KITOZER Double-Row Cold Aisle Containment

I. System Introduction

1.1 Technical Definition

KITOZER Modular Double-Row Cold Aisle Containment is a high-efficiency airflow management solution specially designed for data center facilities. Cabinets are arranged face-to-face to form fully enclosed cold aisles and back-to-back to form open hot aisles via physical partitioning, completely eliminating short-circuit of hot and cold airflow to realize precise cooling and power consumption optimization. Built on modular design philosophy, all components are factory prefabricated for fast on-site assembly, supporting flexible capacity expansion and later renovation, applicable for both new-build and retrofit data center projects of all specifications.

1.2 Core Working Principle

Energy efficiency improvement is realized via four core mechanisms:

  • Airflow Isolation: Fully sealed cold aisle ensures 100% of chilled air from CRAC enters server intake; hot exhaust returns to air conditioner return air plenum from top of hot aisle
  • Static Pressure Balancing: Cold aisle top cover extends 450mm above cabinet roof to form stable static pressure chamber for even cold air distribution across entire aisle
  • Intelligent Fire Linkage: Aisle skylights interlock with fire alarm system and auto-open upon fire detection to comply with fire safety codes
  • Precision Monitoring: Real-time collection of aisle temperature, humidity and differential pressure to dynamically adjust cooling output of air conditioning units
(double row cold aisle) system solution (1)

1.3 Application Benefits

Benefit ItemCore GainQuantified Index
Energy EfficiencyPUE ReductionPUE down to 1.3~1.5, 20%~35% lower vs conventional open computer room
OPEX SavingElectricity Cost CutAnnual operating expense reduced by over 30%
Equipment SafetyHotspot EliminationIntra-aisle temperature deviation ≤1℃, no local hotspot above 24℃
O&M OptimizationSimplified Daily Management40% less maintenance frequency, 50% shorter fault response time
Project DeliveryFast Site DeploymentConstruction cycle shortened by 60%, plug-and-play installation

II. System Composition

KITOZER double-row cold aisle system consists of six highly integrated subsystems for coordinated operation.

2.1 Sealed Cold Aisle Subsystem (Core Part)

ComponentSpecificationFunction Description
Cold Aisle Frame1.5mm cold rolled steel with electrostatic spray coatingLoad-bearing support structure, compatible with standard server racks
End Access Door2050mm height, tempered glass + metal frameOperator access & visual inspection, equipped with electronic access control lock
Modular Top CoverFlat type, 1305mm width, 450mm higher than cabinet topAir sealing, integrated embedded LED lighting
Fire Linkage SkylightAuto-fusible opening, flame retardant fire-rated materialAutomatic release during fire incident for smoke exhaust
Sealing Accessories5mm thick PVC baffle with rubber gasketFill cabinet clearance, cold air leakage rate<5%
Aisle LED LightingRecessed installation, brightness ≥300LuxEnergy-saving uniform aisle illumination

2.2 Cabinet Subsystem

  • Standard Rack: 600/800(W)×1200(D)×2200(H)mm (42U), 1.2~2.0mm cold rolled steel plate
  • Load Capacity: Static full rack load ≥1500kg, single shelf rated load ≥80kg
  • Compatibility: Standard 19-inch equipment mounting, front & rear perforated door ventilation ratio ≥70%
  • Expansion Option: Pre-reserved interface for top cable tray, bottom wiring duct and side-mounted PDU

2.3 Cooling Subsystem

  • In-row CRAC Unit: Horizontal air supply, cooling capacity ranging 5~41kW, available for N+X redundant configuration
  • Air Distribution: Dual airflow mode (underfloor / horizontal supply), partitioned static plenum adapting for variable rack power density
  • Intelligent Regulation: Remote monitoring supported; cooling capacity auto-adjusted according to real-time aisle ambient temperature

2.4 Power Distribution Subsystem

  • End-of-row Power Cabinet: Integrated PDM power distribution module with multi-circuit input & output
  • Intelligent PDU: Real-time monitoring of voltage, current & power; remote on/off switch control
  • Redundant Design: Dual-circuit incoming power for non-stop power supply

2.5 Intelligent Monitoring Subsystem

  • Environmental Sensors: Temp/humidity, differential pressure, smoke & water leakage probes; accuracy ±0.5℃ / ±3%RH
  • Central Controller: Local 10-inch touch screen + WEB remote access & mobile APP monitoring
  • Multi-level Alarm: Audible-visual alert, SMS & email notification for fault auto-reporting
  • Data Visualization: 3D digital twin platform with real-time aisle thermal cloud map display

2.6 Fire Protection Linkage Subsystem

  • Interlock Logic: Auto skylight opening + CRAC shutdown triggered by fire alarm signal
  • Emergency Evacuation: Automatic unlock of end access doors for personnel escape
  • Gas Suppression Compatibility: Seamless docking with FM200 and other clean-agent fire suppression systems
(double row cold aisle) system solution (2)

III. System Classification

3.1 By Rack Power Density

TypeRack Power LoadApplicationCooling Configuration
Standard Density3~6kW/rackGeneral IDC & small-scale data centerStandard underfloor supply in-row air conditioner
Medium Density6~12kW/rackCloud computing & enterprise DCEnhanced horizontal air supply in-row CRAC
High Density12~20kW/rackHPC & AI server clusterWater-cooled in-row precision cooling unit

3.2 By Installation Mode

  1. New-build Integrated Type: Co-designed with civil construction, full factory prefabrication & rapid on-site assembly
  2. Retrofit Adaptation Type: Fit existing room layout without large-scale civil modification, phased construction without service interruption
  3. Hybrid Deployment Type: Partial cold aisle sealing + partial open layout for phased DC expansion project

3.3 By Skylight Opening Type

  1. Auto-fusible skylight: Thermal trigger opening, mainly for clean-agent fire suppression computer room
  2. Electric control skylight: Local/remote motorized opening for conventional fire alarm system
  3. Manual emergency skylight: Backup mechanical opening for extreme emergency evacuation
(double row cold aisle) system solution (3)

IV. Bill of Materials (Brand: KITOZER | Standard Pack: 12-Rack Double-Row Cold Aisle)

No.ItemModelSpecQtyBrand

Part 1: Sealed Aisle System

1|Cold Aisle Frame|KZ-CCF-1200|1200mm width for 600mm standard rack|6 sets|KITOZER|

2|End Access Door|KZ-CCM-2050|2050H, Al+Tempered Glass, digital lock|2 sets|KITOZER|

3|Modular Top Cover|KZ-CCT-1305|1305mm width, +450mm over rack, built-in LED|6 pcs|KITOZER|

4|Fire Interlock Skylight|KZ-CCS-1200|Auto thermal fuse, B1 fire rating|6 pcs|KITOZER|

5|Gap Sealing Kit|KZ-CCS-05|5mm PVC with rubber gasket|12 sets|KITOZER|

6|Aisle LED Lamp|KZ-CCL-300|≥300Lux, 90min emergency backup|6 sets|KITOZER|

Part 2: Cabinet System

7|42U Server Rack|KZ-RACK-42U|600×1200×2200mm, 1.5mm steel|12 units|KITOZER|

8|Perforated Door|KZ-RM-70|≥70% ventilation rate with inspection window|24 pcs|KITOZER|

9|Adjustable Load Shelf|KZ-RS-80|Single shelf load ≥80kg|24 pcs|KITOZER|

Part3: Cooling System

10|In-row CRAC|KZ-CA-15|15kW cooling, horizontal supply, N+1 redundant|2 units|KITOZER|

11|Partition Static Plenum|KZ-CP-1200|Covers 3~4 racks per section|3 sets|KITOZER|

Part4: Power Distribution System

12|End-of-row Power Cabinet|KZ-PDU-630|630A input, multi-outlet with monitoring|2 units|KITOZER|

13|Intelligent Switched PDU|KZ-PD-32|32A input,16 outlets, remote control|24 pcs|KITOZER|

Part5: Environmental Monitoring System

14|Temp&RH Sensor|KZ-TH-01|±0.5℃/±3%RH, RS485 Modbus|6 pcs|KITOZER|

15|Differential Pressure Sensor|KZ-DP-02|Measuring range ±500Pa|2 pcs|KITOZER|

16|Central Monitoring Host|KZ-MC-10|10-inch touch screen + WEB|1 unit|KITOZER|

17|Alarm Terminal|KZ-AL-03|Audible/visual + SMS alert module|1 set|KITOZER|

Part6: Fire Interlock System

18|Fire Linkage Controller|KZ-FC-01|Fire signal reception & skylight drive|1 unit|KITOZER|

19|Emergency Manual Button|KZ-EB-02|Manual forced skylight open|2 pcs|KITOZER|

Optional Upgrade Components

ItemModelFunctionApplication Scenario
Access Control SystemKZ-AC-05Face recognition / card swipe & access logHigh-security data center
HD CCTVKZ-VC-1080IR night vision surveillanceUnattended computer room
3D Airflow VisualizationKZ-AV-3DReal-time airflow thermal cloud displayUltra-high density rack zone
Smart Variable Skylight ControlKZ-SC-03Temp/DP linked auto opening adjustmentDynamic variable IT load IDC
4G Remote GatewayKZ-RM-4GWireless cloud remote monitoringDistributed branch computer room
(double row cold aisle) system solution (4)

V. System Principle Drawings

5.1 Airflow Distribution Diagram

┌─────────────────────────────────────────┐
│ CRAC Supply Air Zone │
│ ┌─────────────────────────────────┐ │
│ │ SEALED COLD AISLE │ │
│ │ ┌─────┐ ┌─────┐ ┌─────┐ │ │
│ │ │RACK1│ │RACK2│ │RACK3│ │ │
│ │ │Face-to-Face │Face-to-Face│ │ │
│ │ └─────┘ └─────┘ └─────┘ │ │
│ │ Cold Air →→→→→→→→→→→→→→→→→→→→→ │ │
│ └─────────────────────────────────┘ │
│ ↑ ↓ │
│ ┌─────────────────────────────────┐ │
│ │ OPEN HOT AISLE │ │
│ │ ┌─────┐ ┌─────┐ ┌─────┐ │ │
│ │ │RACK1│ │RACK2│ │RACK3│ │ │
│ │ │Back-to-Back│Back-to-Back│ │ │
│ │ └─────┘ └─────┘ └─────┘ │ │
│ │ Hot Air →→→→→→→→→→→→→→→→→→→→→ │ │
│ └─────────────────────────────────┘ │
│ CRAC Return Air Zone │
└─────────────────────────────────────────┘

Airflow Description: Cold air flows into rack front intake inside enclosed cold aisle; after heat absorption, hot air exhausts from rack rear to open hot aisle, then returns to air conditioner for cyclic cooling.

5.2 Overall System Architecture Diagram

┌─────────────┐ ┌─────────────┐ ┌─────────────┐
│Cooling System│───▶│Cold Aisle Sys│───▶│Hot Aisle Zone│
└─────────────┘ └─────────────┘ └─────────────┘
│ │ │
▼ ▼ ▼
┌─────────────┐ ┌─────────────┐ ┌─────────────┐
│Power Dist Sys│ │Monitor Sys │ │Fire Control │
└─────────────┘ └─────────────┘ └─────────────┘
│ │ │
└───────────────────┼───────────────────┘
▼
┌─────────────┐
│Central Platform│
└─────────────┘

Logic Note: All subsystems realize centralized monitoring & intelligent linkage via central management platform.

5.3 Fire Interlock Logic Diagram

┌─────────────┐ Fire Alarm Signal ┌─────────────┐
│Fire Alarm Host│───────────────────────▶│Linkage Module│
└─────────────┘ └─────────────┘
│
┌───────────────────────┼───────────────────────┐
│ │ │
▼ ▼ ▼
┌─────────────┐ ┌─────────────┐ ┌─────────────┐
│Skylight Auto│ │CRAC Shutdown│ │Door Unlock │
│Opening Drive│ │ │ │ │
└─────────────┘ └─────────────┘ └─────────────┘

Note: Once fire signal triggered, linkage module synchronously controls three sets of equipment for equipment protection & personnel evacuation safety.

(double row cold aisle) system solution (5)

VI. Technical Specifications

6.1 Core Aisle Component Parameters

ComponentItemSpecCompliance Standard
Aisle FrameMaterial & Thickness1.5mm cold rolled steelGB/T708-2019
Surface FinishPickling+Phosphating+Electrostatic Coating, IP20GB/T1771-2007
Top Load≥200kg/㎡Industry Specification
End Access DoorDimension2050×1200mmCustom Standard
MaterialAl frame+10mm tempered glassGB15763.2-2005
Access ControlDigital lock + IC card compatibleISO15693
Top CoverSingle Module Size1305×1000mmCustom Standard
Fire RatingB1 flame retardantGB8624-2012
Light Transmittance≥85%GB/T2410-2008
Fire SkylightFuse Temp70℃±5℃GB16806-2018
Full Open Time≤5sFire Code Standard
Seal KitMaterial5mm PVC+rubber ringGB/T10002.1-2006
Cold Air Leakage<5%Factory Test Standard

6.2 Overall System Performance Index

CategoryParameterValueTest Condition
EnergySystem PUE1.3~1.5Normal rated IT load
Cold Air Utilization≥95%Fully sealed status
Power Saving≥30%Compared with open room
AmbientCold Aisle Temp18~22℃Steady operation
Temp Uniformity≤±1℃All measuring points
RH Range45%~60%RH24h continuous test
StructureAisle Width1200~1800mmMatches standard raised floor
Installation Speed≤4h/12 racksProfessional construction crew
SafetyMaterial StandardRoHS compliant + B1 fire gradeNational Fire Standard

6.3 Cabinet Detailed Spec

  • Dimension:600×1200×2200mm(42U); Frame 2.0mm, door 1.5mm cold rolled steel
  • Static full rack load≥1500kg, single shelf≥80kg; front/rear door ventilation≥70%
  • Anti-corrosion coating pass 1000h salt spray test, IP20 protection rating

6.4 Monitoring Device Spec

  • Temp&RH: -40~85℃ / 0~100%RH, ±0.5℃/±3%RH, Modbus-RTU
  • Differential Pressure: ±500Pa, accuracy ±1%FS
  • Central Controller:10-inch touch screen, 4-core CPU, 2GB RAM+8GB storage; support WEB/APP/4G remote access; 365-day historical data storage

VII. Application Industry & Scenarios

7.1 Vertical Industry Matching

IndustryCore RequirementProject Value
Cloud & InternetHigh density, flexible expansion, low PUERapid capacity expansion & substantial electricity cost reduction
Financial DCUltra-high reliability & safetyHotspot elimination to guarantee uninterrupted transaction system
Telecom OperatorLarge-scale distributed deploymentCentralized remote O&M to cut field maintenance expense
Government CloudRegulatory compliance & audit traceabilityMeet Grade Protection standard for government IT infrastructure
Enterprise Private CloudFast deployment & lower upfront investmentShorten construction period & reduce total ownership cost(TCO)
Medical Data Center24/7 non-stop stable runningSecure continuous operation for medical image & patient database
University HPC LabHigh computing density & energy savingStable cooling for supercomputing research & lower lab power expense

###7.2 Three Major Project Types

  1. New-build Data Center: Factory prefabrication cuts construction cycle by 60%, phased installment to lower initial CAPEX, standardized compatible design for future upgrade
  2. Legacy Room Retrofit: No large civil alteration; phased off-hour construction without service outage; rapidly improve cooling efficiency & extend existing equipment lifespan
  3. Hybrid Mixed Layout: Partial cold aisle sealing for mixed low/high power density racks, smooth transition toward full enclosed cold aisle in later stage

###7.3 Special High-Density & Edge Scenarios

  • High-density AI/HPC: Support single rack up to 20kW, precise airflow to eliminate hotspot
  • Edge Computing Hub: Compact footprint design for narrow space, full remote monitoring to minimize on-site maintenance
  • Green Energy-saving DC: RoHS eco-friendly material, compatible with free air cooling to further optimize PUE
(double row cold aisle) system solution (6)

VIII. Core Product Advantages

###8.1 Technical Superiority

  1. Modular prefabricated structure: 60% faster installation speed, free capacity expansion & easy spare part replacement
  2. Superior airflow sealing: ≥95% cold air utilization, stable static pressure for uniform temperature distribution & zero hotspot
  3. Multi-layer intelligent linkage: Fire-skylight interlock + cooling-temperature linkage + cloud remote centralized management

###8.2 Economic Benefits

Cost ItemProfitQuantified Index
Initial CAPEXShorten construction period60% less build time, 40% saving on labor cost
Phased investmentExpand along business growth to lower upfront fund pressure
Long-term OPEXElectricity & maintenance≥30% annual power saving, 40% less maintenance workload
Equipment LifespanIT & cooling equipment life extended 15%~20%
Investment ReturnPayback PeriodROI within 1.5~2 years

###8.3 Safety Advantages

  1. Physical access control via electronic lock to prevent unauthorized equipment touch
  2. Constant ambient temperature avoids overheating & reduces server failure rate
  3. 24/7 real-time monitoring with pre-alarm to avoid unexpected downtime & data loss

###8.4 Performance Comparison Table

Comparison ItemKITOZER Double-Row Cold AisleTraditional Open RoomSingle-Row Cold Aisle
PUE1.3~1.51.8~2.21.4~1.6
Cold Air Utilization≥95%60~70%90~95%
Install SpeedFast(4h/12rack)Slow(2~3d/12rack)Medium(6h/12rack)
Max Supported Rack Load3~20kW≤3kW3~12kW
Space UtilizationHighMediumLow
Running OPEXLowHighMedium
(double row cold aisle) system solution (7)

IX. Tender Specification Parameters

###9.1 Mandatory Technical Bid Spec (Non-negotiable core clauses)

  1. Structure: Double-row face-to-face enclosed cold aisle modular assembly, GB/T41783-2022 compliant
  2. Airflow: Cold sealed + hot open layout to prevent air short-circuit, ISO/IEC11801 standard
  3. Energy: PUE≤1.5, cold air utilization≥95%, per GB/T41783
  4. Temp Control: Cold aisle 18~22℃, intra-aisle deviation ≤±1℃, GB50174
  5. Top Cover Height: +450mm over cabinet top, aisle width 1200~1800mm
  6. Fire Skylight: 70℃±5℃ thermal fuse, full open ≤5s, GB16806
  7. Material: Frame steel ≥1.5mm, coating ≥1000h salt spray resistance GB/T10125
  8. Monitoring: Local touch screen + remote WEB/APP dual management GB50462
  9. Install Cycle: ≤4h for standard 12-rack set (±1h tolerance allowed) 10.Warranty: Whole system ≥5Y warranty, core components ≥10Y

###9.2 Commercial Bid Requirement

  • Manufacturer with ISO9001/ISO14001/ISO45001 certification (mandatory qualification)
  • At least 10 similar completed projects over past 3 years with single contract ≥2 million RMB
  • After-sale service: 2h remote response, on-site engineer within 24h, fault fixed within 48h

X. Three Typical Customized Solutions

###10.1 New-Build Green Data Center Solution

  • Key Feature: Full-process BIM pre-design + energy consumption simulation; all parts factory prefabricated, 12-rack set finished within 4h on site; integrated intelligent centralized monitoring platform
  • Execution Flow: Demand Survey→BIM Modeling→Energy Simulation→Factory Production→On-site Install→Commissioning→User Training

###10.2 Existing Open Computer Room Retrofit Solution

  • Key Feature: Phased zone-by-zone construction during off-business hour without service interruption; original air conditioner & fire system reserved for cost saving; PUE optimized down to1.3~1.5 after renovation
  • Execution Flow: On-site Audit→Optimization Design→Risk Plan→Staged Construction→Test & Acceptance

###10.3 Ultra-High Density AI/HPC Solution(≥12kW/Rack)

  • Key Feature: Water-cooled in-row CRAC + enhanced sealing (air leakage<3%) + dynamic skylight auto-adjust by temp/differential pressure + 3D airflow visualization; every 2m equipped with independent temp sensor for precise cooling control
  • Execution Flow: Load Calculation→Cooling Sizing→System Install→Airflow Calibration→Simulation Test→Delivery

XI. Reference Project Cases

###Case1: Cloud Service Provider IDC (Shenzhen, 1000 racks,6~12kW/rack)

  • Result: Original PUE1.8 reduced to1.4, annual power saving ≈8 million CNY; full 1000-rack installation finished within 45 days, 60% shorter than traditional build; intra-aisle temp stably 20±1℃ with zero hotspot

###Case2: National Head Office Bank DC Retrofit (Beijing,500 racks, old PUE1.9)

  • Result: PUE down to1.5, annual electricity saving≈3.5 million CNY; 5-phase phased renovation with each section ≤100 racks & minimal service interruption; investment payback within 1.8 years

###Case3: University HPC Supercomputing Center(Shanghai,200 racks@20kW/rack)

  • Result: Successfully solve extreme high-density heat dissipation, final PUE=1.4 to meet national green DC standard; becomes provincial energy-saving demonstration research data center

XII. SEO Keywords & Tags

###12.1 Core Primary Keywords

Modular Hot Cold Aisle Containment, Double-Row Cold Aisle Solution, KITOZER Cold Aisle System, Data Center Airflow Management, Cold Aisle Sealing System, PUE Optimization for Green Data Center, Data Center Retrofit Energy Saving

###12.2 Long-tail Keywords

Double-row cold aisle working principle, cold aisle tender parameter specification, legacy computer room cold aisle renovation plan, high-density AI rack cooling solution, cold aisle fire linkage design standard

###12.3 Hashtag Tags

#ModularColdAisle #DoubleRowContainment #DataCenterEnergySaving #PUEOptimization #IntelligentDC #ColdAisleRetrofit #FireInterlockSystem

Shopping Cart