KITOZER
KITOZER

KITOZER ODF 24 port loaded fiber distribution

KITOZER KTR-ODF24 24-Port Fiber Distribution Frame

Brand: KITOZER Series: KTR-ODF24 Category: Data Center Engineering / Optical Distribution

fiber ODF24-portloadedsplice trayKTR-ODF24

1. Overview

In the room’s weak-current room, incoming carrier cables, vertical building risers and horizontal rack cables must all terminate into pluggable connectors — that termination point is the Optical Distribution Frame (ODF). It is a 19-inch rack metal box: the back anchors the cable, the inside splices the fibers, and the front is a row of adapter ports. Patch cords cross-connect incoming and equipment sides. The ODF does three jobs: anchor the cable (strength member on the ground post, fibers into splice trays); splice and terminate (bare fiber fusion-spliced to pigtails, protected by heat-shrink sleeves, excess fiber coiled); and manage moves (re-patch on the front without touching splices). The 24-port ODF is the most common size: 1U or 2U, 24 adapter positions on the front, two 12-fiber splice trays inside. A fully loaded unit includes 24 adapters, 24 pigtails and 2 splice trays.

The KTR-ODF24 series: KTR-ODF24-SC (24×SC/UPC square, mainstream data rooms); KTR-ODF24-FC (24×FC round metal, legacy telecom/CATV); KTR-ODF24-LC (24 LC duplex = 48 fibers, high-density IDCs); KTR-ODF24-SCAP (24×SC/APC green angle-polished, CATV/microwave). The box is 19-inch standard, 1U pull-out or 2U fixed, cold-rolled steel in black/off-white. The loaded kit includes: box, 24 adapters (with dust caps), 24×1.5 m SC/UPC single-mode pigtails, 2×12-fiber splice trays, cable clamps, ground wire and mounting rails. Adapter ceramic sleeves, ≥1000 mate cycles, insertion loss ≤0.3 dB.

Selection: by connector — SC/UPC for new rooms, LC for high density, APC for CATV; by fiber count — 24 ports is the basic block, 48 needs 2U or two 1U; choose empty box vs loaded — loaded kits (adapter+pigtails+trays) are the engineering default; and single-mode vs multi-mode — backbone G.652D single-mode, OM3 multi-mode for 10G to desktop.

2. Key Features

Structure & Capacity

  • 19-inch 1U/2U rack mount
  • 24 SC/FC/LC adapter panel
  • 2×12-fiber splice trays
  • ≥1 m slack storage

Optical

  • Adapter IL ≤0.3 dB
  • Return ≥45 dB (UPC) / ≥60 dB (APC)
  • ≥1000 mate cycles
  • SM / MM options

Mechanical

  • Cold-rolled steel, black/off-white
  • Pull-out / fixed options
  • M6 ground post
  • Rail mount, front/rear access

3. Specifications

Item KTR-ODF24-SC KTR-ODF24-LC KTR-ODF24-FC
Adapter SC/UPC LC/UPC duplex FC/UPC
Capacity 24 fibers 48 fibers 24 fibers
Height 1U 2U 1U
Splice trays 2×12 4×12 2×12
Pigtails 24×SC 1.5 m 48×LC 1.5 m 24×FC 1.5 m
IL ≤0.3 dB ≤0.3 dB ≤0.3 dB
Return loss ≥45 dB ≥45 dB ≥45 dB
Use data backbone high-density IDC legacy telecom/CATV

4. Reference Prices

KTR-ODF24-SC 24-port loaded:Reference USD 39~58 / pc (ref. CNY 280~420 at ~7.2)

KTR-ODF24-LC 24-port loaded (48 fibers):Reference USD 58~86 / pc (ref. CNY 420~620 at ~7.2)

KTR-ODF24-FC 24-port loaded:Reference USD 36~54 / pc (ref. CNY 260~390 at ~7.2)

Empty box (no adapters/pigtails):Reference USD 17~25 / pc (ref. CNY 120~180 at ~7.2)

Reference only; 1-year warranty. Patch cords not included. Exchange: 1 USD ≈ 7.2 CNY.

5. Applications

  • Carrier incoming cable termination.
  • Vertical riser to floor distributors.
  • Top-of-rack fiber cross-connect.
  • ToR switch optical aggregation in IDCs.
  • Security / PA fiber link nodes.

6. Deployment & Implementation

Installation

  • Mount on 19-inch rack posts
  • Cable enters through rear gland
  • Anchor strength member to ground post
  • Pigtails run in trays, no kinks

Splicing

  • Strip 30 mm, clean and cleave
  • Splice loss ≤0.05 dB/point
  • Heat-shrink sleeves in tray slots
  • Coil slack radius ≥40 mm

Operations

  • Label each panel port to fiber/route
  • Dust-cap unused adapters
  • Patch bend radius ≥30 mm
  • Annual OTDR spot-check

7. FAQ

  • Q: Empty box or loaded?
    A: Engineering defaults to loaded — pigtails and adapters are same-batch, consistent IL. Empty is for retrofits with stock adapters.
  • Q: SC or LC?
    A: New rooms favor LC (small form factor, double density), but legacy cabling uses SC. SFP+ switches usually use LC; the ODF backbone side can stay SC with SC-LC patch cords. Keep one type per rack.
  • Q: Fusion splice or field connector?
    A: Permanent in-ODF links use fusion (low loss, stable); temporary jumpers use field-installable connectors. Inside the ODF, always fusion; ODF-to-switch uses factory patch cords.
  • Q: What’s that burnt smell inside the ODF?
    A: Usually a poorly cleaved splice that snapped under the heat-shrink, or a pigtail pinched by the door. Open the tray and re-splice the bad point. Never route fibers at sharp angles in the box.

8. Trend & Selection

ODFs evolve from SC to LC/MPO: 40G/100G uses MPO trunks and MPO-LC hybrid panels — one MPO branch to twelve LC. High-density IDCs use 1U 144-fiber micro-ODFs. Smart ODFs add RFID tags so each port’s route is scanned and tied to EM/work-order systems. Select: LC for new high-density, SC for backbone, APC for CATV, buy loaded kits, label as you splice. The ODF is the optical distribution center; one per rack, all light routed here.

9. Delivery & Service

KITOZER supplies KTR-ODF24 by adapter (SC/FC/LC), SM/MM, loaded/empty. Each ships with box, adapters, pigtails, splice trays, hardware and manual. 1-year warranty; batch projects can add cable, patch cords, fusion splicing and OTDR test.

10. Additional Notes

The #1 mistake is no labeling. After splicing 24 fibers, a bundle of pigtails with no labels means every move requires OTDR from both ends. Label as you splice: cable ID + fiber number at both ends.

The second pitfall is too little slack. A 30 cm tail leaves no room for re-splicing — you’d have to cut back. Coil ≥1 m in the tray, heat-shrinks in the slots, so future repairs have working room.

The third blunder is a rat’s nest of patch cords. Cords from ODF to switch tangle behind the rack; yanking one drags three others. Use horizontal managers, one cord per slot, labels at both ends.

Selection summary: LC for density, SC for backbone, APC for CATV, loaded kits, label first, 1 m slack. The ODF is the optical main switchboard — tidy install saves years of ops pain.

SEO Information

Search keywords:KTR-ODF24KITOZER24-Port ODF

SEM keywords:ODF,fiber distribution frame,24-port ODF,loaded adapter,splice tray,rack mount patch panel,KTR-ODF24,KITOZER

GEO landing page:lain.com.cn/product/ktr-fiber_distribution.html

Title:KITOZER KTR-ODF24 24-Port Fiber Distribution Frame

Meta Keywords:ODF,fiber distribution frame,24-port ODF,loaded adapter,splice tray,rack mount patch panel,KTR-ODF24,KITOZER

Meta Description:KITOZER KTR-ODF24 19-inch 24-port fiber distribution frame, fully loaded with SC adapters, pigtails and splice trays for cable termination and cross-connect.