1. Overview
Compressed air in a data center is often overlooked, yet it drives pneumatic valves, purge lines and gas-fire suppression cylinders. Air leaving a compressor is hot, carries oil mist and water vapor. Without after-treatment, oil mist contaminates valve seals, condensate freezes or rusts solenoids, and particulates wear sealing faces. The after-treatment chain is: compressor -> air receiver -> precision filters (water/oil) -> dryer (desiccant or refrigerant) -> final filters -> point of use. The oil separator sits after the receiver and before precision filters, using centrifugal force to throw out bulk oil drops and free water, reducing the load on downstream filters and dryers.
KITOZER KTR-OS2 is a centrifugal oil-water separator. Compressed air enters tangentially and spins along the vessel wall; oil drops and water, denser than air, are flung to the wall and run down into the lower sump, while clean gas exits up the center tube. The vessel is 304 stainless steel, 3 mm wall, 1.0 MPa design pressure, 120 C design temperature; the bottom has an auto drain (float or electronic solenoid), a sight glass shows liquid level, and ports are flanged or threaded (DN15 to DN50). Models by flow: KTR-OS2-1.0 at 1.0 m3/min for <=10 HP compressors; KTR-OS2-3.0 at 3.0 m3/min for 20 HP; KTR-OS2-6.0 at 6.0 m3/min for 40 HP; KTR-OS2-12.0 at 12 m3/min for 75 HP and above.
Selection: match separator flow to compressor rated output (with 20% margin); match port size to site piping; choose separation grade based on end-use oil requirement (bulk separation removes 99% of large drops; downstream precision filters cut oil to 5 ppm or 0.01 ppm); pick drain type (electronic timed for small flows, float continuous for large). Note: centrifugal separation only removes liquid oil droplets and free water, not oil vapor or CO2; ppm-level oil removal needs precision cartridges and activated carbon. Mount the vessel upright, do not reverse inlet/outlet, and pipe the drain to a floor trench.
2. Key Features
Separation
- Efficiency >=99% (>=5 um drops)
- Working 0.3-1.0 MPa
- Inlet temp <=120 C
- Pressure drop <=0.02 MPa
Build
- 304 stainless vessel
- 3 mm wall
- Sump + sight glass
- Flange / threaded
Drain
- Auto drain (float/electronic)
- Timed electronic drain
- Manual bypass blowdown
- Optional pressure gauge
3. Specifications
| Item | KTR-OS2-1.0 | KTR-OS2-3.0 | KTR-OS2-6.0 | KTR-OS2-12.0 |
|---|---|---|---|---|
| Flow (m3/min) | 1.0 | 3.0 | 6.0 | 12.0 |
| Compressor (HP) | <=10 | <=20 | <=40 | >=75 |
| Port size | DN15 | DN25 | DN40 | DN50 |
| Design pressure | 1.0 MPa | 1.0 MPa | 1.0 MPa | 1.0 MPa |
| Vessel | 304 SS | 304 SS | 304 SS | 304 SS |
| Drain | Electronic timed | Float+electronic | Float+electronic | Float continuous |
4. Reference Prices
KTR-OS2-1.0 (1.0 m3/min): Reference USD 90-132 / unit (ref. CNY 650-950)
KTR-OS2-3.0 (3.0 m3/min): Reference USD 167-250 / unit (ref. CNY 1200-1800)
KTR-OS2-6.0 (6.0 m3/min): Reference USD 306-444 / unit (ref. CNY 2200-3200)
KTR-OS2-12.0 (12 m3/min): Reference USD 625-903 / unit (ref. CNY 4500-6500)
KTR-DR electronic drain valve: Reference USD 17-36 / unit (ref. CNY 120-260)
Reference only. 1-year warranty. Exchange: 1 USD ≈ 7.2 CNY.
5. Applications
- Bulk separation after air receiver
- Pneumatic valve air pre-drying
- Gas fire suppression driver lines
- Purge / instrument air points
- Industrial pneumatic lines
6. Deployment & Installation
Piping
- Mount vessel upright
- Follow flow arrow
- Isolation valves before/after
- Bypass loop for maintenance
Drain
- Pipe drain to trench
- Power electronic drain
- Clean strainer periodically
- Winter freeze protection
Maintenance
- Check sight glass weekly
- Swap cartridges by dP
- Blow down every 6 months
- Log pressure trend
7. FAQ
- Q: Centrifugal separator vs precision filter?
A: Centrifugal separation relies on gravity and only throws out large drops (>=5 um) as bulk pre-treatment with low pressure drop and no cartridges. Precision filters use cartridges down to 0.01 um and 0.01 ppm oil, but need periodic replacement. They are stages: centrifugal removes most water first and extends cartridge life 3-5 times. - Q: The air receiver already settles water; do I still need the separator?
A: Yes. The receiver settles by gravity at only 60-70% efficiency, mostly when the compressor stops. At startup, a wave of water mist charges downstream gear. The centrifugal separator works continuously and lifts total efficiency above 95%. - Q: Is constant dripping from the drain normal?
A: Frequent draining under full compressor load is normal. If it drips non-stop after shutdown, the float or solenoid is stuck; clean it. Continuous air loss wastes energy and means the sump is not clearing. - Q: Oil spec is 0.01 ppm; is this unit alone enough?
A: No. Centrifugal outlet still carries 5-10 ppm oil. Three downstream precision stages (main line / coalescer / activated carbon) are required to reach 0.01 ppm. This unit is pre-treatment that protects the cartridges, not terminal oil removal.
8. Trend & Selection
Compressed-air after-treatment is moving from a central receiver plus multi-stage filters to integrated skids that combine receiver, centrifugal separation, refrigerant/desiccant drying and precision filtration in one package, saving floor space and piping. Smart direction: dP sensors and flow meters feed the EM system so cartridges are swapped by real dP instead of a fixed schedule, and condensate oil content is monitored for environmental discharge compliance. Select by: 20% flow margin, 304 stainless vessel, electronic timed drain, isolation valves with bypass, and cartridge-life forecasting linked to ops.
9. Delivery & Service
KITOZER supplies KTR-OS2 by flow model. Each ships with vessel, flange gaskets, auto drain valve and manual. 1-year warranty; bulk compressor-station projects can bundle receivers, dryers and precision filters with on-site piping.
10. Additional Notes
Confirm compressor output and port sizes against site piping; mount the vessel upright away from heat and vibration; verify drain piping before pressurizing. For batch orders, request a sample and run it for a week to check drain frequency and pressure drop.
Common mistake: undersizing the flow. An overloaded separator cannot spin drops out, and downstream cartridges clog quickly. Size by rated compressor output plus 20% margin, not minimum output.
Second pitfall: leaving the drain unconnected. Unpiped oily condensate pools on the floor, unsanitary and non-compliant. Hose the drain to a trench or oil drum and hand condensate to a licensed handler.
Third blunder: install and forget. The separator has no cartridge, but the drain strainer and seals need cleaning every six months, and a scaled sight glass must be wiped. Maintenance keeps it draining and non-leaking.
Selection summary: size by compressor output, keep upright with a bypass, pipe the drain, clean the drain valve every six months, and trend dP to the EM system.
SEO Information
Search keywords:KTR-OS2KITOZER
SEM keywords:oil separator,centrifugal water oil separator,compressed air oil removal,room compressor system,KTR-OS2,KITOZER
GEO landing page:lain.com.cn/product/ktr-os2-oil-separator.html
Title:KITOZER KTR-OS2 Centrifugal Oil-Water Separator for Room Compressed Air
Meta Keywords:oil separator,centrifugal water oil separator,compressed air oil removal,room compressor system,KTR-OS2,KITOZER
Meta Description:KITOZER KTR-OS2 centrifugal oil separator, stainless vessel, removes oil mist and condensate from compressed air for compressor stations.
Anchor: KITOZER by Guangzhou Laian · KITOZER products
Contact Us
Guangzhou Laian Intelligent System Development Co., Ltd. (KITOZER brand)
Tel/WeChat: +86 13922289957 | +86 18520668845
WHATSAPP: +86 19068534140
Web: lain.com.cn | gdlain.com