ToggleI. System Introduction
KITOZER Modular Hot & Cold Aisle Containment is a high-efficiency airflow management solution tailor-made for data centers, computer rooms and IT equipment operating environments. Physical separation fully isolates cold intake zone at cabinet front and hot exhaust zone at cabinet rear to form independent enclosed cold plenum and hot plenum, realizing precise airflow control, thoroughly eliminating cross-mixing & short-circuit of cold/hot air, drastically boosting cooling efficiency, cutting down PUE and extending service life of IT equipment with stable, secure and high-efficiency operating surroundings.
Designed on modular philosophy, the system supports rapid on-site deployment, flexible capacity expansion and standardized management, compatible with mainstream server racks, precision air conditioners and environmental monitoring systems. Multiple configurable layouts are available: single/double-row cold aisle, single/double-row hot aisle and hybrid aisle combination, covering full-range airflow demands from small-medium computer rooms to large-scale hyperscale data centers.
Core Working Principle
Enclosed cold aisle builds positive static pressure (5~10Pa relative pressure). Chilled air is delivered into cold aisle via in-row CRAC or under-floor air supply, flows through cabinet front door into IT hardware; after heat absorption, hot air exhausts from cabinet rear into hot aisle, then returns to air conditioner for re-cooling to complete cyclic airflow circulation and maximize energy utilization efficiency.

II. System Composition
| System Tier | Component Name | Function Description |
|---|---|---|
| Core Aisle Frame Structure | Single-row Cold Aisle Frame | Main body for linearly arranged single-row enclosed cold aisle, including Al/CRS upright beam & connecting fittings |
| Double-row Cold Aisle Frame | Face-to-face rack layout forming central enclosed cold aisle, optimizing space utilization | |
| Single-row Hot Aisle Frame | Linear single-row enclosed hot aisle for concentrated hot air collection and improved return air efficiency | |
| Double-row Hot Aisle Frame | Back-to-back rack layout with central sealed hot aisle to maximize hot air capture and cut power consumption | |
| Aisle Sealing Accessories | Cold Aisle Skylight | Fixed/openable fire-rated skylight with fire linkage for auto opening during emergency fire |
| Cold Aisle Access Control | Card/fingerprint/password access controller with remote authorization & access log for aisle security management | |
| Custom EPDM Rubber Sealing Strip | Gap sealing between frame, rack and skylight, cold air leakage ≤5% | |
| Monitoring Module | Temp & Humidity Detector | High-precision sensor for real-time ambient data collection, remote monitoring & fault alarming |
| Air Velocity Transmitter | Monitor airflow speed inside aisle to optimize air distribution uniformity | |
| Differential Pressure Sensor | Real-time positive pressure tracking of cold aisle to guarantee stable positive-pressure operation | |
| Safety Linkage Parts | Fire Interlock Assembly | Interlock with fire alarm host to auto unlock skylight & end door for pressure relief and personnel evacuation |
| Emergency LED Lighting | Auto switch-on upon power failure for emergency escape illumination | |
| Auxiliary Heat Dissipation | Auxiliary Cooling Unit | Extra heat exchanger for high-density IT load scenarios |
| Adjustable Air Louver | Hot aisle exclusive component to modulate return airflow matching variable equipment power | |
| Auxiliary Fittings | Support Bracket | Al/steel bearing structure for aisle frame fixing and load bearing |
| Decorative Panel | Dustproof & ornamental cladding for integral appearance optimization | |
| Cable Management Trunking | Built-in wiring duct to arrange cables without blocking normal airflow |

III. System Classification
3.1 By Aisle Layout
| Type | Structural Feature | Applicable Scenario | Core Advantage |
|---|---|---|---|
| Single-row Cold Aisle | Racks line up along wall with sealed cold aisle & open hot aisle | Small narrow-space computer room, phased expansion project | Low cost, flexible layout, quick construction & easy maintenance |
| Double-row Cold Aisle | Face-to-face racks form middle enclosed cold aisle with open side hot aisles | Medium-large dense equipment IDC, high-density computing cluster | High space utilization, excellent cooling efficiency, PUE down to 1.2 for large-scale deployment |
| Single-row Hot Aisle | Wall-mounted single rack with sealed hot aisle & open cold aisle | Legacy computer room renovation, customized air-conditioning layout | High hot air capture rate, lower AC return air temperature and improved EER |
| Double-row Hot Aisle | Back-to-back racks with central sealed hot aisle & bilateral open cold aisles | Large core data center, ultra-high density server deployment | Optimal hot air isolation, prominent energy saving for heavy-load computing |
| Hybrid Hot/Cold Aisle | Flexible combination of sealed cold & hot aisle per site layout | Irregular old computer room, staged expansion project | Strong adaptability, shortened investment payback period |
3.2 By Sealing Grade
- Full-sealed Type: Complete enclosure with end door, skylight and full sealing strip, cold air leakage ≤5%, for strict temperature-controlled green data center
- Semi-sealed Type: Main frame sealed with partially open skylight/access door, balance of energy saving and daily maintenance convenience for medium-size room
- Economy Simple Type: Only core frame and partial sealing fitting, low investment & fast installation for temporary IT project and limited-budget reconstruction
3.3 By Control Mode
- Manual Control: Manual skylight & door operation for small low-maintenance computer room
- Auto Electric Control: Motorized skylight + intelligent access lock with local/remote control for medium-large IDC
- Intelligent Linked Control: Deep integration with BMS, fire alarm and cooling system for auto regulation & early warning, financial-grade core data center
3.4 By Air Supply Matching
- Under-floor Air Supply: Matched with raised-floor plenum air outlet
- In-row CRAC Matching: Near-end precision cooling with short airflow path and high efficiency
- Ceiling Air Supply: Top-inlet cold aisle for non-raised-floor computer room
- Hybrid Air Supply: Compatible with multiple air inlet modes for complicated site condition

IV. Standard BOM List (Brand: KITOZER)
4.1 Single-row Cold Aisle Standard Configuration
| No. | Item | Model | Qty | Unit | Specification |
|---|---|---|---|---|---|
| 1 | Single-row Cold Aisle Frame | KT-CD-01 | 1 | Set | 6063-T5 Al alloy, customized length for standard 42U rack |
| 2 | Aisle End Door | KT-CD-DM01 | 2 | Pc | Frameless explosion-proof tempered glass with mechanical lock, transmittance ≥90% |
| 3 | Fire Skylight | KT-CD-TC01 | 1 | Group | B1 fire rating aluminum frame, compatible with fire linkage |
| 4 | EPDM Sealing Strip | KT-CD-MF01 | 1 | Set | Full gap sealing, cold leakage ≤5% |
| 5 | Temp & RH Sensor | KT-MON-TH01 | 2 | Pc | -10~50℃, 0~100%RH, accuracy ±0.5℃/±3%RH |
| 6 | Differential Pressure Transmitter | KT-MON-PC01 | 1 | Pc | 0~100Pa measuring range, precision ±1Pa |
| 7 | Fire Linkage Controller | KT-FIRE-LK01 | 1 | Set | Interlock with FAS for auto skylight & door release |
| 8 | Adjustable Support Foot | KT-CD-ZZ01 | 4 | Pc | Steel structure, single bearing ≥500kg |
| 9 | Metal Decor Panel | KT-CD-ZS01 | 1 | Set | Dustproof metal cladding |
| 10 | Cable Trunking | KT-CD-CW01 | 1 | M | Al alloy internal wiring channel |
4.2 Double-row Cold Aisle Standard Configuration
| No. | Item | Model | Qty | Unit | Specification |
|---|---|---|---|---|---|
| 1 | Double-row Cold Aisle Frame | KT-CD-02 | 1 | Set | Al frame for 6~48 racks per modular section |
| 2 | Double-swing Access Door | KT-CD-DM02 | 2 | Pc | Smart lock supporting card/password/remote unlock |
| 3 | Motorized Fire Skylight | KT-CD-TC02 | 1 | Group | Electric flip opening ≥90°, built-in fire trigger module |
| 4 | Multi-function Access Control | KT-CD-MJ01 | 1 | Set | Fingerprint+IC+password three-in-one recognition |
| 5 | Full-set Sealing Rubber | KT-CD-MF02 | 1 | Set | Custom EPDM for all rack/frame gaps |
| 6 | High-precision Temp RH Sensor | KT-MON-TH02 | 4 | Pc | RS485 Modbus for environmental monitoring platform access |
| 7 | Airflow Speed Sensor | KT-MON-SD01 | 2 | Pc | 0~10m/s, tolerance ±0.1m/s |
| 8 | DP Sensor | KT-MON-PC02 | 2 | Pc | 0~100Pa real-time cold plenum pressure detection |
| 9 | Complete Fire Interlock Kit | KT-FIRE-LK02 | 1 | Set | Controller+electromagnetic lock+manual emergency button |
| 10 | Emergency LED Lamp | KT-CD-YJ01 | 2 | Pc | ≥90min backup duration after power loss |
| 11 | Auxiliary Cooling Fan | KT-CD-SR01 | 2 | Set | Extra heat exchange for high-density cabinet area |
| 12 | Load-bearing Support | KT-CD-ZZ02 | 8 | Pc | Height adjustable steel foot, ≥500kg each |
| 13 | Decorative Cover Plate | KT-CD-ZS02 | 1 | Set | Metal dust-proof outer panel |
| 14 | Integrated Cable Management | KT-CD-CW02 | 1 | Set | Trunk+wire organizer full kit |
4.3 Single-row Hot Aisle Standard Configuration
| No. | Item | Model | Qty | Unit | Remark |
|---|---|---|---|---|---|
| 1 | Single-row Hot Aisle Frame | KT-RD-01 | 1 | Set | Customizable length Al frame |
| 2 | Fireproof End Door | KT-RD-DM01 | 2 | Pc | Metal frame+B1 fireproof board with mechanical lock |
| 3 | Adjustable Air Louver | KT-RD-BY01 | 4 | Pc | Angle adjustable for return air regulation |
| 4 | High-temperature Resistant Seal | KT-RD-MF01 | 1 | Set | Heat-resistant EPDM rubber |
| 5 | Environment Sensor | KT-MON-TH01 | 2 | Pc | Standard temp&humidity detection |
| 6 | Support Bracket | KT-RD-ZZ01 | 4 | Pc | Adjustable load-bearing foot |
| 7 | Outer Decor Panel | KT-RD-ZS01 | 1 | Set | Dustproof metal shell |
4.4 Double-row Hot Aisle Standard Configuration
| No. | Item | Model | Qty | Unit | Remark |
|---|---|---|---|---|---|
| 1 | Double-row Hot Aisle Frame | KT-RD-02 | 1 | Set | Modular Al frame for 6~48 racks |
| 2 | Smart Fireproof Door | KT-RD-DM02 | 2 | Pc | Electric lock with remote management |
| 3 | Motorized Adjustable Louver | KT-RD-BY02 | 8 | Pc | Remote electric angle adjustment |
| 4 | High-temp Sealing Strip | KT-RD-MF02 | 1 | Set | Heat-resistant EPDM material |
| 5 | RH/Temp Detector | KT-MON-TH02 | 4 | Pc | RS485 communication protocol |
| 6 | Airflow Transmitter | KT-MON-SD01 | 2 | Pc | 0~10m/s airflow monitoring |
| 7 | Steel Support Foot | KT-RD-ZZ02 | 8 | Pc | Height adjustable bearing base |
| 8 | Decor Cover | KT-RD-ZS02 | 1 | Set | Integrated dustproof panel |
| 9 | Cable Trunking Kit | KT-RD-CW01 | 1 | Set | Complete internal wiring fitting |
4.5 Universal Spare Parts for All Aisle Types
| No. | Item | Model | Qty | Unit | Application |
|---|---|---|---|---|---|
| 1 | Universal Environmental Sensor | KT-MON-TH03 | 1 | Pc | POE powered, compatible for all aisle layout |
| 2 | General Fire Interlock Controller | KT-FIRE-LK03 | 1 | Pc | Unified signal processing for skylight & door linkage |
| 3 | Aisle Central Control Module | KT-CTL-01 | 1 | Set | Local/remote access to BMS platform |
| 4 | Universal Emergency Lamp | KT-EM-LIGHT01 | 1 | Pc | Auto power-off startup LED lighting |
| 5 | Maintenance Cleaning Kit | KT-CLEAN-01 | 1 | Set | Daily aisle upkeep accessories |

V. Airflow Principle Diagram Description
5.1 Single-row Cold Aisle Airflow
In-row CRAC / Underfloor Air Supply → Cold Aisle Inlet → Positive-Pressure Sealed Cold Aisle(5~10Pa) → Cabinet Front → IT Equipment → Cabinet Rear → Open Hot Aisle → AC Return Air → Cooling & Circulation
Feature: Precise cold air delivery, no air mixing, cooling efficiency +30%+.
5.2 Double-row Cold Aisle Airflow
Air Supply Source → Central Enclosed Cold Plenum(5~10Pa) → Bilateral Cabinet Intake → IT Load → Rear Exhaust → Two-side Open Hot Aisle → AC Return Plenum → Recycle Cooling
Feature: Central cold source feeding dual-side racks, high space utilization, minimum PUE down to1.2.
5.3 Single-row Hot Aisle Airflow
Open Cold Aisle Air Supply → Cabinet Front → IT Hardware → Rear Outlet → Negative-Pressure Sealed Hot Aisle → Hot Air Duct → AC Return Air → Circulation Cooling
Feature: Hot air capture ≥95%, lower AC inlet temperature and boost COP.
5.4 Double-row Hot Aisle Airflow
Bilateral Open Cold Intake → Cabinet Front → Equipment Heat Dissipation → Central Sealed Negative Hot Plenum → Concentrated Hot Air Outlet → Air Conditioner Return → Cyclic Cooling
Feature: Central hot air collection rate ≥98%, optimal solution for ultra-high density load, cooling consumption cut ≥40%.
5.5 Fire Linkage Logic
Fire Alarm Controller → Alarm Signal → Aisle Fire Interlock Host → Auto Skylight Opening + End Door Unlock + Audible&Visual Alarm + BMS Remote Alert
Feature: Instant pressure relief and evacuation guarantee under fire emergency.

VI. Key Technical Specifications
6.1 Aisle Frame Parameter
| Spec Item | Single Cold | Double Cold | Single Hot | Double Hot |
|---|---|---|---|---|
| Material | 6063-T5 Al / 2.0mm CRS | 6063-T5 Al / 2.0mm CRS | 6063-T5 Al / 2.0mm CRS | 6063-T5 Al / 2.0mm CRS |
| Surface Finish | Electrostatic powder coating customizable color | Same | Same | Same |
| Applicable Rack | 42U 600/800W×1000/1200D | Same | Same | Same |
| Length Range | 2000~6000mm custom | 3000~12000mm custom | 2000~6000mm custom | 3000~12000mm custom |
| Bearing Capacity | ≥500kg/m | ≥800kg/m | ≥500kg/m | ≥800kg/m |
| Fire Grade | B1 | B1 | B1 | B1 |
| IP Rating | IP20 | IP20 | IP20 | IP20 |
6.2 Cold Aisle Skylight Spec
| Parameter | KT-CD-TC01 Manual | KT-CD-TC02 Electric |
|---|---|---|
| Frame&Glass | Al+8mm explosion-proof tempered glass | Al+8mm explosion-proof tempered glass |
| Light Transmittance | ≥90% | ≥90% |
| Opening Mode | Manual flip | Electric rotate ≥90° |
| Fire Linkage | Optional accessory | Built-in auto fire trigger |
| Service Life | ≥10 Years | ≥10 Years |
6.3 Access Control Parameter(KT-CD-MJ01)
Fingerprint/Card/Password triple identification; Fingerprint storage ≥1000pcs; RS485/Ethernet communication; DC12V working; -10~+55℃ ambient; IP30 protection.
6.4 Temp&RH Sensor(KT-MON-TH02)
Temp:-40~+85℃(±0.5℃); Hum:0~100%RH(±3%RH); Modbus-RTU; DC12V/POE optional; IP20.
6.5 Fire Interlock Module(KT-FIRE-LK02)
DC24V input; dry contact signal; relay output 250VAC/10A; response ≤1s; -10~+55℃; IP30.

VII. Executive Standard Summary
| Component | Core Index | Compliance Standard |
|---|---|---|
| Aisle Frame | 2.0mm CRS/6063-T5 Al, electrostatic coating | GB/T30046-2013 |
| Skylight | 8mm tempered glass, B1 fire rating | GB50016-2014 |
| Access Controller | Multi-mode identification, remote communication | GB/T35656-2017 |
| EPDM Seal | Cold leakage ≤5%, -40~+120℃ resistant | GB/T10711-2006 |
| Environment Sensor | ±0.5℃/±3%RH, Modbus protocol | GB/T15478-2018 |
| Fire Linkage | Response ≤1s, DC24V drive | GB50116-2013 |
VIII. Application Industry & Scenarios
8.1 Core Data Center Industry
Cloud IDC, Financial Core Data Room, Internet Enterprise Computer Room, Telecom Operator Central Equipment Room
8.2 General Enterprise & Institutional Computer Room
Government Org IT Room, Private Enterprise Server Room, Medical HIS/PACS Data Center, University HPC Research Lab
8.3 Special Scenario
Edge Computing Node, Prefabricated Modular Data Center, Container Outdoor DC, Precision Instrument Laboratory
8.4 High-density Specialized Computing
AI Training Center, Blockchain Node IDC, 5G Core Equipment Room, Industrial Control Computer Room

IX. Core Product Advantages
9.1 Energy Saving & PUE Reduction
- Complete cold/hot separation eliminates airflow short circuit, cooling efficiency +30%~45%, PUE down to 1.2
- Air leakage cut from traditional 15~20% down below 5%, remarkable power saving
- Compatible with free cooling to extend natural cold source utilization period
- In-row near-end cooling shortens airflow path and improves AC EER by 45%
9.2 Modular Flexible Customization
- Prefabricated modular parts cut construction period over 50%
- Free combination of single/double cold/hot aisle adapting arbitrary site layout
- Compatible with existing rack & AC equipment to lower retrofit CAPEX
- Support phased capacity expansion to protect initial investment
9.3 Precise Temperature Control & Stable Operation
Cold aisle kept 18~22℃, temperature deviation ≤1℃ with no hotspot over 24℃; RH stabilized 45~60% with fluctuation ≤±3% complying GB50174; real-time DP/temp monitoring + fire auto interlock for equipment & personnel safety.
9.4 Intelligent O&M Management
Local + remote centralized management via BMS platform; early fault warning with 10-second pinpoint; access log & authority management; modular quick replacement to reduce maintenance cost.
9.5 Safety & Eco-friendly
All materials RoHS compliant; B1 fire rating; seismic resistance Grade 8; ISO9001 certified with 5-year full-system warranty & lifetime technical service.
X. Tender Bid Core Specification
10.1 Mandatory Technical Index
- Support four core layout: single/double cold & single/double hot aisle for full-range solution
- Cold air leakage ≤5%
- Cold aisle temp 18~22℃, regional deviation ≤1℃, no hotspot>24℃ per GB50174
- RH 45~60% with daily fluctuation ≤±3%
- System optimized PUE ≤1.3 for large data center
- Sealed hot aisle air capture rate ≥95%
- Frame:6063-T5 Al or ≥2.0mm CRS with electrostatic coating
- Skylight glass ≥8mm tempered, transmittance≥90%
- Fire linkage response ≤1s with auto skylight/door release
- Sensor support RS485 Modbus to connect centralized environmental monitoring platform
10.2 Qualification Requirement
- ISO9001 manufacturer certification; fire test inspection report; GB50174 conformity document; ≥3-year project experience with similar data center references; 5-year system warranty commitment.
10.3 After-sale Service Standard
Professional design & construction team; 7×24h technical support, ≤2h remote response, onsite troubleshooting within 48h; free user operation training.
XI. Four Customized Turnkey Solutions
11.1 Small Room Single-row Cold Aisle
Applicable: ≤10 racks, ≤3kW/rack, floor area<100㎡
Adopt standard single-row cold aisle kit, match underfloor/ceiling air supply without AC replacement, manual skylight + basic environmental sensor; construction ≤3 days.
Effect: Cooling efficiency +30%, PUE<1.5, aisle temp stabilized 18~22℃, deviation ≤1℃.
11.2 Medium IDC Double-row Cold Aisle
Applicable:10~48 racks,3~8kW/rack,100~500㎡ room
Full-set double-row cold aisle with motorized skylight, smart access, full monitoring + fire linkage matched with in-row CRAC, remote BMS control; construction ≤7 days.
Effect: Efficiency +40%, PUE down to1.2, temp deviation ≤0.5℃ zero hotspot.
11.3 Large-scale Hybrid Hot&Cold Aisle DC
Applicable:>40 racks,>8kW/rack, over500㎡ large data center
Custom hybrid cold/hot aisle layout, match free-cooling fluorine pump in-row AC, full-function multi-parameter monitoring + AI airflow self-adaptive optimization, dock with DCIM platform; parallel modular construction.
Effect: Cooling efficiency +45%, PUE≈1.15, temp 18~20℃, hot air capture>95%.
11.4 Legacy Room Hot Aisle Retrofit
Applicable: Existing open room with severe hot air backflow & overheat hotspot
Seal hot aisle only without modifying original cold layout & air conditioner, install adjustable louver + temp sensor; construction ≤5 days without service interruption.
Effect: Hot capture≥95%, AC return temp drop3~5℃, cooling efficiency+25% with hotspot eliminated.
XII. Typical Engineering Cases
Case1: Financial Core DC Double Cold Aisle Project
30 racks@5kW/rack, original PUE=1.8 with severe hotspot; after KITOZER double cold aisle + in-row cooling, PUE down to1.2, annual power saving ≈800,000CNY, temp stabilized 20℃(ΔT≤0.5℃), passed green data center certification.
Case2: Internet Small Room Single Cold Retrofit
15 narrow-space racks, original PUE=1.7; 2-day quick reconstruction without service outage, PUE=1.45, annual saving≈250,000CNY, ROI<1.5 years.
Case3: Government Office Hot Aisle Renovation
8 standard racks, original AC return temp 35℃; single hot aisle sealed solution finished within 1 day, return temp reduced to28℃, PUE=1.5 as local energy-saving demonstration project.
Case4: Medical Hybrid Aisle Data Center
25 racks@6kW/rack for HIS/PACS 24/7 continuous operation; core zone double cold + edge single hot hybrid layout, temp fixed 20℃, RH=50%(fluct±2%), PUE=1.25, annual electricity saving≈600,000CNY.
XIII. SEO Keywords & Tags
Core Primary Keywords
Modular Hot Cold Aisle Containment, KITOZER Aisle Containment, Single/Double Row Cold Aisle, Data Center Airflow Management, Data Center PUE Optimization, Legacy Computer Room Cooling Retrofit, Fire Linked Cold Aisle Skylight
Long-tail SEO Keywords
High-density server cold aisle design, In-row CRAC matching aisle system, cold aisle tender specification standard, EPDM sealing cold leakage control, modular prefabricated data center construction
Product Hashtag
#KITOZERAisle #ModularColdAisle #DataCenterEnergySaving #HotAisleContainment #GreenIDC #ColdAisleRetrofit #FireInterlockAisle