagship) | KTZ-LD-M-ZD-1500-FLAG | 2 | leaf | KITOZER | High-strength aluminum alloy frame embedded with monolithic 10 mm tempered glass, double sliding door size 1,500*2,200 mm, imported brushless DC motor, industrial microcomputer controller with operating noise ≤50 dB, dual infrared anti-pinch safety light curtains, mechanical emergency release, auto-open during power outages, integrated 21.5-inch touch display showing aisle status and personnel information, national cryptographic algorithm access control system |
| 6 | Redundant Hot-Standby Integrated Control Mainframe (Flagship) | KTZ-LD-KZ-6U-FLAG | 2 | unit | KITOZER | Standard 19-inch 6U rack-mountable 1+1 redundant hot standby configuration, dual AC220V + UPS redundant input, DC24V 20 A safe voltage output, hardware-level fire linkage supporting active/passive dual redundant fire signal circuits, controls up to 256 skylights with integrated door, lighting and air conditioner linkage control modules, standard RS485/RS232/dual Ethernet/SNMP/BACnet communication ports for seamless integration with environmental monitoring/BMS/fire systems |
| 7 | Industrial Touch Screen HMI Unit (Flagship) | KTZ-LD-CP-21 | 2 | unit | KITOZER | 1 unit installed at each aisle end, 21.5-inch industrial touch screen, 1920*1080 resolution, ARM Cortex-A17 1.8 GHz processor, embedded Linux/Android optional, 3D visualization interface rendering full real-time parameters and equipment status, local control, parameter configuration, alarm query and multi-tier permission management with remote access support |
| 8 | High-Security National Cryptographic Access Control System | KTZ-LD-MJ-GM | 2 | set | KITOZER | Facial recognition + fingerprint + card swiping + password four-factor authentication encrypted via national cryptographic algorithms, supports ≥50,000 user profiles and ≥1,000,000 access record storage, tamper, coercion and unauthorized entry alarms, linkage with aisle doors, lighting and video surveillance systems, paired exit and emergency release push buttons |
| 9 | AI Intelligent Environmental Monitoring System | KTZ-LD-DH-AI | 1 | set | KITOZER | Includes 1 dual redundant power AI environmental monitoring host (Linux system with AI algorithm engine), 20 cabinet-level high-precision temperature/humidity sensors (1 per cabinet, accuracy ±0.2°C / ±1.5%RH), 10 hot aisle temperature/humidity sensors, 1 positioning water leak detection system (±1 m positioning accuracy), 5 smoke sensors, 2 infrared intrusion detectors, 4 door magnetic sensors, 2 air quality sensors (PM2.5/CO₂) for 24/7 full-parameter monitoring, AI intelligent analysis, predictive fault early warning, energy consumption optimization, 3D visualization O&M and digital twin functionality |
| 10 | High-Definition Video Surveillance System | KTZ-LD-SP-01 | 1 | set | KITOZER | Includes 4 pcs of 4 MP HD network cameras (2 at each aisle end) with night vision, POE power supply, paired NVR storage host + 4 T hard disk for 24/7 video recording, motion detection capture and access control linkage recording with remote access support |
| 11 | Emergency Lighting & Evacuation System (Flagship) | KTZ-LD-ZM-YJ-FLAG | 1 | set | KITOZER | 4 emergency lighting fixtures + 2 evacuation indicator signs DC24V powered, auto-activate upon fire linkage with ≥180 min power outage runtime, illuminance ≥300 lux complying with high-grade fire emergency requirements |
| 12 | Full-Circuit Reinforced Sealing Kit (Flagship) | KTZ-LD-MF-10G-FLAG | 1 | set | KITOZER | Includes high-density brush cabinet gap sealing strips, dual-layer EPDM flame-retardant sealing strips, 60 pcs of 1U/2U/4U cabinet blanking panels, cable penetration sealing modules and full cabinet side/bottom/top gap baffles for zero blind spot aisle sealing with overall air leakage rate ≤1% |
| 13 | In-Row Air Conditioner Adaptation Assembly | KTZ-LD-KT-SP | 1 | set | KITOZER | Sealing docking assemblies and airflow guide plates for seamless integration with KITOZER in-row precision air conditioners to maximize cooling efficiency, compatible with 20/25/30/35 kW in-row air conditioners |
| 14 | Standard Connectors & Fasteners (Flagship) | KTZ-LD-LJ-10G-FLAG | 1 | set | KITOZER | Complete installation auxiliary materials including cabinet connection bolts, frame connectors, grounding bolts, all 304 stainless steel anti-corrosion hardware paired with dedicated grounding copper bars and multi-strand wires for full-system equipotential bonding with grounding resistance ≤4 Ω |
| 15 | Custom Protection Assembly | KTZ-LD-FH-01 | 1 | set | KITOZER | Optional electromagnetic shielding reinforcement, dust/moisture protection and seismic reinforcement assemblies for special scenario demands |
VI. Full-Series Technical Parameters of KITOZER Modular Cold Aisle Cooling System
6.1 Core Technical Parameters of Cold Aisle Main Structure
è¡¨æ ¼
| No. | Parameter Item | Economy Standard | Standard Mid-Range | Flagship Premium | Applicable Standard |
|---|---|---|---|---|---|
| 1 | Compatible Aisle Width Range | 1,200 mm | 1,200 / 1,500 mm | 1,200 / 1,500 / 1,800 mm | GB/T 41783-2022 |
| 2 | Minimum Aisle Clear Height | ≥2,000 mm | ≥2,200 mm | ≥2,200 mm | GB 50174-2017 |
| 3 | Maximum Compatible Cabinets Per Single Aisle | 20 cabinets | 40 cabinets | 100 cabinets | Enterprise Internal Standard |
| 4 | Main Frame Material | SPCC cold-rolled steel ≥1.2 mm thick | SPCC cold-rolled steel ≥1.5 mm thick | 6061-T5 aluminum alloy ≥2.0 mm thick | GB/T 13237-2013 |
| 5 | Frame Static Load Capacity | ≥1,000 kg | ≥1,500 kg | ≥2,000 kg | YD 5083-2005 |
| 6 | Seismic Performance | Grade 8 seismic resistance | Grade 8 seismic resistance | Grade 9 seismic resistance | YD 5083-2005 |
| 7 | Overall Static Air Leakage Rate | ≤5% | ≤3% | ≤1% | GB/T 41783-2022 |
| 8 | Surface Treatment | Electrostatic powder coating ≥50 μm thickness | Electrostatic powder coating ≥60 μm thickness | Anodizing / powder coating ≥60 μm thickness | GB/T 9286-1998 |
| 9 | Coating Adhesion Grade | Grade 1 | Grade 1 | Grade 1 | GB/T 9286-1998 |
| 10 | Non-Metal Flame Retardancy Grade | UL94 V-1 | UL94 V-0 | UL94 V-0 | GB/T 2408-2008 |
| 11 | Compatible Cabinet Widths | 600 mm standard cabinet | 600 / 800 mm standard cabinet | 600 / 800 / 1,000 mm custom non-standard cabinet | Enterprise Internal Standard |
| 12 | Compatible Cabinet Depths | 1,000 / 1,200 mm | 1,000 / 1,200 / 1,100 mm | Full customization 800–1,500 mm | Enterprise Internal Standard |
| 13 | Operating Ambient Temperature | -5°C ~ +45°C | -5°C ~ +45°C | -10°C ~ +55°C | GB/T 17626-2018 |
| 14 | Operating Ambient Humidity | ≤95%RH non-condensing | ≤95%RH non-condensing | ≤95%RH non-condensing | GB/T 17626-2018 |
| 15 | System Design Service Life | ≥10 years | ≥15 years | ≥20 years | Enterprise Internal Standard |
6.2 Aisle Door Assembly Technical Parameters
6.2.1 Manual Swing Door Technical Parameters
è¡¨æ ¼
| Parameter Item | Technical Index | Applicable Standard |
|---|---|---|
| Door Body Dimensions | Width 1,200 / 1,500 mm, Height 2,000 / 2,200 mm, customizable | Enterprise Internal Standard |
| Door Frame Material | Premium SPCC cold-rolled steel ≥1.5 mm thick | GB/T 13237-2013 |
| Door Glass | 5 mm tempered glass, light transmittance ≥85%, complies with safety glass standards | GB 15763.2-2005 |
| Maximum Opening Angle | ≥160° | Enterprise Internal Standard |
| Hinges | 304 stainless steel industrial hinges, pass 100,000 opening/closing cycle durability testing | Enterprise Internal Standard |
| Door Closer | Hydraulic buffer door closer with adjustable closing speed and force | Enterprise Internal Standard |
| Door Lock | Anti-theft mechanical lock with internal emergency release anti-pry design | GA/T 73-2015 |
| Sealing Performance | Air leakage rate ≤3% when fully closed | GB/T 41783-2022 |
| Non-Metal Flame Retardancy | UL94 V-0 grade for all non-metallic components | GB/T 2408-2008 |
6.2.2 Automatic Sliding Door Technical Parameters
è¡¨æ ¼
| Parameter Item | Standard Mid-Range Index | Flagship Premium Index | Applicable Standard |
|---|---|---|---|
| Door Body Dimensions | Width 1,200 / 1,500 mm, Height 2,200 mm, customizable | Width 1,200 / 1,500 / 1,800 mm, Height 2,200 / 2,400 mm, customizable | Enterprise Internal Standard |
| Door Frame Material | Premium SPCC cold-rolled steel ≥1.5 mm thick | 6061-T5 high-strength aluminum alloy extrusion | GB/T 13237-2013 |
| Door Glass | 8 mm tempered glass, light transmittance ≥85% | 10 mm tempered glass, light transmittance ≥90% | GB 15763.2-2005 |
| Drive Motor | Brushless DC motor ≥60 W power | Imported brushless DC motor ≥90 W power | Enterprise Internal Standard |
| Power Supply | AC220V ±10%, 50 Hz | AC220V ±10%, 50 Hz with UPS backup power interface | GB 50054-2011 |