Modular Hot and Cold Aisle Containment | KITOZER

Table of Contents

I. System Introduction

KITOZER Modular Hot & Cold Aisle Containment is a high-efficiency airflow management solution tailor-made for data centers, computer rooms and IT equipment operating environments. Physical separation fully isolates cold intake zone at cabinet front and hot exhaust zone at cabinet rear to form independent enclosed cold plenum and hot plenum, realizing precise airflow control, thoroughly eliminating cross-mixing & short-circuit of cold/hot air, drastically boosting cooling efficiency, cutting down PUE and extending service life of IT equipment with stable, secure and high-efficiency operating surroundings.

Designed on modular philosophy, the system supports rapid on-site deployment, flexible capacity expansion and standardized management, compatible with mainstream server racks, precision air conditioners and environmental monitoring systems. Multiple configurable layouts are available: single/double-row cold aisle, single/double-row hot aisle and hybrid aisle combination, covering full-range airflow demands from small-medium computer rooms to large-scale hyperscale data centers.

Core Working Principle

Enclosed cold aisle builds positive static pressure (5~10Pa relative pressure). Chilled air is delivered into cold aisle via in-row CRAC or under-floor air supply, flows through cabinet front door into IT hardware; after heat absorption, hot air exhausts from cabinet rear into hot aisle, then returns to air conditioner for re-cooling to complete cyclic airflow circulation and maximize energy utilization efficiency.

modular hot and cold aisle system solutions (1)

II. System Composition

System TierComponent NameFunction Description
Core Aisle Frame StructureSingle-row Cold Aisle FrameMain body for linearly arranged single-row enclosed cold aisle, including Al/CRS upright beam & connecting fittings
Double-row Cold Aisle FrameFace-to-face rack layout forming central enclosed cold aisle, optimizing space utilization
Single-row Hot Aisle FrameLinear single-row enclosed hot aisle for concentrated hot air collection and improved return air efficiency
Double-row Hot Aisle FrameBack-to-back rack layout with central sealed hot aisle to maximize hot air capture and cut power consumption
Aisle Sealing AccessoriesCold Aisle SkylightFixed/openable fire-rated skylight with fire linkage for auto opening during emergency fire
Cold Aisle Access ControlCard/fingerprint/password access controller with remote authorization & access log for aisle security management
Custom EPDM Rubber Sealing StripGap sealing between frame, rack and skylight, cold air leakage ≤5%
Monitoring ModuleTemp & Humidity DetectorHigh-precision sensor for real-time ambient data collection, remote monitoring & fault alarming
Air Velocity TransmitterMonitor airflow speed inside aisle to optimize air distribution uniformity
Differential Pressure SensorReal-time positive pressure tracking of cold aisle to guarantee stable positive-pressure operation
Safety Linkage PartsFire Interlock AssemblyInterlock with fire alarm host to auto unlock skylight & end door for pressure relief and personnel evacuation
Emergency LED LightingAuto switch-on upon power failure for emergency escape illumination
Auxiliary Heat DissipationAuxiliary Cooling UnitExtra heat exchanger for high-density IT load scenarios
Adjustable Air LouverHot aisle exclusive component to modulate return airflow matching variable equipment power
Auxiliary FittingsSupport BracketAl/steel bearing structure for aisle frame fixing and load bearing
Decorative PanelDustproof & ornamental cladding for integral appearance optimization
Cable Management TrunkingBuilt-in wiring duct to arrange cables without blocking normal airflow
modular hot and cold aisle system solutions (2)

III. System Classification

3.1 By Aisle Layout

TypeStructural FeatureApplicable ScenarioCore Advantage
Single-row Cold AisleRacks line up along wall with sealed cold aisle & open hot aisleSmall narrow-space computer room, phased expansion projectLow cost, flexible layout, quick construction & easy maintenance
Double-row Cold AisleFace-to-face racks form middle enclosed cold aisle with open side hot aislesMedium-large dense equipment IDC, high-density computing clusterHigh space utilization, excellent cooling efficiency, PUE down to 1.2 for large-scale deployment
Single-row Hot AisleWall-mounted single rack with sealed hot aisle & open cold aisleLegacy computer room renovation, customized air-conditioning layoutHigh hot air capture rate, lower AC return air temperature and improved EER
Double-row Hot AisleBack-to-back racks with central sealed hot aisle & bilateral open cold aislesLarge core data center, ultra-high density server deploymentOptimal hot air isolation, prominent energy saving for heavy-load computing
Hybrid Hot/Cold AisleFlexible combination of sealed cold & hot aisle per site layoutIrregular old computer room, staged expansion projectStrong adaptability, shortened investment payback period

3.2 By Sealing Grade

  • Full-sealed Type: Complete enclosure with end door, skylight and full sealing strip, cold air leakage ≤5%, for strict temperature-controlled green data center
  • Semi-sealed Type: Main frame sealed with partially open skylight/access door, balance of energy saving and daily maintenance convenience for medium-size room
  • Economy Simple Type: Only core frame and partial sealing fitting, low investment & fast installation for temporary IT project and limited-budget reconstruction

3.3 By Control Mode

  • Manual Control: Manual skylight & door operation for small low-maintenance computer room
  • Auto Electric Control: Motorized skylight + intelligent access lock with local/remote control for medium-large IDC
  • Intelligent Linked Control: Deep integration with BMS, fire alarm and cooling system for auto regulation & early warning, financial-grade core data center

3.4 By Air Supply Matching

  • Under-floor Air Supply: Matched with raised-floor plenum air outlet
  • In-row CRAC Matching: Near-end precision cooling with short airflow path and high efficiency
  • Ceiling Air Supply: Top-inlet cold aisle for non-raised-floor computer room
  • Hybrid Air Supply: Compatible with multiple air inlet modes for complicated site condition
modular hot and cold aisle system solutions (3)

IV. Standard BOM List (Brand: KITOZER)

4.1 Single-row Cold Aisle Standard Configuration

No.ItemModelQtyUnitSpecification
1Single-row Cold Aisle FrameKT-CD-011Set6063-T5 Al alloy, customized length for standard 42U rack
2Aisle End DoorKT-CD-DM012PcFrameless explosion-proof tempered glass with mechanical lock, transmittance ≥90%
3Fire SkylightKT-CD-TC011GroupB1 fire rating aluminum frame, compatible with fire linkage
4EPDM Sealing StripKT-CD-MF011SetFull gap sealing, cold leakage ≤5%
5Temp & RH SensorKT-MON-TH012Pc-10~50℃, 0~100%RH, accuracy ±0.5℃/±3%RH
6Differential Pressure TransmitterKT-MON-PC011Pc0~100Pa measuring range, precision ±1Pa
7Fire Linkage ControllerKT-FIRE-LK011SetInterlock with FAS for auto skylight & door release
8Adjustable Support FootKT-CD-ZZ014PcSteel structure, single bearing ≥500kg
9Metal Decor PanelKT-CD-ZS011SetDustproof metal cladding
10Cable TrunkingKT-CD-CW011MAl alloy internal wiring channel

4.2 Double-row Cold Aisle Standard Configuration

No.ItemModelQtyUnitSpecification
1Double-row Cold Aisle FrameKT-CD-021SetAl frame for 6~48 racks per modular section
2Double-swing Access DoorKT-CD-DM022PcSmart lock supporting card/password/remote unlock
3Motorized Fire SkylightKT-CD-TC021GroupElectric flip opening ≥90°, built-in fire trigger module
4Multi-function Access ControlKT-CD-MJ011SetFingerprint+IC+password three-in-one recognition
5Full-set Sealing RubberKT-CD-MF021SetCustom EPDM for all rack/frame gaps
6High-precision Temp RH SensorKT-MON-TH024PcRS485 Modbus for environmental monitoring platform access
7Airflow Speed SensorKT-MON-SD012Pc0~10m/s, tolerance ±0.1m/s
8DP SensorKT-MON-PC022Pc0~100Pa real-time cold plenum pressure detection
9Complete Fire Interlock KitKT-FIRE-LK021SetController+electromagnetic lock+manual emergency button
10Emergency LED LampKT-CD-YJ012Pc≥90min backup duration after power loss
11Auxiliary Cooling FanKT-CD-SR012SetExtra heat exchange for high-density cabinet area
12Load-bearing SupportKT-CD-ZZ028PcHeight adjustable steel foot, ≥500kg each
13Decorative Cover PlateKT-CD-ZS021SetMetal dust-proof outer panel
14Integrated Cable ManagementKT-CD-CW021SetTrunk+wire organizer full kit

4.3 Single-row Hot Aisle Standard Configuration

No.ItemModelQtyUnitRemark
1Single-row Hot Aisle FrameKT-RD-011SetCustomizable length Al frame
2Fireproof End DoorKT-RD-DM012PcMetal frame+B1 fireproof board with mechanical lock
3Adjustable Air LouverKT-RD-BY014PcAngle adjustable for return air regulation
4High-temperature Resistant SealKT-RD-MF011SetHeat-resistant EPDM rubber
5Environment SensorKT-MON-TH012PcStandard temp&humidity detection
6Support BracketKT-RD-ZZ014PcAdjustable load-bearing foot
7Outer Decor PanelKT-RD-ZS011SetDustproof metal shell

4.4 Double-row Hot Aisle Standard Configuration

No.ItemModelQtyUnitRemark
1Double-row Hot Aisle FrameKT-RD-021SetModular Al frame for 6~48 racks
2Smart Fireproof DoorKT-RD-DM022PcElectric lock with remote management
3Motorized Adjustable LouverKT-RD-BY028PcRemote electric angle adjustment
4High-temp Sealing StripKT-RD-MF021SetHeat-resistant EPDM material
5RH/Temp DetectorKT-MON-TH024PcRS485 communication protocol
6Airflow TransmitterKT-MON-SD012Pc0~10m/s airflow monitoring
7Steel Support FootKT-RD-ZZ028PcHeight adjustable bearing base
8Decor CoverKT-RD-ZS021SetIntegrated dustproof panel
9Cable Trunking KitKT-RD-CW011SetComplete internal wiring fitting

4.5 Universal Spare Parts for All Aisle Types

No.ItemModelQtyUnitApplication
1Universal Environmental SensorKT-MON-TH031PcPOE powered, compatible for all aisle layout
2General Fire Interlock ControllerKT-FIRE-LK031PcUnified signal processing for skylight & door linkage
3Aisle Central Control ModuleKT-CTL-011SetLocal/remote access to BMS platform
4Universal Emergency LampKT-EM-LIGHT011PcAuto power-off startup LED lighting
5Maintenance Cleaning KitKT-CLEAN-011SetDaily aisle upkeep accessories
modular hot and cold aisle system solutions (4)

V. Airflow Principle Diagram Description

5.1 Single-row Cold Aisle Airflow

In-row CRAC / Underfloor Air Supply → Cold Aisle Inlet → Positive-Pressure Sealed Cold Aisle(5~10Pa) → Cabinet Front → IT Equipment → Cabinet Rear → Open Hot Aisle → AC Return Air → Cooling & Circulation

Feature: Precise cold air delivery, no air mixing, cooling efficiency +30%+.

5.2 Double-row Cold Aisle Airflow

Air Supply Source → Central Enclosed Cold Plenum(5~10Pa) → Bilateral Cabinet Intake → IT Load → Rear Exhaust → Two-side Open Hot Aisle → AC Return Plenum → Recycle Cooling

Feature: Central cold source feeding dual-side racks, high space utilization, minimum PUE down to1.2.

5.3 Single-row Hot Aisle Airflow

Open Cold Aisle Air Supply → Cabinet Front → IT Hardware → Rear Outlet → Negative-Pressure Sealed Hot Aisle → Hot Air Duct → AC Return Air → Circulation Cooling

Feature: Hot air capture ≥95%, lower AC inlet temperature and boost COP.

5.4 Double-row Hot Aisle Airflow

Bilateral Open Cold Intake → Cabinet Front → Equipment Heat Dissipation → Central Sealed Negative Hot Plenum → Concentrated Hot Air Outlet → Air Conditioner Return → Cyclic Cooling

Feature: Central hot air collection rate ≥98%, optimal solution for ultra-high density load, cooling consumption cut ≥40%.

5.5 Fire Linkage Logic

Fire Alarm Controller → Alarm Signal → Aisle Fire Interlock Host → Auto Skylight Opening + End Door Unlock + Audible&Visual Alarm + BMS Remote Alert

Feature: Instant pressure relief and evacuation guarantee under fire emergency.

modular hot and cold aisle system solutions (5)

VI. Key Technical Specifications

6.1 Aisle Frame Parameter

Spec ItemSingle ColdDouble ColdSingle HotDouble Hot
Material6063-T5 Al / 2.0mm CRS6063-T5 Al / 2.0mm CRS6063-T5 Al / 2.0mm CRS6063-T5 Al / 2.0mm CRS
Surface FinishElectrostatic powder coating customizable colorSameSameSame
Applicable Rack42U 600/800W×1000/1200DSameSameSame
Length Range2000~6000mm custom3000~12000mm custom2000~6000mm custom3000~12000mm custom
Bearing Capacity≥500kg/m≥800kg/m≥500kg/m≥800kg/m
Fire GradeB1B1B1B1
IP RatingIP20IP20IP20IP20

6.2 Cold Aisle Skylight Spec

ParameterKT-CD-TC01 ManualKT-CD-TC02 Electric
Frame&GlassAl+8mm explosion-proof tempered glassAl+8mm explosion-proof tempered glass
Light Transmittance≥90%≥90%
Opening ModeManual flipElectric rotate ≥90°
Fire LinkageOptional accessoryBuilt-in auto fire trigger
Service Life≥10 Years≥10 Years

6.3 Access Control Parameter(KT-CD-MJ01)

Fingerprint/Card/Password triple identification; Fingerprint storage ≥1000pcs; RS485/Ethernet communication; DC12V working; -10~+55℃ ambient; IP30 protection.

6.4 Temp&RH Sensor(KT-MON-TH02)

Temp:-40~+85℃(±0.5℃); Hum:0~100%RH(±3%RH); Modbus-RTU; DC12V/POE optional; IP20.

6.5 Fire Interlock Module(KT-FIRE-LK02)

DC24V input; dry contact signal; relay output 250VAC/10A; response ≤1s; -10~+55℃; IP30.

modular hot and cold aisle system solutions (6)

VII. Executive Standard Summary

ComponentCore IndexCompliance Standard
Aisle Frame2.0mm CRS/6063-T5 Al, electrostatic coatingGB/T30046-2013
Skylight8mm tempered glass, B1 fire ratingGB50016-2014
Access ControllerMulti-mode identification, remote communicationGB/T35656-2017
EPDM SealCold leakage ≤5%, -40~+120℃ resistantGB/T10711-2006
Environment Sensor±0.5℃/±3%RH, Modbus protocolGB/T15478-2018
Fire LinkageResponse ≤1s, DC24V driveGB50116-2013

VIII. Application Industry & Scenarios

8.1 Core Data Center Industry

Cloud IDC, Financial Core Data Room, Internet Enterprise Computer Room, Telecom Operator Central Equipment Room

8.2 General Enterprise & Institutional Computer Room

Government Org IT Room, Private Enterprise Server Room, Medical HIS/PACS Data Center, University HPC Research Lab

8.3 Special Scenario

Edge Computing Node, Prefabricated Modular Data Center, Container Outdoor DC, Precision Instrument Laboratory

8.4 High-density Specialized Computing

AI Training Center, Blockchain Node IDC, 5G Core Equipment Room, Industrial Control Computer Room

modular hot and cold aisle system solutions (7)

IX. Core Product Advantages

9.1 Energy Saving & PUE Reduction

  • Complete cold/hot separation eliminates airflow short circuit, cooling efficiency +30%~45%, PUE down to 1.2
  • Air leakage cut from traditional 15~20% down below 5%, remarkable power saving
  • Compatible with free cooling to extend natural cold source utilization period
  • In-row near-end cooling shortens airflow path and improves AC EER by 45%

9.2 Modular Flexible Customization

  • Prefabricated modular parts cut construction period over 50%
  • Free combination of single/double cold/hot aisle adapting arbitrary site layout
  • Compatible with existing rack & AC equipment to lower retrofit CAPEX
  • Support phased capacity expansion to protect initial investment

9.3 Precise Temperature Control & Stable Operation

Cold aisle kept 18~22℃, temperature deviation ≤1℃ with no hotspot over 24℃; RH stabilized 45~60% with fluctuation ≤±3% complying GB50174; real-time DP/temp monitoring + fire auto interlock for equipment & personnel safety.

9.4 Intelligent O&M Management

Local + remote centralized management via BMS platform; early fault warning with 10-second pinpoint; access log & authority management; modular quick replacement to reduce maintenance cost.

9.5 Safety & Eco-friendly

All materials RoHS compliant; B1 fire rating; seismic resistance Grade 8; ISO9001 certified with 5-year full-system warranty & lifetime technical service.

X. Tender Bid Core Specification

10.1 Mandatory Technical Index

  1. Support four core layout: single/double cold & single/double hot aisle for full-range solution
  2. Cold air leakage ≤5%
  3. Cold aisle temp 18~22℃, regional deviation ≤1℃, no hotspot>24℃ per GB50174
  4. RH 45~60% with daily fluctuation ≤±3%
  5. System optimized PUE ≤1.3 for large data center
  6. Sealed hot aisle air capture rate ≥95%
  7. Frame:6063-T5 Al or ≥2.0mm CRS with electrostatic coating
  8. Skylight glass ≥8mm tempered, transmittance≥90%
  9. Fire linkage response ≤1s with auto skylight/door release
  10. Sensor support RS485 Modbus to connect centralized environmental monitoring platform

10.2 Qualification Requirement

  • ISO9001 manufacturer certification; fire test inspection report; GB50174 conformity document; ≥3-year project experience with similar data center references; 5-year system warranty commitment.

10.3 After-sale Service Standard

Professional design & construction team; 7×24h technical support, ≤2h remote response, onsite troubleshooting within 48h; free user operation training.

XI. Four Customized Turnkey Solutions

11.1 Small Room Single-row Cold Aisle

Applicable: ≤10 racks, ≤3kW/rack, floor area<100㎡

Adopt standard single-row cold aisle kit, match underfloor/ceiling air supply without AC replacement, manual skylight + basic environmental sensor; construction ≤3 days.

Effect: Cooling efficiency +30%, PUE<1.5, aisle temp stabilized 18~22℃, deviation ≤1℃.

11.2 Medium IDC Double-row Cold Aisle

Applicable:10~48 racks,3~8kW/rack,100~500㎡ room

Full-set double-row cold aisle with motorized skylight, smart access, full monitoring + fire linkage matched with in-row CRAC, remote BMS control; construction ≤7 days.

Effect: Efficiency +40%, PUE down to1.2, temp deviation ≤0.5℃ zero hotspot.

11.3 Large-scale Hybrid Hot&Cold Aisle DC

Applicable:>40 racks,>8kW/rack, over500㎡ large data center

Custom hybrid cold/hot aisle layout, match free-cooling fluorine pump in-row AC, full-function multi-parameter monitoring + AI airflow self-adaptive optimization, dock with DCIM platform; parallel modular construction.

Effect: Cooling efficiency +45%, PUE≈1.15, temp 18~20℃, hot air capture>95%.

11.4 Legacy Room Hot Aisle Retrofit

Applicable: Existing open room with severe hot air backflow & overheat hotspot

Seal hot aisle only without modifying original cold layout & air conditioner, install adjustable louver + temp sensor; construction ≤5 days without service interruption.

Effect: Hot capture≥95%, AC return temp drop3~5℃, cooling efficiency+25% with hotspot eliminated.

XII. Typical Engineering Cases

Case1: Financial Core DC Double Cold Aisle Project

30 racks@5kW/rack, original PUE=1.8 with severe hotspot; after KITOZER double cold aisle + in-row cooling, PUE down to1.2, annual power saving ≈800,000CNY, temp stabilized 20℃(ΔT≤0.5℃), passed green data center certification.

Case2: Internet Small Room Single Cold Retrofit

15 narrow-space racks, original PUE=1.7; 2-day quick reconstruction without service outage, PUE=1.45, annual saving≈250,000CNY, ROI<1.5 years.

Case3: Government Office Hot Aisle Renovation

8 standard racks, original AC return temp 35℃; single hot aisle sealed solution finished within 1 day, return temp reduced to28℃, PUE=1.5 as local energy-saving demonstration project.

Case4: Medical Hybrid Aisle Data Center

25 racks@6kW/rack for HIS/PACS 24/7 continuous operation; core zone double cold + edge single hot hybrid layout, temp fixed 20℃, RH=50%(fluct±2%), PUE=1.25, annual electricity saving≈600,000CNY.

XIII. SEO Keywords & Tags

Core Primary Keywords

Modular Hot Cold Aisle Containment, KITOZER Aisle Containment, Single/Double Row Cold Aisle, Data Center Airflow Management, Data Center PUE Optimization, Legacy Computer Room Cooling Retrofit, Fire Linked Cold Aisle Skylight

Long-tail SEO Keywords

High-density server cold aisle design, In-row CRAC matching aisle system, cold aisle tender specification standard, EPDM sealing cold leakage control, modular prefabricated data center construction

Product Hashtag

#KITOZERAisle #ModularColdAisle #DataCenterEnergySaving #HotAisleContainment #GreenIDC #ColdAisleRetrofit #FireInterlockAisle

Shopping Cart