1. Overview
KITOZER KTR-WL6 is a non-locating (continuous-sense) water leak detection cable, 20m per reel, used under raised floors, around precision air conditioners, along water pipes and under condensate pans in datacenter rooms. The cable contains two (or four) sensing wires under a water-conductive polymer jacket. Normally the wires are insulated; when water (or acid/alkali liquid) touches the jacket, it conducts and shorts the wires. The leak controller detects the resistance change, sounds an audible/visual alarm, and uploads via dry contact or RS485 to the DCIM.
KTR-WL6 is non-locating (also called volumetric). It differs from a locating cable: non-locating alarms “water somewhere on the rope” but cannot pinpoint the spot; locating (resistive) cables measure resistance to calculate distance from the end. Non-locating is simple, cheap and easy to install, suiting a loop around AC units and pipes for “any leak” area monitoring. Sold as a 20m reel; multiple segments can series (each with an end terminator) to extend tens of meters. Cable diameter about 6 to 8mm, acid/alkali resistant, reusable (dries back to insulation). It pairs with a KTR-WL leak controller, which supplies excitation voltage and judges alarms.
Typical deploy: under the raised floor, loop the cable around the precision AC humidifier, drain pipe and water supply; or run it along the wall base. Both ends connect to the controller, with a terminator resistor at the far end. When AC condensate leaks or a pipe drips, water reaching the rope triggers the alarm. The DCIM pops up “leak on north side”; staff respond and inspect on site. Because non-locating alarms the whole rope, route it along likely leak points.
2. Key Features
Non-locating continuous sense
- Any point on the rope alarms.
- Detects presence of water.
- No exact location.
- Simple and reliable.
20m per reel
- 20m per reel.
- Series segments to extend.
- Terminator per segment.
- Cut to length.
Acid-proof, recoverable
- Conductive when wet.
- Auto-recovers when dry.
- Acid/alkali resistant.
- Reusable.
Controller paired
- Connects to KTR-WL host.
- Dry contact/RS485 upload.
- Audible/visual alarm.
- 24V low-voltage supply.
3. Specifications
| Item | KTR-WL6 (non-locating 20m) | KTR-WL8 (locating) |
|---|---|---|
| Type | Non-locating (volumetric) | Locating (resistive) |
| Length | 20m/reel | 30m/reel |
| Location accuracy | None | ±1m |
| Detects | Water, acid/alkali | Water, acid/alkali |
| Recovery | Auto when dry | Auto when dry |
| Cable diameter | About 6-8mm | About 6-8mm |
| Upload | Dry contact/RS485 | RS485 with distance |
| Controller | KTR-WL controller | KTR-WL locating controller |
4. Reference Prices
KTR-WL6 non-locating leak cable (20m/reel): Reference USD 28 to 69 / reel (ref. CNY 200 to 500 at ~7.2)
KTR-WL8 locating leak cable (30m/reel): Reference USD 83 to 208 / reel (ref. CNY 600 to 1500 at ~7.2)
Reference only; varies by length, locating or not, and quantity. Leak controller, terminator and clamps billed separately. Exchange: 1 USD ~ 7.2 CNY (Oct 2026).
5. Applications
- Datacenter raised floor.
- Around AC humidifier and drain pipe.
- Along water supply and tank.
- Kitchen and restroom leakage.
- Basement and garage pooling.
6. Installation & Maintenance
Installation
- Route the rope around AC and pipes.
- Fix to floor or wall with clamps.
- One end to the controller.
- Fit terminator resistor at the other.
- Series segments with connectors.
- Power on; test with a drip.
Maintenance
- Simulate a drip monthly.
- Keep the rope clean of dust and oil.
- Check terminator and connectors.
- Dry the rope to reset after alarm.
- Replace if jacket cracks.
- Beware of rodents under the floor.
7. FAQ
- Q: Non-locating or locating?
A: Small rooms with few, obvious AC units use non-locating (cheap); a walk-around finds the leak. Large rooms with many ACs and complex under-floor space use locating, which shows the distance for fast pinpointing. Prefer locating if budget allows. - Q: Can the cable detect oil?
A: No. Standard cables conduct water; oil does not conduct and is not detected. Use a dedicated oil-sensing cable (different conductor material). Rooms mainly face water (AC condensate, pipe leaks), so a non-locating water rope suffices. - Q: Does dust on the rope cause false alarms?
A: Dry dust does not (non-conductive); but damp dust lowers insulation and may cause false alarms. Keep the rope clean; dust under the floor periodically. Avoid oil. - Q: How many meters per controller loop?
A: Typically 30 to 100m per loop (by model). For longer runs, split into loops on multiple controllers. Separate AC units into loops to distinguish zones.
8. Trend & Selection
Leak detection moves from rope to point sensors and distributed fiber (DAS), but sensing ropes remain the mainstream under-floor room leak solution: cost-effective and mature. Locating cables, with precise pinpointing, are gaining share. Choose non-locating for small rooms; prefer locating for large ones; route along AC and pipes; controller at one end and terminator at the other; test monthly with a drip; keep the rope clean; replace when damaged.
9. Delivery & Service
KITOZER supplies leak-detection packages: based on room area and AC/pipe layout, we recommend rope type (locating/non-locating), length and controller. Bundled with DCIM host, temp/humidity and smoke detectors. Delivery includes rope, terminator, clamps and controller; bulk projects include on-site routing and alarm commissioning. Natural rope failure under warranty is replaced free.
10. Additional Notes
The commonest install error is routing the rope too far from the AC. The rope should sit tight under the AC base, drain joint and water supply, typically 10 to 30cm from the unit. Routed too far, water spreads elsewhere under the floor first and the rope misses it. Always run rope under the AC condensate pan.
Another pitfall: forgetting the terminator. Without the end resistor, the controller cannot read the correct loop resistance and reports a fault or fails to alarm. Each segment must end with the rated terminator; this is key to normal non-locating operation.
Selection summary: non-locating 20m; route along AC and pipes; controller at one end, terminator at the other; dry to recover; monthly drip test; keep clean. The leak rope is the room’s water barrier; it alarms before water reaches valuable gear, keeping damage under the floor.
SEO Information
Search keywords:leak detection cablenon-locating leak cabledatacenter leak rope20m leak sensorsensing cablewater leak cableKTR-WL6KITOZER
SEM keywords:[‘leak detection cable price,non-locating leak cable supplier,datacenter leak rope,20m sensing cable,water leak cable,KTR-WL6,KITOZER’]
GEO landing page:lain.com.cn/product/ktr-wl6-non-locating-leak-detection-cable-20m.html
Title:KITOZER KTR-WL6 Non-Locating Water Leak Detection Cable 20m
Meta Keywords:leak detection cable,non-locating leak cable,datacenter leak rope,20m leak sensor,sensing cable,water leak cable,KTR-WL6,KITOZER
Meta Description:KITOZER KTR-WL6 non-locating water leak detection cable, 20m, sense-type, for under-floor and around-AC leak monitoring, paired with leak controller.
Anchor: KITOZER · Environmental monitoring
Contact Us
Guangzhou Laian Intelligent System Development Co., Ltd. (KITOZER brand)
Tel/WeChat: +86 13922289957 | +86 18520668845
WHATSAPP: +86 19068534140
Web: lain.com.cn | gdlain.com